Andersons Trailer Court
What EPA’s and Wisconsin’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 95 people
- Connections
- 35
- Water source
- Groundwater
- Based in
- Rice Lake, WI
- County
- Barron
- Owner
- Private
- Hardness
- Moderately hard
The short answer
Nothing in EPA’s and Wisconsin’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 2 health-based violations since 2016.
What was found
Chromium (total), nitrate and arsenic: Wisconsin’s own results, samples taken from Sept. 9, 2020 to July 23, 2026, with EPA’s 2012 to 2019 file for earlier years.
Fluoride: EPA’s compliance monitoring file, samples taken from Sept. 17, 2018 to Sept. 17, 2018. Newer results are in the utility’s annual water quality report.
Below EPA’s limits2
Chromium (total)
Comes from the source
1.3ppb
Highest yearly average, 2026
Averaged by year, the highest was 1.3 ppb, in 2026, below EPA’s legal limit of 100 ppb. That is the only year on file.
What handles it
- NSF/ANSI 58 look for “Chromium (Hexavalent) Reduction”
- NSF/ANSI 53 look for “Chromium Reduction”
Nitrate
Comes from the source
0.088ppm
Highest sample; found in 2 of 3
2022, one sample: 0.075 ppm
The highest sample, in 2021, was 0.088 ppm, below EPA’s legal limit of 10 ppm. In 2022, the latest year on file, its one sample was 0.075 ppm.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
3 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
- Arsenic
- Fluoride
- Lead
Hardness
Moderately hard, typically 78 mg/L (4.6 grains per gallon), across 2 sampling points, 2018 to 2026.
Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.
Violations since 2016
| Contaminant or rule | Type | Period | Measured | Status |
|---|---|---|---|---|
| Revised Total Coliform Rule | Coliform results required a check of the system, and the check or its fixes were not done on time.EPA: Treatment Technique, Level 1 Assessment (RTCR) | Nov. 16, 2025 | — | Resolved |
| Lead and Copper Rule Revisions | The required inventory of lead service lines was not completed or submitted on time.EPA: LSL Inventory | Oct. 17, 2024 | — | Resolved |
| Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 27 monitoring or reporting violations not shown. | ||||
What this report can’t tell you
Everything else. Chromium (total), nitrate and arsenic results here are Wisconsin’s own from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride comes from EPA’s file alone, which ends in 2019. Andersons Trailer Court’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Wisconsin’s results run from Sept. 9, 2020 to July 23, 2026; EPA’s compliance samples are from Sept. 17, 2018 to Sept. 17, 2018.
Testing your own tap
No lab Wisconsin certifies is within 75 miles of the area Andersons Trailer Court serves on the state’s list. Some take samples by mail; the state’s page lists them all.
Wisconsin State Laboratory of Hygiene: Well water test kits ordered by phone and shipped free; you pay to mail the sample back, and the lab bills you after testing. Tests run from bacteria alone to a homeowner package covering bacteria, nitrate, fluoride, metals, hardness, volatile organic compounds and atrazine. Bacteria is $35, nitrate $35, lead $38, and the homeowner package $450, as of July 1, 2026. Public Environmental and Water Testing Prices, Wisconsin State Laboratory of Hygiene.
All 156 certified labs for WisconsinSources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Wisconsin Department of Natural Resources, Drinking Water Program, results from Jan. 2, 2020 to Oct. 5, 2026, read Oct. 8, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Hardness: Wisconsin Department of Natural Resources, Drinking Water Program, results from Sept. 17, 2018 to July 23, 2026, read Oct. 10, 2026
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID WI6030140. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Nothing here is above a health goalIn EPA’s and Wisconsin’s records for this utility. They don’t cover everything, which is why the next step matters.Every contaminant TapBuff tracks
- Get the utility’s own reportAndersons Trailer Court must send you a water quality report every year. It covers contaminants this page does not show, and has newer results than EPA’s national file for the ones here that come from it.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded