Mdwasa/Rex UtilitiesWater quality report

Standards for what was found here

5358
Serves
45,200
Connections
12,700
Water source
Groundwater
Based in
Miami, FL
County
Miami - Dade
Owner
Local government
The 15 ZIP codes it serves

33010, 33014, 33015, 33016, 33018, 33030, 33031, 33032, 33033, 33034, 33035, 33039, 33054, 33055, 33056

PWSID FL4131202 · EPA data

Read this first

  • PFOS was found in 10 of 10 samples, highest 37.4 ppt. Above the 4.0 ppt legal limit in at least one sample. Compliance is judged on a running annual average, not one sample.
  • PFOA was found in six of 10 samples, highest 10.6 ppt. Above the 4.0 ppt legal limit in at least one sample. Compliance is judged on a running annual average, not one sample.
  • Lead In the latest period, 9 in 10 homes sampled were at or below 1.0 ppb, below the 15 ppb action level. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

No health-based violations on file since 2016. EPA lists 14 monitoring or reporting violations, which are paperwork and testing lapses rather than water quality findings.

What handles it

What was found, stop by stop

  • Below the health goal
  • Above the health goal
  • Above the legal limit
  • No federal data
  1. At the source

    EPA UCMR 5 sampled this utility for 29 PFAS and lithium from Feb. 11, 2025 to Aug. 12, 2025. Each tick under a result’s line is one sample where it was found, dated when you point at it.

    NSF’s PFAS claims are tested to below 20 ppt. EPA’s limit is 4.0 ppt, and EPA says no certification yet shows a filter reaching its levels.

  2. PFOS

    Above the legal limit

    37.4ppt

    Highest of 10 samples; found in 10

    Above the 4.0 ppt legal limit in at least one sample. Compliance is judged on a running annual average, not one sample.

    • NSF/ANSI 53 · Look for: PFOS ReductionSame claim, other certifiers’ wording: Total PFAS Reduction; Perfluorooctane Sulfonate (PFOS)

    • NSF/ANSI 58 · Look for: Perfluorooctane Sulfonate (PFOS)

  3. PFOA

    Above the legal limit

    10.6ppt

    Highest of 10 samples; found in six

    Above the 4.0 ppt legal limit in at least one sample. Compliance is judged on a running annual average, not one sample.

    • NSF/ANSI 53 · Look for: PFOA ReductionSame claim, other certifiers’ wording: Total PFAS Reduction; Perfluorooctanoic Acid (PFOA)

    • NSF/ANSI 58 · Look for: Perfluorooctanoic Acid (PFOA)

  4. PFHxS

    Below the health goal

    3.8ppt

    Highest of 10 samples; found in five

    Detected, below the legal limit and the health goal.

    • NSF/ANSI 53 · Look for: Total PFAS ReductionSame claim, other certifiers’ wording: Perfluorohexane Sulfonic Acid (PFHxS)

  5. PFBS

    Below the benchmark

    17ppt

    Highest of 10 samples; found in 10

    Below EPA’s hazard index benchmark of 2,000 ppt. PFBS has no legal limit or health goal of its own.

  6. Also found, with no federal limit

    EPA measured these PFAS to learn how often they occur. None has a legal limit or a health goal yet.

    CompoundHighest sampleFound inCertification claim
    PFPeA14.6 ppt6 of 10None covers it
    PFHxA11.1 ppt6 of 10None covers it
    PFBA9.8 ppt9 of 10None covers it
    PFHpA6.6 ppt6 of 10NSF/ANSI 53: Total PFAS Reduction
  7. In treatment

    No federal results for this stop. Disinfection byproduct, chlorine and fluoride levels are in Mdwasa/Rex Utilities’s own annual report, which it must send you every year.

  8. In the pipes

    Lead and copper, from the homes the utility samples. Your own service line, solder and fixtures decide yours.

  9. Lead

    Above the health goal

    1.0ppb

    90th percentile, 2023

    In the latest period, 9 in 10 homes sampled were at or below 1.0 ppb, below the 15 ppb action level. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

    EPA SDWIS, lead and copper monitoring periods ending 2000 to 2023. The line stops at the latest period; each tick under it is an earlier one.

  10. At your tap

    The last stretch is your own plumbing. A certified lab test is the only way to know what reaches your glass. Lead in your water: what to do

Tested and not found

Below EPA’s minimum reporting level in every sample taken from Feb. 11, 2025 to Aug. 12, 2025. Not found means not measured above that level, which is not the same as zero.

All 22 compounds tested and not found
  • 11Cl-PF3OUdS
  • 4:2 FTS
  • 6:2 FTS
  • 8:2 FTS
  • 9Cl-PF3ONS
  • ADONA
  • HFPO-DA (GenX)
  • Lithium
  • NEtFOSAA
  • NFDHA
  • NMeFOSAA
  • PFDA
  • PFDoA
  • PFEESA
  • PFHpS
  • PFMBA
  • PFMPA
  • PFNA
  • PFPeS
  • PFTA
  • PFTrDA
  • PFUnA

Violations since 2016

No health-based violations on file with EPA since 2016. There are 14 monitoring or reporting violations: a sample missed, late or not reported.

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: PFOS Reduction, PFOA Reduction, Lead Reduction

    For: PFOS, PFOA, Lead

  • NSF/ANSI 58

    Claims: Perfluorooctane Sulfonate (PFOS), Perfluorooctanoic Acid (PFOA), Lead Reduction

    For: PFOS, PFOA, Lead

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Compare five-year costs

Filters with those claims on a certifier’s listing

TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

What this report cannot tell you

  • Levels of everything else. Federal bulk data carries results for PFAS, lithium, lead and copper, and violations for the rest. Nitrate, arsenic, disinfection byproducts and other levels are in Mdwasa/Rex Utilities’s own annual report, which it must send you every year.
  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
  • Anything after the latest data. SDWIS data is from 2026 Q2; UCMR 5 samples are from Feb. 11, 2025 to Aug. 12, 2025.

What to do next

  1. Start with PFOS

    What each marked result does to health, where it comes from, and the certification claim that addresses it.

  2. Read the utility’s own report

    Mdwasa/Rex Utilities must send you a water quality report every year. It lists nitrate, arsenic and byproduct levels this page cannot.

  3. Test your own tap for lead

    Your service line, solder and fixtures decide the lead at your faucet, not the utility’s average.

  4. Compare five-year costs

    What the filters certified for these results cost over five years, cartridges included.