Skip to content
TapBuff

West Bountiful City Water System

EPA’s and Utah’s records have results for 37 contaminants in its water; 6 were found.

Serves 5,600 people · Surface water bought from another system · Woods Cross, UT · Hardness: moderately hard

Serves
5,600 people
Connections
1,897
Water source
Surface water bought from another system
Based in
Woods Cross, UT
County
Davis
Owner
Local government
Hardness
Moderately hard
The ZIP code it serves

84087

The short answer

None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. No health-based violations on file since 2016.

Filters for lead, if you want it lower⁠

What was found

Where these results come from, and when

PFAS and lithium: EPA UCMR 5, samples taken from Jan. 24 to Oct. 18, 2023.

Lead and copper: EPA SDWIS monitoring periods ending 2004 to 2025.

Nitrate, fluoride, arsenic and chromium (total): Utah’s own results, samples taken from Jan. 10, 2020 to Jan. 8, 2026, with EPA’s 2012 to 2019 file for earlier years.

Total trihalomethanes (TTHM) and haloacetic acids (HAA5): EPA’s compliance monitoring file, samples taken from Oct. 19, 2012 to Nov. 18, 2019. Newer results are in the utility’s annual water quality report.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.
Health reference level:
A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.

PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.

Below EPA’s limits, 6 results

Lead has a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health reference level:
A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
Lithium, Health reference level 10 ppbAt EPA’s benchmark, as EPA rounds; highest 14.5 ppb

Highest sample, Jan. 24, 2023; found in 6 of 6 · Comes from the source

The highest sample was 14.5 ppb. As EPA rounds results, that is at EPA’s health reference level of 10 ppb, not above it: EPA counts a result as above it from 15 ppb.

What handles it

No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.

How to read your utility’s report
About lithium
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 46.9 ppb

Highest yearly average, 2012 to 2019 · 2019 average: 15.3 ppb · Forms or is added in treatment

Averaged by year, the highest was 46.9 ppb, in 2014, below EPA’s legal limit of 80 ppb. Its highest single sample was 60.3 ppb. In 2019, the latest year on file, its eight samples averaged below the limit.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
About total trihalomethanes (TTHM)
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 30.1 ppb

Highest yearly average, 2012 to 2019 · 2019 average: 5.8 ppb · Forms or is added in treatment

Averaged by year, the highest was 30.1 ppb, in 2014, below EPA’s legal limit of 60 ppb. Its highest single sample was 36.7 ppb. In 2019, the latest year on file, its eight samples averaged below the limit.

What handles it

No certification claim covers this compound yet.

About haloacetic acids (HAA5)
Nitrate, Legal limit 10 ppm; highest 2.9 ppm

Highest sample; found in 10 of 10 · 2026, one sample: 2.1 ppm · Comes from the source

The highest sample, in 2020, was 2.9 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest sample of 3.3 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
Lead, Action level 15 ppb · health goal zero; 90th percentile 2.2 ppb

90th percentile, 2023 to 2025 · Comes from pipes, often your own

In the latest period, 9 in 10 homes sampled were at or below 2.2 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

About lead
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.15 ppm

Highest yearly average, 2020 to 2026 · 2026: not found · Forms or is added in treatment

Averaged by year, the highest was 0.15 ppm, in 2024, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, it wasn’t found in its one sample.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.82 ppm, in 2016.

What handles it

About fluoride
Utilities above EPA’s PFAS limits, state by state⁠
31 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.

From routine monitoring

  • Arsenic
  • Chromium (total)

PFAS and lithium, from EPA’s UCMR 5 sampling

  • 11Cl-PF3OUdS
  • 4:2 FTS
  • 6:2 FTS
  • 8:2 FTS
  • 9Cl-PF3ONS
  • ADONA
  • HFPO-DA (GenX)
  • NEtFOSAA
  • NFDHA
  • NMeFOSAA
  • PFBA
  • PFBS
  • PFDA
  • PFDoA
  • PFEESA
  • PFHpA
  • PFHpS
  • PFHxA
  • PFHxS
  • PFMBA
  • PFMPA
  • PFNA
  • PFOA
  • PFOS
  • PFPeA
  • PFPeS
  • PFTA
  • PFTrDA
  • PFUnA

Violations since 2016

No health-based violations on file with EPA since 2016. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Skip past the filters

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

2 more filters
Compare five-year costs

Every filter certified for it⁠

The best water filters for lead, ranked⁠

Hardness

Moderately hard, 108 mg/L (6.3 grains per gallon), at its one sampling point, in 2019.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

Disinfectant

West Bountiful City Water System reported disinfecting with chlorine, not chloramine, at all 2 of its sampling points, in its 2023 sampling for EPA.

What that means

Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This utility buys its water from another system, so what it reported may leave out treatment done before the water reaches it. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.

What this report can’t tell you

  • Everything else. Nitrate, fluoride, arsenic and chromium (total) results here are Utah’s own from 2020 on, with EPA’s national file for 2012 to 2019. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) come from EPA’s file alone, which ends in 2019. West Bountiful City Water System’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Jan. 24 to Oct. 18, 2023; Utah’s results run from Jan. 10, 2020 to Jan. 8, 2026; EPA’s compliance samples are from Oct. 19, 2012 to Nov. 18, 2019.

Testing your own tap

West Bountiful City Water System’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Utah certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. West Bountiful City Water System’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 2.2 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Utah certifies closest to the area West Bountiful City Water System serves, or a kit by mail

The 3 labs Utah certifies closest to the area West Bountiful City Water System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Central Valley Water Relamation Facility

    South Salt Lake, UT · about 13 miles

    Certified for bacteria, lead and copper, metals, minerals and other inorganics

    (801) 973-9100

  • Utah Department of Health Division of Lab Services (EPA cert.)

    Taylorsville, UT · about 15 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, disinfection byproducts, PFAS

    (801) 965-2400

  • Rio Tinto Kennecott Environmental and Industrial Hygiene Laboratory

    Magna, UT · about 15 miles

    Certified for nitrate, lead and copper, metals, minerals and other inorganics

    (801) 569-7952

All 60 certified labs for Utah⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Utah certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Utah’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID UTAH06014. Rebuilt from EPA data on Oct. 25, 2026.