What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 250 people
- Connections
- 90
- Water source
- Surface water bought from another system
- Based in
- North Vernon, IN
- County
- Jennings
- Owner
- Private
The short answer
Nothing in EPA’s and CDC’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 6 health-based violations since 2016.
What was found
Total trihalomethanes (TTHM) and haloacetic acids (HAA5): Indiana’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2022 to 2023, with EPA’s 2012 to 2019 file for earlier years.
Below EPA’s limits2
Total trihalomethanes (TTHM)
Forms or is added in treatment
62.6ppb
Highest yearly average, 2022 to 2023
Averaged by year, the highest was 62.6 ppb, in 2023, below EPA’s legal limit of 80 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 92.9 ppb, in 2015, and EPA recorded a violation in 2017.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5)
Forms or is added in treatment
42.4ppb
Highest yearly average, 2022 to 2023
Averaged by year, the highest was 42.4 ppb, in 2023, below EPA’s legal limit of 60 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 98.3 ppb, in 2015, and EPA recorded violations in 2017, 2018 and 2019.
What handles it
No certification claim covers this compound yet.
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
- Lead
Violations since 2016
| Contaminant or rule | Type | Period | Measured | Status |
|---|---|---|---|---|
| Lead and Copper Rule Revisions | The required inventory of lead service lines was not completed or submitted on time.EPA: LSL Inventory | Oct. 17, 2024 | — | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2019 to March 31, 2019 | 67.8 UG/L | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2018 to Dec. 31, 2018 | 64.7 UG/L | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2017 to Dec. 31, 2017 | 73.4 UG/L | Resolved |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2017 to Sept. 30, 2017 | 84.7 UG/L | Resolved |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2017 to Sept. 30, 2017 | 72.7 UG/L | Resolved |
| Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 38 monitoring or reporting violations not shown. | ||||
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are Indiana’s yearly averages as CDC publishes them, from 2022 on, with EPA’s national file for 2012 to 2019. Hickory Manor Mobile Home Park’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for Indiana cover 2022 to 2023.
Testing your own tap
No lab Indiana certifies is within 75 miles of the area Hickory Manor Mobile Home Park serves on the state’s list. Some take samples by mail; the state’s page lists them all.
Indiana Department of Health laboratory: Test kits for well water: nitrate, fluoride, and arsenic, lead and copper, ordered from the lab and returned by mail. They are open to the public. Nitrate is $10 a sample plus $6.50 shipping per order, fluoride $10 plus shipping, and the arsenic, lead and copper kit $20 plus $6.50 shipping. Water Testing, Indiana Department of Health.
All 81 certified labs for IndianaSources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- CDC Environmental Public Health Tracking Network, yearly averages Indiana supplied to CDC, 2022 to 2023, read Oct. 8, 2026. TapBuff’s comparisons with EPA’s limits are its own, not CDC’s or Indiana’s.
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID IN5240012. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Nothing here is above a health goalIn EPA’s and CDC’s records for this utility. They don’t cover everything, which is why the next step matters.Every contaminant TapBuff tracks
- Get the utility’s own reportHickory Manor Mobile Home Park must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded