Skip to content
TapBuff

Hickory Manor Mobile Home Park

What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
250 people
Connections
90
Water source
Surface water bought from another system
Based in
North Vernon, IN
County
Jennings
Owner
Private

The short answer

Nothing in EPA’s and CDC’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 6 health-based violations since 2016.

What was found

Total trihalomethanes (TTHM) and haloacetic acids (HAA5): Indiana’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2022 to 2023, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits2

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

62.6ppb

Highest yearly average, 2022 to 2023

Averaged by year, the highest was 62.6 ppb, in 2023, below EPA’s legal limit of 80 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 92.9 ppb, in 2015, and EPA recorded a violation in 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

42.4ppb

Highest yearly average, 2022 to 2023

Averaged by year, the highest was 42.4 ppb, in 2023, below EPA’s legal limit of 60 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 98.3 ppb, in 2015, and EPA recorded violations in 2017, 2018 and 2019.

What handles it

No certification claim covers this compound yet.

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Resolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2019 to March 31, 201967.8 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 201864.7 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2017 to Dec. 31, 201773.4 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 201784.7 UG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 201772.7 UG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 38 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are Indiana’s yearly averages as CDC publishes them, from 2022 on, with EPA’s national file for 2012 to 2019. Hickory Manor Mobile Home Park’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for Indiana cover 2022 to 2023.

Testing your own tap

Hickory Manor Mobile Home Park’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Indiana certifies.

No lab Indiana certifies is within 75 miles of the area Hickory Manor Mobile Home Park serves on the state’s list. Some take samples by mail; the state’s page lists them all.

Indiana Department of Health laboratory: Test kits for well water: nitrate, fluoride, and arsenic, lead and copper, ordered from the lab and returned by mail. They are open to the public. Nitrate is $10 a sample plus $6.50 shipping per order, fluoride $10 plus shipping, and the arsenic, lead and copper kit $20 plus $6.50 shipping. Water Testing, Indiana Department of Health.

All 81 certified labs for Indiana

Sources

PWSID IN5240012. Rebuilt from EPA data on Oct. 18, 2026.