Fairbury
EPA’s and Illinois’s records have results for 37 contaminants in its water; 4 were found.
Serves 3,633 people · Groundwater · Fairbury, IL · Hardness: hard
- Serves
- 3,633 people
- Connections
- 1,749
- Water source
- Groundwater
- Based in
- Fairbury, IL
- County
- Livingston
- Owner
- Local government
- Hardness
- Hard
The ZIP code it serves
The short answer
None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. 1 health-based violation since 2016, resolved in EPA’s file.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from March 5 to Sept. 24, 2024.
Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic and chromium (total): Illinois’s own results, samples taken from Feb. 24, 2020 to Aug. 12, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Health goal (MCLG):
- Not enforceable. The level with no expected risk, with a margin of safety.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
Below EPA’s limits, 4 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 46.4 ppb
Highest yearly average, 2020 to 2026 · 2026, one sample: 34.3 ppb · Forms or is added in treatment
Averaged by year, the highest was 46.4 ppb, in 2024, below EPA’s legal limit of 80 ppb. Its highest single sample was 47.4 ppb. In 2026, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 42 ppb, in 2018.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 15 ppb
Highest yearly average, 2020 to 2026 · Forms or is added in treatment
Averaged by year, the highest was 15 ppb, in 2026, below EPA’s legal limit of 60 ppb. That was also the latest year on file.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 10.7 ppb, in 2019.
What handles it
No certification claim covers this compound yet.
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.71 ppm
Highest yearly average, 2021 to 2024 · 2024, one sample: 0.57 ppm · Forms or is added in treatment
Averaged by year, the highest was 0.71 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. In 2024, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 1.2 ppm, in 2015.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Nitrate, Legal limit 10 ppm; highest 0.93 ppm
Highest sample; found in 6 of 7 · 2026: not found · Comes from the source
The highest sample, in 2020, was 0.93 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, it wasn’t found in its one sample.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest sample of 0.88 ppm, in 2013.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
33 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Arsenic
- Chromium (total)
- Lead
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- Lithium
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
1 health-based violation since 2016 for the Lead and Copper Rule Revisions. It began Oct. 17, 2024.
- Resolved:
- EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
- No fix on record:
- It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).
EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Got a notice about one? What it means and what to do| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Lead and Copper Rule Revisions | The required inventory of lead service lines was not completed or submitted on time.EPA: LSL Inventory | Oct. 17, 2024 | Resolved |
Health-based violations only.
Hardness
Hard, 140 mg/L (8.2 grains per gallon), at its one sampling point, 2018 to 2024.
Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.
Disinfectant
Fairbury reported disinfecting with chlorine, not chloramine, at its one sampling point, in its 2024 sampling for EPA.
What that means
Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic and chromium (total) results here are Illinois’s own from 2020 on, with EPA’s national file for 2012 to 2019. Fairbury’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from March 5 to Sept. 24, 2024; Illinois’s results run from Feb. 24, 2020 to Aug. 12, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Fairbury’s latest lead sampling in EPA’s records, 2025, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Illinois certifies closest to the area Fairbury serves, or a kit by mail
The 3 labs Illinois certifies closest to the area Fairbury serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Key Laboratory Services, Inc.
Monticello, IL · about 49 miles
Certified for bacteria
Test, Inc.
Peru, IL · about 52 miles
Certified for bacteria
Will County Health Department
Joliet, IL · about 58 miles
Certified for bacteria
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Illinois certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Illinois’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded
- Get the utility’s own reportFairbury must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Illinois Environmental Protection Agency, Bureau of Water, results from Jan. 2, 2020 to Oct. 13, 2026, read Oct. 17, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: Illinois Department of Public Health, certified water microbiology laboratories, read Oct. 10, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Hardness: Illinois Environmental Protection Agency, Bureau of Water, results from Oct. 10, 2018 to Oct. 9, 2024, read Oct. 17, 2026
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID IL1050350. Rebuilt from EPA data on Oct. 25, 2026.