Skip to content
TapBuff

Valley Mobile Home LLC

What EPA’s and Colorado’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
85 people
Connections
28
Water source
Groundwater
Based in
Carbondale, CO
County
Alamosa
Owner
Private
Hardness
Moderately hard
The ZIP code it serves

81101

The short answer

2 results are above EPA’s legal limit. The worst: Arsenic, above the legal limit. 37 health-based violations since 2016.

What handles it

What was found

Arsenic, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, chromium (total) and uranium: Colorado’s own results, samples taken from Feb. 10, 2020 to Sept. 2, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit2

Arsenic

Comes from the source

Above the legal limit

20.3ppb

Highest yearly average, 2020 to 2026

2026 average: 13.3 ppb

Averaged by year, the highest was 20.3 ppb, in 2023, about twice EPA’s legal limit of 10 ppb. Its highest single sample was 24 ppb. In 2026, the latest year on file, its 12 samples averaged 13.3 ppb, above the limit. EPA recorded violations for arsenic at this utility in 2020, 2021, 2022, 2023 and 2024. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 16.4 ppb, in 2019, and EPA recorded violations in 2013, 2014, 2018 and 2019.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

88.7ppb

Highest yearly average, 2020 to 2026

2026 average: 30.2 ppb

Averaged by year, the highest was 88.7 ppb, in 2020, above EPA’s legal limit of 80 ppb. Its highest single sample was 133 ppb. In 2026, the latest year on file, its three samples averaged 30.2 ppb. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2020 and 2021. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 99.7 ppb, in 2015, and EPA recorded violations in 2017 and 2018.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Below EPA’s limits4

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

38.4ppb

Highest yearly average, 2020 to 2026

2026 average: 18.6 ppb

Averaged by year, the highest was 38.4 ppb, in 2020, below EPA’s legal limit of 60 ppb. Its highest single sample was 62.8 ppb. In 2026, the latest year on file, its three samples averaged 18.6 ppb. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 48.5 ppb, in 2014.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.9ppm

Highest yearly average, 2022 to 2026

2026, one sample: 0.76 ppm

Averaged by year, the highest was 0.9 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its one sample was 0.76 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.0 ppm, in 2019.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.93ppm

Highest sample; found in 2 of 7

2026, one sample: 0.021 ppm

The highest sample, in 2024, was 0.93 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was 0.021 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 1.1 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

3.0ppb

Highest yearly average, 2022 to 2026

Averaged by year, the highest was 3.0 ppb, in 2026, below EPA’s legal limit of 100 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.0 ppb, in 2016.

What handles it

2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead
  • Uranium

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Trihalomethanes (TTHM) Reduction

    For: Arsenic, Total trihalomethanes (TTHM)

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level); VOC Reduction

  • NSF/ANSI 58

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Trihalomethanes (TTHM) Reduction

    For: Arsenic, Total trihalomethanes (TTHM)

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Hardness

Moderately hard, typically 66 mg/L (3.9 grains per gallon), across 2 sampling points, in 2025.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyAug. 3, 2024—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyAug. 3, 2024—Addressed
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 20240.011 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2024 to March 31, 20240.017 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2023 to Dec. 31, 20230.02 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2023 to Sept. 30, 20230.022 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2023 to June 30, 20230.024 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2023 to March 31, 20230.019 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2022 to Dec. 31, 20220.018 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2022 to Sept. 30, 20220.018 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2022 to June 30, 20220.016 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2022 to March 31, 20220.015 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2021 to Dec. 31, 20210.015 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 20210.098 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 20210.013 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2021 to June 30, 20210.013 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2021 to June 30, 20210.093 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2021 to March 31, 20210.092 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2021 to March 31, 20210.013 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2020 to Dec. 31, 20200.089 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2020 to Dec. 31, 20200.015 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2020 to Sept. 30, 20200.015 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 20200.018 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2020 to March 31, 20200.017 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2019 to Dec. 31, 20190.016 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 201916 UG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2019 to June 30, 201913.3 UG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2019 to March 31, 201912.5 UG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 201811.8 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 201882.1 UG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2018 to Sept. 30, 20180.012 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2018 to June 30, 20180.11 MG/LResolved
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2018 to June 30, 20180.013 MG/LResolved
Stage 1 Disinfectants and Disinfection Byproducts RuleTreatment was not run by a certified operator as required.EPA: Treatment Technique No Certif. OperatorMarch 11, 2018—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2018 to March 31, 201895.5 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2017 to Dec. 31, 20170.099 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 20170.089 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 127 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Arsenic, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, chromium (total) and uranium results here are Colorado’s own from 2020 on, with EPA’s national file for 2012 to 2019. Valley Mobile Home LLC’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Colorado’s results run from Feb. 10, 2020 to Sept. 2, 2026.

Testing your own tap

Valley Mobile Home LLC’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Colorado certifies.

The lab Colorado certifies closest to the area Valley Mobile Home LLC serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Sangre De Cristo Laboratory

    Alamosa, CO · under a mile

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

All 54 certified labs for Colorado

Sources

PWSID CO0102300. Rebuilt from EPA data on Oct. 18, 2026.