Skip to content
TapBuff

Rancho Murieta Community Servi

EPA’s and California’s records have results for 37 contaminants in its water; 2 were found.

Serves 5,728 people · Surface water · Rancho Murieta, CA · Hardness: soft

Serves
5,728 people
Connections
2,921
Water source
Surface water
Based in
Rancho Murieta, CA
County
Sacramento
Owner
Local government
Hardness
Soft
The ZIP code it serves

95683

The short answer

None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. 1 health-based violation since 2016, resolved in EPA’s file.

The violation⁠Got a notice? What it means⁠

What was found

Where these results come from, and when

PFAS and lithium: EPA UCMR 5, samples taken from Jan. 7 to Oct. 8, 2025.

Total trihalomethanes (TTHM), fluoride, arsenic, chromium (total), nitrate and uranium: California’s own results, samples taken from Jan. 8, 2020 to May 19, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.

PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.

Below EPA’s limits, 2 results

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 7.5 ppb

Highest yearly average, 2020 to 2026 · 2026: not found · Forms or is added in treatment

Averaged by year, the highest was 7.5 ppb, in 2021, below EPA’s legal limit of 80 ppb. Its highest single sample was 15 ppb. In 2026, the latest year on file, it wasn’t found in its one sample.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 14 ppb, in 2014, and EPA recorded a violation in 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
About total trihalomethanes (TTHM)
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.13 ppm

Highest yearly average, 2020 to 2025 · 2025: not found · Forms or is added in treatment

Averaged by year, the highest was 0.13 ppm, in 2020, below EPA’s legal limit of 4.0 ppm. In 2025, the latest year on file, it wasn’t found in any of its two samples.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.11 ppm, in 2014.

What handles it

About fluoride
California utilities above EPA’s PFAS limits⁠
35 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.

From routine monitoring

  • Arsenic
  • Chromium (total)
  • Lead
  • Nitrate
  • Uranium

PFAS and lithium, from EPA’s UCMR 5 sampling

  • 11Cl-PF3OUdS
  • 4:2 FTS
  • 6:2 FTS
  • 8:2 FTS
  • 9Cl-PF3ONS
  • ADONA
  • HFPO-DA (GenX)
  • Lithium
  • NEtFOSAA
  • NFDHA
  • NMeFOSAA
  • PFBA
  • PFBS
  • PFDA
  • PFDoA
  • PFEESA
  • PFHpA
  • PFHpS
  • PFHxA
  • PFHxS
  • PFMBA
  • PFMPA
  • PFNA
  • PFOA
  • PFOS
  • PFPeA
  • PFPeS
  • PFTA
  • PFTrDA
  • PFUnA

Violations since 2016

1 health-based violation since 2016 for TTHM. It began Jan. 1, 2016.

Resolved:
EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
No fix on record:
It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).

EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Got a notice about one? What it means and what to do⁠
Health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2016 to March 31, 2016, 82,000 ppbResolved

Health-based violations only. 1 monitoring or reporting violation not shown.

Hardness

Soft, 42 mg/L (2.5 grains per gallon), at its one sampling point, 2019 to 2025.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

Disinfectant

Rancho Murieta Community Servi reported disinfecting with chlorine, not chloramine, at all 2 of its sampling points, in its 2025 sampling for EPA.

What that means

Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), fluoride, arsenic, chromium (total), nitrate and uranium results here are California’s own from 2020 on, with EPA’s national file for 2012 to 2019. Rancho Murieta Community Servi’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Jan. 7 to Oct. 8, 2025; California’s results run from Jan. 8, 2020 to May 19, 2026.

Testing your own tap

Rancho Murieta Community Servi’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab California certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Rancho Murieta Community Servi’s latest lead sampling in EPA’s records, 2024 to 2026, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs California certifies closest to the area Rancho Murieta Community Servi serves, or a kit by mail

The 3 labs California certifies closest to the area Rancho Murieta Community Servi serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Ceres Analytical Laboratory, Inc.

    El Dorado Hills, CA · about 9 miles

    Certified for organic chemicals

    (916) 932-5011

  • Onterris Laboratories, LLC

    El Dorado Hills, CA · about 9 miles

    Certified for organic chemicals, PFAS

    (916) 673-1520

  • California Laboratory Services

    Rancho Cordova, CA · about 10 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts

    (916) 638-7301

All 145 certified labs for California⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that California certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against California’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID CA3410005. Rebuilt from EPA data on Oct. 25, 2026.