What EPA’s and California’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
946 people
Connections
109
Water source
Groundwater
Based in
Dillon Beach, CA
County
Marin
Owner
Private
Hardness
Moderately hard
The ZIP code it serves

94971

The short answer

Nothing in EPA’s and California’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.

What was found

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 1.4 ppm, for the period ending Dec. 31, 2000. None since is on file, so it is not counted as a current finding.

Total trihalomethanes (TTHM), nitrate, haloacetic acids (HAA5), fluoride, arsenic and chromium (total): California’s own results, samples taken from April 27, 2020 to March 5, 2025, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits4

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

21ppb

Highest yearly average, 2021 to 2024

2024, one sample: 14 ppb

Averaged by year, the highest was 21 ppb, in 2023, below EPA’s legal limit of 80 ppb. In 2024, the latest year on file, its one sample was 14 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 26 ppb, in 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Nitrate

Comes from the source

Below EPA’s limits

2.3ppm

Highest sample; found in 15 of 15

2025 average: 1.4 ppm

The highest sample, in 2020, was 2.3 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its three samples averaged 1.4 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 2.9 ppm, in 2012.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

7.8ppb

Highest yearly average, 2021 to 2024

2024: not found

Averaged by year, the highest was 7.8 ppb, in 2023, below EPA’s legal limit of 60 ppb. In 2024, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 12 ppb, in 2019.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.18ppm

Highest yearly average, 2020 to 2025

2025: not found

Averaged by year, the highest was 0.18 ppm, in 2020, below EPA’s legal limit of 4.0 ppm. In 2025, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.34 ppm, in 2017.

What handles it

3 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead

Hardness

Moderately hard, typically 89 mg/L (5.2 grains per gallon), across 3 sampling points, 2020 to 2023.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

Violations since 2016

No health-based violations on file with EPA since 2016. There are 2 monitoring or reporting violations: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), nitrate, haloacetic acids (HAA5), fluoride, arsenic and chromium (total) results here are California’s own from 2020 on, with EPA’s national file for 2012 to 2019. Lawson S Landing’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; California’s results run from April 27, 2020 to March 5, 2025.

Testing your own tap

Lawson S Landing’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab California certifies.

The 3 labs California certifies closest to the area Lawson S Landing serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Alpha Analytical Laboratories Inc. - North Bay

    Petaluma, CA · about 15 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, PFAS

    (707) 769-3128

  • Brelje and Race Laboratories, Inc.

    Santa Rosa, CA · about 19 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts

    (707) 544-8807

  • Sonoma County Public Health Laboratory

    Santa Rosa, CA · about 20 miles

    Certified for bacteria

    (707) 565-4711

All 145 certified labs for California

Sources

PWSID CA2110008. Rebuilt from EPA data on Oct. 18, 2026.