Skip to content
TapBuff

Encinal Rd WS #01

What EPA’s and California’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
91 people
Connections
9
Water source
Groundwater
Based in
Salinas, CA
County
Monterey
Owner
Private
Hardness
Very hard
The 2 ZIP codes it serves

93908, 93925

The short answer

1 result is above EPA’s legal limit, and 3 more are above the health goal. The worst: Nitrate, above the legal limit. 40 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2012 to 2024.

Nitrate, arsenic, uranium, fluoride and chromium (total): California’s own results, samples taken from Jan. 23, 2020 to June 10, 2026, with EPA’s 2012 to 2019 file for earlier years.

Total trihalomethanes (TTHM): EPA’s compliance monitoring file, samples taken from Sept. 11, 2013 to Sept. 12, 2019. Newer results are in the utility’s annual water quality report.

Above the legal limit1

Nitrate

Comes from the source

Above the legal limit

105ppm

Highest sample; found in 133 of 143

2026 average: 36.2 ppm

From 2020 to 2026, at least 25 samples were above EPA’s legal limit of 10 ppm, the highest 105 ppm in 2024. The next sample at the same point, within 30 days, kept the average above the limit for eight; 17 have no follow-up sample on file within 30 days. In 2026, the latest year on file, its 12 samples averaged 36.2 ppm, above the limit. EPA recorded violations for nitrate at this utility in 2020, 2021, 2022, 2023, 2024 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 66.7 ppm, in 2019, and EPA recorded violations in 2012, 2013, 2014, 2015, 2016, 2017, 2018 and 2019.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Above the health goal3

Arsenic

Comes from the source

Above the health goal

3.5ppb

Highest yearly average, 2023

Averaged by year, the highest was 3.5 ppb, in 2023: below EPA’s legal limit of 10 ppb, but above its health goal of zero. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.0 ppb, in 2013.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Uranium

Comes from the source

Above the health goal

7.9ppb

Highest yearly average, 2020 to 2021

Averaged by year, the highest was 7.9 ppb, in 2021: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 7.5 ppb, in 2014.

What handles it

Lead

Comes from pipes, often your own

Above the health goal

2.4ppb

90th percentile, 2022 to 2024

In the latest period, 9 in 10 homes sampled were at or below 2.4 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits2

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.5ppm

Highest yearly average, 2023

Averaged by year, the highest was 0.5 ppm, in 2023, below EPA’s legal limit of 4.0 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.5 ppm, in 2016.

What handles it

Chromium (total)

Comes from the source

Below EPA’s limits

1.2ppb

Highest yearly average, 2023

Averaged by year, the highest was 1.2 ppb, in 2023, below EPA’s legal limit of 100 ppb. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.0 ppb, in 2016.

What handles it

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Total trihalomethanes (TTHM)

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Nitrate/Nitrite (30 ppm challenge), Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Nitrate, Arsenic, Lead

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Nitrate/Nitrite Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Uranium, Lead Reduction

    For: Nitrate, Arsenic, Uranium, Lead

    Other certifiers’ wording: Nitrate; Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

The best water filters for lead, ranked

Hardness

Very hard, 507 mg/L (29.6 grains per gallon), at its one sampling point, in 2023.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2026 to June 30, 202677 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2026 to March 31, 202662.1 MG/LArchived
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Unaddressed
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2024 to Dec. 31, 202462 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2024 to Sept. 30, 202481 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2024 to June 30, 2024105 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2024 to March 31, 202488 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2023 to Dec. 31, 202361 MG/LArchived
Revised Total Coliform RuleE. coli was confirmed in the water system.EPA: Maximum Contaminant Level Violation, E. coli (RTCR)Aug. 1, 2023 to Aug. 31, 2023—Resolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2023 to Sept. 30, 202388 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2023 to June 30, 202384 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2023 to March 31, 202379 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2022 to Dec. 31, 202261 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2022 to Sept. 30, 202252 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2022 to June 30, 202268 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2022 to March 31, 202283 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2021 to Dec. 31, 202158 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2021 to Sept. 30, 202153 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2021 to June 30, 202169 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2021 to March 31, 202171 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2020 to Dec. 31, 202055 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2020 to Sept. 30, 202057 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2020 to June 30, 202072 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2020 to March 31, 202055 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2019 to Dec. 31, 201954 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2019 to Sept. 30, 201967 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2019 to June 30, 201955 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2019 to March 31, 201952 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2018 to Dec. 31, 201955 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2018 to Sept. 30, 201854 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2018 to June 30, 201856 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2018 to March 31, 201850 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2017 to Dec. 31, 201746 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2017 to Sept. 30, 201747 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2017 to June 30, 201755 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2017 to March 31, 201718.3 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2016 to Dec. 31, 201649 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2016 to Sept. 30, 201645 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2016 to June 30, 201655 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2016 to March 31, 201620 MG/LArchived
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 1 monitoring or reporting violation not shown.

What this report can’t tell you

  • Everything else. Nitrate, arsenic, uranium, fluoride and chromium (total) results here are California’s own from 2020 on, with EPA’s national file for 2012 to 2019. Total trihalomethanes (TTHM) comes from EPA’s file alone, which ends in 2019. Encinal Rd WS #01’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; California’s results run from Jan. 23, 2020 to June 10, 2026; EPA’s compliance samples are from Sept. 11, 2013 to Sept. 12, 2019.

Testing your own tap

Encinal Rd WS #01’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab California certifies.

The 3 labs California certifies closest to the area Encinal Rd WS #01 serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Monterey County Consolidated Environmental Laboratory

    Salinas, CA · about 9 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (831) 755-4516

  • Monterey Bay Analytical Services, Inc.

    Monterey, CA · about 18 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, radioactivity

    (831) 375-6227

  • CM Analytical, Inc.

    Gilroy, CA · about 26 miles

    Certified for bacteria

    (408) 848-3619

All 145 certified labs for California

Sources

PWSID CA2701241. Rebuilt from EPA data on Oct. 18, 2026.