Skip to content
TapBuff

Quechan Utility

EPA’s records have results for 36 contaminants in its water; 5 were found.

Serves 5,660 people · Groundwater · Yuma, AZ

Serves
5,660 people
Connections
1,201
Water source
Groundwater
Based in
Yuma, AZ
Owner
Native American
The ZIP code it serves

92283

The short answer

None of the results here is above a limit in force today. Lithium is above EPA’s health benchmark. 3 health-based violations since 2016, 1 with no fix on record in EPA’s file.

This is what the records show, not medical advice. Worried about a health effect? Talk to a doctor or your local health department.

Filters for lead, arsenic and uranium, if you want them lower⁠The 3 violations⁠Got a notice? What it means⁠

What was found

Where these results come from, and when

PFAS and lithium: EPA UCMR 5, samples taken from Feb. 20 to July 11, 2024.

Lead and copper: EPA SDWIS monitoring periods ending 2007 to 2025.

Arsenic, uranium, nitrate, chromium (total) and fluoride: EPA’s compliance monitoring file, samples taken from Feb. 27, 2012 to Dec. 2, 2019. Newer results are in the utility’s annual water quality report.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.
Health reference level:
A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.

PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.

Above EPA’s health benchmark, 1 result

Lithium

Comes from the source

Above EPA’s health benchmark

63 ppb

Highest sample, July 11, 2024; found in 4 of 4

The highest sample was 63 ppb, about 6.3 times EPA’s health reference level of 10 ppb. That is a screening level, not an enforceable limit.

What handles it

No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.

How to read your utility’s report

Below EPA’s limits, 4 results

Lead, arsenic and uranium have a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Lead, Action level 15 ppb · health goal zero; 90th percentile 6.1 ppb

90th percentile, 2023 to 2025 · Comes from pipes, often your own

In the latest period, 9 in 10 homes sampled were at or below 6.1 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

About lead
Arsenic, Legal limit 10 ppb · health goal zero; highest yearly average 3.1 ppb

Highest yearly average, 2014 to 2019 · Comes from the source

Averaged by year, the highest was 3.1 ppb, in 2019, below EPA’s legal limit of 10 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. That was also the latest year on file.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
About arsenic
Uranium, Legal limit 30 ppb · health goal zero; highest yearly average 6.7 ppb

Highest yearly average, 2015 to 2019 · 2019 average: 3.8 ppb · Comes from the source

Averaged by year, the highest was 6.7 ppb, in 2015, below EPA’s legal limit of 30 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. In 2019, the latest year on file, its two samples averaged below the limit.

What handles it

About uranium
Nitrate, Legal limit 10 ppm; highest 2.0 ppm

Highest sample; found in 1 of 8 · 2019: not found · Comes from the source

The highest sample, in 2012, was 2.0 ppm, below EPA’s legal limit of 10 ppm. In 2019, the latest year on file, it wasn’t found in any of its two samples.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
Arizona utilities above EPA’s PFAS limits⁠
31 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.

From routine monitoring

  • Chromium (total)
  • Fluoride

PFAS and lithium, from EPA’s UCMR 5 sampling

  • 11Cl-PF3OUdS
  • 4:2 FTS
  • 6:2 FTS
  • 8:2 FTS
  • 9Cl-PF3ONS
  • ADONA
  • HFPO-DA (GenX)
  • NEtFOSAA
  • NFDHA
  • NMeFOSAA
  • PFBA
  • PFBS
  • PFDA
  • PFDoA
  • PFEESA
  • PFHpA
  • PFHpS
  • PFHxA
  • PFHxS
  • PFMBA
  • PFMPA
  • PFNA
  • PFOA
  • PFOS
  • PFPeA
  • PFPeS
  • PFTA
  • PFTrDA
  • PFUnA

Violations since 2016

3 health-based violations since 2016, 2 for the Groundwater Rule and 1 for the Revised Total Coliform Rule. The latest began May 31, 2025, and 1 has no fix on record in EPA’s file.

Resolved:
EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
No fix on record:
It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).

EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Got a notice about one? What it means and what to do⁠
Health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyMay 31, 2025No fix on recordEPA: unaddressed
Dec. 11, 2021Resolved
Revised Total Coliform RuleColiform or E. coli results required a detailed review of the system, and it or its fixes were not done on time.EPA: Treatment Technique, Level 2 Assessment (RTCR)Dec. 1, 2019Resolved

Health-based violations only. 214 monitoring or reporting violations not shown.

Skip past the filters

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.

  • NSF/ANSI 53

    Claims: Lead Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Lead, Arsenic

    Other claims that cover it: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Lead Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Uranium

    For: Lead, Arsenic, Uranium

    Other claims that cover it: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

2 more filters
Compare five-year costs

Every filter for these, those that cover all 3 first⁠

The best water filters for lead, ranked⁠

The best reverse osmosis systems, ranked⁠

Disinfectant

Quechan Utility reported adding no disinfectant at all 2 of its sampling points, in its 2024 sampling for EPA.

What that means

Most utilities add chlorine or chloramine. CDC says some that draw groundwater don’t need a disinfectant, because testing shows the water doesn’t carry enough germs to make people sick. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.

What this report can’t tell you

  • Newer results, and everything else. Nitrate, arsenic, fluoride, chromium, uranium and disinfection byproduct results here come from EPA’s national compliance file, which ends in 2019. Quechan Utility’s own annual report, which it must send you every year, has newer results and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Feb. 20 to July 11, 2024; EPA’s compliance samples are from Feb. 27, 2012 to Dec. 2, 2019.

Testing your own tap

Quechan Utility’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Arizona certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Quechan Utility’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 6.1 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
  • What Quechan Utility’s results flag: lithium. It is in the water the utility sends out, so a test of your tap mostly confirms it. Include it if you want a number for your own home.
The 2 labs Arizona certifies closest to the area Quechan Utility serves, or a kit by mail

The 2 labs Arizona certifies closest to the area Quechan Utility serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Fresh Terra Services, LLC.

    Yuma, AZ · about 22 miles

    (928) 257-3601

  • Eurofins Microbiology Laboratories

    Yuma, AZ · about 22 miles

    (928) 317-1127

All 49 certified labs for Arizona⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Arizona certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Arizona’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID 090400089. Rebuilt from EPA data on Oct. 25, 2026.