Skip to content
TapBuff

Dateland Public Service Co

What EPA’s and CDC’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
319 people
Connections
125
Water source
Groundwater
Based in
Dateland, AZ
County
Yuma
Owner
Private
The ZIP code it serves

85333

The short answer

1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Fluoride, above the legal limit. 2 health-based violations since 2016.

What handles it

What was found

Arsenic and nitrate: Arizona’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2023, with EPA’s 2012 to 2019 file for earlier years.

Fluoride and chromium (total): EPA’s compliance monitoring file, samples taken from March 14, 2012 to Nov. 6, 2019. Newer results are in the utility’s annual water quality report.

Above the legal limit1

Fluoride

Forms or is added in treatment

Above the legal limit

3.6ppm

Highest yearly average, 2012 to 2019

2019 average: 0.64 ppm

Averaged by year, the highest was 3.6 ppm, in 2012, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 6.0 ppm. In 2019, the latest year on file, its five samples averaged 0.64 ppm. EPA judges this limit at each sampling point, and recorded a violation for fluoride at this utility in 2012.

What handles it

Above the health goal1

Arsenic

Comes from the source

Above the health goal

6.2ppb

Highest yearly average, 2020 to 2023

2023 average: 4.8 ppb

Averaged by year, the highest was 6.2 ppb, in 2021: below EPA’s legal limit of 10 ppb, but above its health goal of zero. In 2023, the latest year on file, it averaged 4.8 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 14.1 ppb, in 2012, and EPA recorded a violation in 2012.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Below EPA’s limits2

Nitrate

Comes from the source

Below EPA’s limits

0.67ppm

Highest yearly average, 2020 to 2023

2023 average: 0.22 ppm

Averaged by year, the highest was 0.67 ppm, in 2021, below EPA’s legal limit of 10 ppm. In 2023, the latest year on file, it averaged 0.22 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.85 ppm, in 2012.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

1.2ppb

Highest yearly average, 2015

Averaged by year, the highest was 1.2 ppb, in 2015, below EPA’s legal limit of 100 ppb. That is the only year on file.

What handles it

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Fluoride, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Fluoride, Arsenic

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Fluoride Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Fluoride, Arsenic

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best water filters for fluoride, ranked

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Revised Total Coliform RuleColiform or E. coli results required a detailed review of the system, and it or its fixes were not done on time.EPA: Treatment Technique, Level 2 Assessment (RTCR)Nov. 21, 2022—Resolved
Revised Total Coliform RuleColiform results required a check of the system, and the check or its fixes were not done on time.EPA: Treatment Technique, Level 1 Assessment (RTCR)Sept. 5, 2022—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 29 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Arsenic and nitrate results here are Arizona’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Fluoride and chromium (total) come from EPA’s file alone, which ends in 2019. Dateland Public Service Co’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; CDC’s yearly averages for Arizona cover 2020 to 2023; EPA’s compliance samples are from March 14, 2012 to Nov. 6, 2019.

Testing your own tap

Dateland Public Service Co’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Arizona certifies.

The 2 labs Arizona certifies closest to the area Dateland Public Service Co serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Fresh Terra Services, LLC.

    Yuma, AZ · about 65 miles

    (928) 257-3601

  • Eurofins Microbiology Laboratories

    Yuma, AZ · about 65 miles

    (928) 317-1127

All 49 certified labs for Arizona

Sources

PWSID AZ0414003. Rebuilt from EPA data on Oct. 18, 2026.