Skip to content
TapBuff

Florala Water Works & Sewer Board

EPA’s and Alabama’s records have results for 7 contaminants in its water; 7 were found.

Serves 3,834 people · Groundwater · Florala, AL · Hardness: very hard

Serves
3,834 people
Connections
1,278
Water source
Groundwater
Based in
Florala, AL
County
Covington
Owner
Local government
Hardness
Very hard
The ZIP code it serves

32567

The short answer

None of the results here is above a limit in force today. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.

Filters for arsenic and lead, if you want them lower⁠

What was found

Where these results come from, and when

Lead and copper: EPA SDWIS monitoring periods ending 2006 to 2023.

Arsenic, total trihalomethanes (TTHM), nitrate, fluoride, haloacetic acids (HAA5) and chromium (total): Alabama’s own results, samples taken from Feb. 19, 2020 to July 15, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.

Below EPA’s limits, 7 results

Arsenic and lead have a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Arsenic, Legal limit 10 ppb · health goal zero; highest yearly average 1.2 ppb

Highest yearly average, 2021 to 2025 · Comes from the source

Averaged by year, the highest was 1.2 ppb, in 2025, below EPA’s legal limit of 10 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. Its highest single sample was 1.9 ppb. That was also the latest year on file.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.85 ppb, in 2013.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
About arsenic
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 6.9 ppb

Highest yearly average, 2020 to 2026 · 2026 average: 4.8 ppb · Forms or is added in treatment

Averaged by year, the highest was 6.9 ppb, in 2021, below EPA’s legal limit of 80 ppb. Its highest single sample was 8.4 ppb. In 2026, the latest year on file, its two samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 6.9 ppb, in 2018.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
About total trihalomethanes (TTHM)
Nitrate, Legal limit 10 ppm; highest 0.56 ppm

Highest sample; found in 14 of 14 · 2026 average: 0.19 ppm · Comes from the source

The highest sample, in 2025, was 0.56 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its two samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest sample of 0.62 ppm, in 2016.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.22 ppm

Highest yearly average, 2021 to 2025 · Forms or is added in treatment

Averaged by year, the highest was 0.22 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 0.43 ppm. That was also the latest year on file.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.085 ppm, in 2013.

What handles it

About fluoride
Lead, Action level 15 ppb · health goal zero; 90th percentile 0.54 ppb

90th percentile, 2021 to 2023 · Comes from pipes, often your own

In the latest period, 9 in 10 homes sampled were at or below 0.54 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

About lead
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 1.4 ppb

Highest yearly average, 2020 to 2026 · 2026: not found · Forms or is added in treatment

Averaged by year, the highest was 1.4 ppb, in 2020, below EPA’s legal limit of 60 ppb. Its highest single sample was 2.1 ppb. In 2026, the latest year on file, it wasn’t found in any of its two samples.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 1.5 ppb, in 2013.

What handles it

No certification claim covers this compound yet.

About haloacetic acids (HAA5)
Chromium (total), Legal limit 100 ppb; highest yearly average 1.9 ppb

Highest yearly average, 2021 to 2025 · 2025 average: 0.78 ppb · Comes from the source

Averaged by year, the highest was 1.9 ppb, in 2021, below EPA’s legal limit of 100 ppb. Its highest single sample was 2.5 ppb. In 2025, the latest year on file, its two samples averaged below the limit.

What handles it

About chromium (total)

Violations since 2016

No health-based violations on file with EPA since 2016. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Skip past the filters

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.

  • NSF/ANSI 53

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Arsenic, Lead

    Other claims that cover it: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Arsenic, Lead

    Other claims that cover it: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

2 more filters
Compare five-year costs

Every filter for these, those that cover both first⁠

The best reverse osmosis systems, ranked⁠

The best water filters for lead, ranked⁠

Hardness

Very hard, 204 mg/L (11.9 grains per gallon), at its one sampling point, 2016 to 2025.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

What this report can’t tell you

  • Everything else. Arsenic, total trihalomethanes (TTHM), nitrate, fluoride, haloacetic acids (HAA5) and chromium (total) results here are Alabama’s own from 2020 on, with EPA’s national file for 2012 to 2019. Florala Water Works & Sewer Board’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Alabama’s results run from Feb. 19, 2020 to July 15, 2026.

Testing your own tap

Florala Water Works & Sewer Board’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Alabama certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Florala Water Works & Sewer Board’s latest lead sampling in EPA’s records, 2021 to 2023, had a 90th percentile of 0.54 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Alabama certifies closest to the area Florala Water Works & Sewer Board serves, or a kit by mail

The 3 labs Alabama certifies closest to the area Florala Water Works & Sewer Board serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

All 64 certified labs for Alabama⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Alabama certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Alabama’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID AL0000363. Rebuilt from EPA data on Oct. 25, 2026.