Skip to content
TapBuff

Vista del Rio

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
126 people
Connections
42
Water source
Groundwater
Based in
Marble Falls, TX
County
Burnet
Owner
Private
The ZIP code it serves

78654

The short answer

1 result is above EPA’s legal limit, and 3 more are above the health goal. The worst: Copper, above the action level. 8 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2020 to 2024.

Arsenic, uranium, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate and chromium (total): Texas’s own results, samples taken from March 13, 2020 to July 28, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit1

Copper

Comes from pipes, often your own

Above the action level

1.6ppm

90th percentile, 2024

In the latest period, 9 in 10 homes sampled were at or below 1.6 ppm, above EPA’s action level of 1.3 ppm.

What handles it

Above the health goal3

Arsenic

Comes from the source

Above the health goal

2.4ppb

Highest yearly average, 2021 to 2024

2024: not found

Averaged by year, the highest was 2.4 ppb, in 2021: below EPA’s legal limit of 10 ppb, but above its health goal of zero. In 2024, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.1 ppb, in 2018.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Lead

Comes from pipes, often your own

Above the health goal

2.1ppb

90th percentile, 2026

In the latest period, 9 in 10 homes sampled were at or below 2.1 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Uranium

Comes from the source

Above the health goal

1.5ppb

Highest yearly average, 2021 to 2024

Averaged by year, the highest was 1.5 ppb, in 2024: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.5 ppb, in 2015.

What handles it

Below EPA’s limits4

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

75.7ppb

Highest yearly average, 2020 to 2026

2026 average: 37.7 ppb

Averaged by year, the highest was 75.7 ppb, in 2020, below EPA’s legal limit of 80 ppb. Its highest single sample was 114 ppb. In 2026, the latest year on file, its three samples averaged 37.7 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 96.7 ppb, in 2017, and EPA recorded a violation in 2018.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

22.8ppb

Highest yearly average, 2020 to 2026

2026 average: 11.1 ppb

Averaged by year, the highest was 22.8 ppb, in 2020, below EPA’s legal limit of 60 ppb. Its highest single sample was 37.4 ppb. In 2026, the latest year on file, its three samples averaged 11.1 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 22.1 ppb, in 2019.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.38ppm

Highest yearly average, 2022 to 2025

2025: not found

Averaged by year, the highest was 0.38 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. In 2025, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.38 ppm, in 2013.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.92ppm

Highest sample; found in 7 of 7

2026, one sample: 0.51 ppm

The highest sample, in 2025, was 0.92 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was 0.51 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.81 ppm, in 2012.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Chromium (total)

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Copper Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Copper, Arsenic, Lead

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Copper Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction, Uranium

    For: Copper, Arsenic, Lead, Uranium

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Resolved
Lead and Copper RuleOCCT/SOWT Treatment Installation/DemonstrationApril 1, 2024—Resolved
Lead and Copper RuleOCCT/SOWT Treatment Installation/DemonstrationOct. 3, 2022—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2018 to June 30, 20180.1 MG/LResolved
Lead and Copper RuleA required study or plan for corrosion control was not done on time.EPA: OCCT/SOWT Study/RecommendationApril 1, 2018—Resolved
Lead and Copper RuleA required study or plan for corrosion control was not done on time.EPA: OCCT/SOWT Study/RecommendationMarch 31, 2018—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2018 to March 31, 20180.086 MG/LResolved
Lead and Copper RuleRequired information about lead was not given to customers.EPA: Public EducationDec. 1, 2017—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 20 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Arsenic, uranium, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate and chromium (total) results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Vista del Rio’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from March 13, 2020 to July 28, 2026.

Testing your own tap

Vista del Rio’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The 3 labs Texas certifies closest to the area Vista del Rio serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Integrity Testing, Inc.

    Austin, TX · about 29 miles

    Certified for lead and copper

    (512) 891-7777

  • Environmental Monitoring Lab

    Llano, TX · about 30 miles

    Certified for bacteria

    (325) 247-3295

  • Texas Department of State Health Services Laboratory Services Section

    Austin, TX · about 33 miles

    Certified for bacteria, lead and copper

    (512) 458-7318

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX0270082. Rebuilt from EPA data on Oct. 18, 2026.