Skip to content
TapBuff

The Consolidated WSC Central System

EPA’s and Texas’s records have results for 38 contaminants in its water; 6 were found.

In the name, WSC means water supply corporation.

Serves 3,878 people · Groundwater · Crockett, TX

Serves
3,878 people
Connections
1,515
Water source
Groundwater
Based in
Crockett, TX
County
Houston
Owner
Local government
The 4 ZIP codes it serves

75835, 75844, 75849, 75851

The short answer

EPA recorded violations of the legal limit for haloacetic acids (HAA5) here in 2024 and 2025. In 2026, the latest year on file, it averaged 40.2 ppb, below the limit. EPA recorded violations of the legal limit for total trihalomethanes (TTHM) here in 2024 and 2025. In 2026, the latest year on file, it averaged 54.7 ppb, below the limit. 16 health-based violations since 2016, all resolved in EPA’s file.

This is what the records show, not medical advice. Worried about a health effect? Talk to a doctor or your local health department.

What handles it⁠The 16 violations⁠Got a notice? What it means⁠

What was found

Where these results come from, and when

PFAS and lithium: EPA UCMR 5, samples taken from Feb. 12, 2024 to April 7, 2025.

Lead and copper: EPA SDWIS monitoring periods ending 2003 to 2025.

Haloacetic acids (HAA5), total trihalomethanes (TTHM), fluoride, nitrate, arsenic, chromium (total) and uranium: Texas’s own results, samples taken from Jan. 8, 2020 to Sept. 2, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.

PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. One other PFAS with no federal limit was found, the highest PFBA at 5.1 ppt: see it below.

A legal-limit violation on record, below the limit in the latest year, 2 results

Haloacetic acids (HAA5)

Forms or is added in treatment

Violation on record (2025)

What it means for you. EPA’s concern is long-term exposure, years of drinking it, not an immediate risk to health. A violation like this calls for a notice to customers within 30 days.

121 ppb

Highest yearly average, 2020 to 2026

2026 average: 40.2 ppb

Averaged by year, the highest was 121 ppb, in 2024, about twice EPA’s legal limit of 60 ppb. Its highest single sample was 322 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded violations for haloacetic acids (HAA5) at this utility in 2024 and 2025.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 51.1 ppb, in 2016, and EPA recorded violations in 2015 and 2016.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Violation on record (2025)

What it means for you. EPA’s concern is long-term exposure, years of drinking it, not an immediate risk to health. A violation like this calls for a notice to customers within 30 days. A filter certified for it, at the tap you drink from, reduces it.

111 ppb

Highest yearly average, 2020 to 2026

2026 average: 54.7 ppb

Averaged by year, the highest was 111 ppb, in 2024, above EPA’s legal limit of 80 ppb. Its highest single sample was 250 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2024 and 2025.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 81.2 ppb, in 2016, and EPA recorded violations in 2015, 2016, 2017 and 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Below EPA’s limits, 3 results

Lead has a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Lead, Action level 15 ppb · health goal zero; 90th percentile 1.3 ppb

90th percentile, 2025 · Comes from pipes, often your own

In the latest period, 9 in 10 homes sampled were at or below 1.3 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

About lead
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.32 ppm

Highest yearly average, 2024 · Forms or is added in treatment

Averaged by year, the highest was 0.32 ppm, in 2024, below EPA’s legal limit of 4.0 ppm. That is the only year on file.

What handles it

About fluoride
Nitrate, Legal limit 10 ppm; highest 0.32 ppm

Highest sample; found in 20 of 20 · 2025 average: 0.081 ppm · Comes from the source

The highest sample, in 2024, was 0.32 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its two samples averaged below the limit.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
Texas utilities above EPA’s PFAS limits⁠

Also found, with no federal limit

EPA measured these PFAS to learn how often they occur. None has a legal limit or a health goal yet.

PFAS found with no federal limit
CompoundHighest sampleFound inCertification claim
PFBA5.1 ppt1 of 6None covers it
32 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.

From routine monitoring

  • Arsenic
  • Chromium (total)
  • Uranium

PFAS and lithium, from EPA’s UCMR 5 sampling

  • 11Cl-PF3OUdS
  • 4:2 FTS
  • 6:2 FTS
  • 8:2 FTS
  • 9Cl-PF3ONS
  • ADONA
  • HFPO-DA (GenX)
  • Lithium
  • NEtFOSAA
  • NFDHA
  • NMeFOSAA
  • PFBS
  • PFDA
  • PFDoA
  • PFEESA
  • PFHpA
  • PFHpS
  • PFHxA
  • PFHxS
  • PFMBA
  • PFMPA
  • PFNA
  • PFOA
  • PFOS
  • PFPeA
  • PFPeS
  • PFTA
  • PFTrDA
  • PFUnA
Skip past the filters

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

    Other claims that cover it: VOC Reduction

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

2 more filters
Compare five-year costs

Every filter certified for it⁠

The best water filters for TTHM, ranked⁠

The best water filters for lead, ranked⁠

Disinfectant

The Consolidated WSC Central System reported chloramine at 1 of its 2 sampling points and chlorine without chloramine at 1, in its 2024 to 2025 sampling for EPA. Which one reaches your tap can depend on where you live.

What that means

Chloramine is chlorine combined with ammonia. It lasts longer in the pipes, and unlike chlorine, it doesn’t leave water that sits out. A filter’s chlorine claim doesn’t cover it: look for the separate chloramine claim under NSF/ANSI 42. No shower filter can carry one: NSF/ANSI 177, the shower filter standard, covers free chlorine only. Fish, turtles and frogs need it removed from their water. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.

Violations since 2016

16 health-based violations since 2016, 11 for TTHM and 5 for total Haloacetic Acids (HAA5). The latest began Jan. 1, 2025.

Resolved:
EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
No fix on record:
It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).

EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Got a notice about one? What it means and what to do⁠
Health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 2025, 93 ppbResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 2025, 99 ppbResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 2024, 90 ppbResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 2024, 97 ppbResolved
July 1, 2024 to Sept. 30, 2024, 77 ppbResolved
The other 11, back to 2016
Earlier health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 2024, 87 ppbResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 2024, 100 ppbResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 2024, 89 ppbResolved
Oct. 1, 2019 to Dec. 31, 2019, 81 ppbResolved
July 1, 2019 to Sept. 30, 2019, 85 ppbResolved
April 1, 2019 to June 30, 2019, 81 ppbResolved
Jan. 1, 2017 to March 31, 2017, 90 ppbResolved
Oct. 1, 2016 to Dec. 31, 2016, 89 ppbResolved
July 1, 2016 to Sept. 30, 2016, 86 ppbResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 2016, 65 ppbResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 2016, 97 ppbResolved

Health-based violations only. 12 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM), fluoride, nitrate, arsenic, chromium (total) and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. The Consolidated WSC Central System’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Feb. 12, 2024 to April 7, 2025; Texas’s results run from Jan. 8, 2020 to Sept. 2, 2026.

Testing your own tap

The Consolidated WSC Central System’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. The Consolidated WSC Central System’s latest lead sampling in EPA’s records, 2025, had a 90th percentile of 1.3 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
  • What The Consolidated WSC Central System’s results flag: haloacetic acids (HAA5) and total trihalomethanes (TTHM). These are in the water the utility sends out, so a test of your tap mostly confirms them. Include them if you want a number for your own home.
The 3 labs Texas certifies closest to the area The Consolidated WSC Central System serves, or a kit by mail

The 3 labs Texas certifies closest to the area The Consolidated WSC Central System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Chaparral Laboratories, Inc.

    Huntsville, TX · about 36 miles

    Certified for bacteria, lead and copper

    (936) 291-1881

  • Eastex Environmental Lab, Inc. -Coldspring

    Coldspring, TX · about 51 miles

    Certified for bacteria, lead and copper

    (936) 653-3249

  • Eastex Environmental Lab, Inc.-Nacogdoches

    Nacogdoches, TX · about 60 miles

    Certified for bacteria

    (936) 569-8879

All 80 certified labs for Texas⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Texas certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Texas’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID TX1130031. Rebuilt from EPA data on Oct. 25, 2026.