South Freestone County WSC
EPA’s and Texas’s records have results for 38 contaminants in its water; 6 were found.
In the name, WSC means water supply corporation.
Serves 3,753 people · Groundwater · Teague, TX
- Serves
- 3,753 people
- Connections
- 1,251
- Water source
- Groundwater
- Based in
- Teague, TX
- County
- Freestone
- Owner
- Local government
The short answer
None of the results here is above a limit in force today. Lithium is above EPA’s health benchmark. No health-based violations on file since 2016.
This is what the records show, not medical advice. Worried about a health effect? Talk to a doctor or your local health department.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from June 7, 2023 to May 6, 2024.
Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, chromium (total), arsenic and uranium: Texas’s own results, samples taken from March 17, 2020 to May 6, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Health goal (MCLG):
- Not enforceable. The level with no expected risk, with a margin of safety.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
Above EPA’s health benchmark, 1 result
Lithium
Comes from the source
17.8 ppb
Highest sample, Dec. 5, 2023; found in 9 of 18
The highest sample was 17.8 ppb, above EPA’s health reference level of 10 ppb. That is a screening level, not an enforceable limit.
What handles it
No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.
How to read your utility’s reportBelow EPA’s limits, 5 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 45.5 ppb
Highest yearly average, 2020 to 2026 · 2026, one sample: 8.5 ppb · Forms or is added in treatment
Averaged by year, the highest was 45.5 ppb, in 2022, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 26.2 ppb, in 2016.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 6.0 ppb
Highest yearly average, 2020 to 2026 · 2026, one sample: 4.7 ppb · Forms or is added in treatment
Averaged by year, the highest was 6.0 ppb, in 2024, below EPA’s legal limit of 60 ppb. In 2026, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 4.0 ppb, in 2016.
What handles it
No certification claim covers this compound yet.
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.1 ppm
Highest yearly average, 2020 to 2026 · 2026 average: 0.093 ppm · Forms or is added in treatment
Averaged by year, the highest was 0.1 ppm, in 2020, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 0.15 ppm. In 2026, the latest year on file, its four samples averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 0.096 ppm, in 2014.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Nitrate, Legal limit 10 ppm; highest 0.1 ppm
Highest sample; found in 56 of 58 · 2026 average: 0.021 ppm · Comes from the source
The highest sample, in 2025, was 0.1 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its four samples averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest sample of 0.066 ppm, in 2016.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
Chromium (total), Legal limit 100 ppb; highest yearly average 0.88 ppb
Highest yearly average, 2020 to 2026 · 2026: not found · Comes from the source
Averaged by year, the highest was 0.88 ppb, in 2020, below EPA’s legal limit of 100 ppb. Its highest single sample was 3.8 ppb. In 2026, the latest year on file, it wasn’t found in any of its four samples.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 6.3 ppb, in 2014.
What handles it
- NSF/ANSI 58 look for “Chromium (Hexavalent) Reduction”
- NSF/ANSI 53 look for “Chromium Reduction”
32 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Arsenic
- Lead
- Uranium
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
No health-based violations on file with EPA since 2016. There are 2 monitoring or reporting violations: a sample missed, late or not reported. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Disinfectant
South Freestone County WSC reported chloramine in some sampling rounds and not in others, in its 2023 to 2024 sampling for EPA. Of its 9 sampling points, 1 in some rounds only and 8 chlorine without chloramine. CDC says some utilities switch between chlorine and chloramine with the seasons.
What that means
Chloramine is chlorine combined with ammonia. It lasts longer in the pipes, and unlike chlorine, it doesn’t leave water that sits out. A filter’s chlorine claim doesn’t cover it: look for the separate chloramine claim under NSF/ANSI 42. No shower filter can carry one: NSF/ANSI 177, the shower filter standard, covers free chlorine only. Fish, turtles and frogs need it removed from their water. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, chromium (total), arsenic and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. South Freestone County WSC’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from June 7, 2023 to May 6, 2024; Texas’s results run from March 17, 2020 to May 6, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. South Freestone County WSC’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
- What South Freestone County WSC’s results flag: lithium. It is in the water the utility sends out, so a test of your tap mostly confirms it. Include it if you want a number for your own home.
The 3 labs Texas certifies closest to the area South Freestone County WSC serves, or a kit by mail
The 3 labs Texas certifies closest to the area South Freestone County WSC serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Bio-Chem Lab, Inc.
West, TX · about 61 miles
Certified for bacteria, lead and copper
Chaparral Laboratories, Inc.
Huntsville, TX · about 62 miles
Certified for bacteria, lead and copper
Analytical Environmental Labs
Tyler, TX · about 64 miles
Certified for bacteria
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Texas certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Texas’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Read up on lithiumWhat it does to health, where it comes from, and the certification claim that addresses it.About lithium
- Get the utility’s own reportSouth Freestone County WSC must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Texas Commission on Environmental Quality, Texas Drinking Water Viewer, results from Jan. 7, 2020 to Oct. 6, 2026, read Oct. 16, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: TCEQ, drinking water laboratories approved for public water system samples, read Oct. 10, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID TX0810005. Rebuilt from EPA data on Oct. 25, 2026.