Pollok - Redtown WSC
What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 2,012 people
- Connections
- 774
- Water source
- Groundwater
- Based in
- Pollok, TX
- County
- Angelina
- Owner
- Local government
The short answer
Nothing in EPA’s and Texas’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.
What was found
Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, chromium (total), nitrate, arsenic and uranium: Texas’s own results, samples taken from June 17, 2020 to May 29, 2025, with EPA’s 2012 to 2019 file for earlier years.
Below EPA’s limits5
Total trihalomethanes (TTHM)
Forms or is added in treatment
69.7ppb
Highest yearly average, 2020 to 2025
2025 average: 39.1 ppb
Averaged by year, the highest was 69.7 ppb, in 2022, below EPA’s legal limit of 80 ppb. Its highest single sample was 205 ppb. In 2025, the latest year on file, its two samples averaged 39.1 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 55.5 ppb, in 2019.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5)
Forms or is added in treatment
38.2ppb
Highest yearly average, 2020 to 2025
2025 average: 12.7 ppb
Averaged by year, the highest was 38.2 ppb, in 2022, below EPA’s legal limit of 60 ppb. Its highest single sample was 113 ppb. In 2025, the latest year on file, its two samples averaged 12.7 ppb. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 32.6 ppb, in 2019.
What handles it
No certification claim covers this compound yet.
Fluoride
Forms or is added in treatment
0.15ppm
Highest yearly average, 2021 to 2024
2024, one sample: 0.13 ppm
Averaged by year, the highest was 0.15 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. In 2024, the latest year on file, its one sample was 0.13 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.18 ppm, in 2018.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Chromium (total)
Comes from the source
2.9ppb
Highest yearly average, 2021 to 2024
2024: not found
Averaged by year, the highest was 2.9 ppb, in 2021, below EPA’s legal limit of 100 ppb. In 2024, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.2 ppb, in 2015.
What handles it
- NSF/ANSI 58 look for “Chromium (Hexavalent) Reduction”
- NSF/ANSI 53 look for “Chromium Reduction”
Nitrate
Comes from the source
0.039ppm
Highest sample; found in 5 of 6
2025, one sample: 0.039 ppm
The highest sample, in 2025, was 0.039 ppm, below EPA’s legal limit of 10 ppm. That was also the latest year on file, and its one sample was 0.039 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.07 ppm, in 2019.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
3 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
- Arsenic
- Lead
- Uranium
Violations since 2016
No health-based violations on file with EPA since 2016. There are 5 monitoring or reporting violations: a sample missed, late or not reported.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, chromium (total), nitrate, arsenic and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Pollok - Redtown WSC’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from June 17, 2020 to May 29, 2025.
Testing your own tap
The 3 labs Texas certifies closest to the area Pollok - Redtown WSC serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Eastex Environmental Lab, Inc.-Nacogdoches
Nacogdoches, TX · about 24 miles
Certified for bacteria
Analytical Environmental Labs
Tyler, TX · about 57 miles
Certified for bacteria
Chaparral Laboratories, Inc.
Huntsville, TX · about 61 miles
Certified for bacteria, lead and copper
Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.
All 80 certified labs for TexasSources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Texas Commission on Environmental Quality, Texas Drinking Water Viewer, results from Jan. 7, 2020 to Oct. 6, 2026, read Oct. 16, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Certified labs: TCEQ, drinking water laboratories approved for public water system samples, read Oct. 10, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID TX0030094. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Nothing here is above a health goalIn EPA’s and Texas’s records for this utility. They don’t cover everything, which is why the next step matters.Every contaminant TapBuff tracks
- Get the utility’s own reportPollok - Redtown WSC must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded