Skip to content
TapBuff

Murray Hill Water System

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
1,320 people
Connections
440
Water source
Groundwater
Based in
Itasca, TX
County
Hill
Owner
Private
The ZIP code it serves

76692

The short answer

Nothing in EPA’s and Texas’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.

What was found

Fluoride, total trihalomethanes (TTHM), haloacetic acids (HAA5), nitrate, arsenic, chromium (total) and uranium: Texas’s own results, samples taken from Sept. 17, 2020 to July 29, 2025, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits4

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.92ppm

Highest yearly average, 2020 to 2023

2023 average: 0.41 ppm

Averaged by year, the highest was 0.92 ppm, in 2020, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 1.4 ppm. In 2023, the latest year on file, its two samples averaged 0.41 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.47 ppm, in 2017.

What handles it

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

3.6ppb

Highest yearly average, 2020 to 2025

2025, one sample: 1.3 ppb

Averaged by year, the highest was 3.6 ppb, in 2023, below EPA’s legal limit of 80 ppb. In 2025, the latest year on file, its one sample was 1.3 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.3 ppb, in 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

1.5ppb

Highest yearly average, 2020 to 2025

2025: not found

Averaged by year, the highest was 1.5 ppb, in 2023, below EPA’s legal limit of 60 ppb. In 2025, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.1 ppb, in 2017.

What handles it

No certification claim covers this compound yet.

Nitrate

Comes from the source

Below EPA’s limits

0.046ppm

Highest sample; found in 12 of 12

2025 average: 0.031 ppm

The highest sample, in 2021, was 0.046 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its two samples averaged 0.031 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.19 ppm, in 2013.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Uranium

Violations since 2016

No health-based violations on file with EPA since 2016. There is 1 monitoring or reporting violation: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Fluoride, total trihalomethanes (TTHM), haloacetic acids (HAA5), nitrate, arsenic, chromium (total) and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Murray Hill Water System’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Sept. 17, 2020 to July 29, 2025.

Testing your own tap

Murray Hill Water System’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The 3 labs Texas certifies closest to the area Murray Hill Water System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Environmental Monitoring Lab

    Hillsboro, TX · about 12 miles

    Certified for bacteria

    (254) 582-2622

  • Bio-Chem Lab, Inc.

    West, TX · about 19 miles

    Certified for bacteria, lead and copper

    (254) 829-8001

  • Tarrant County Public Health Laboratory

    Fort Worth, TX · about 53 miles

    Certified for bacteria

    (817) 321-4758

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX1090014. Rebuilt from EPA data on Oct. 18, 2026.