Skip to content
TapBuff

Mountain Springs WSC

EPA’s and Texas’s records have results for 8 contaminants in its water; 5 were found.

In the name, WSC means water supply corporation.

Serves 3,756 people · Groundwater · Valley View, TX

Serves
3,756 people
Connections
1,252
Water source
Groundwater
Based in
Valley View, TX
County
Cooke
Owner
Local government
The 2 ZIP codes it serves

76271, 76272

The short answer

None of the results here is above a limit in force today. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 1 health-based violation since 2016, resolved in EPA’s file.

The violation⁠Got a notice? What it means⁠

What was found

Where these results come from, and when

Total trihalomethanes (TTHM), chromium (total), fluoride, haloacetic acids (HAA5), nitrate, arsenic and uranium: Texas’s own results, samples taken from May 13, 2020 to May 5, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.

Below EPA’s limits, 5 results

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 28.2 ppb

Highest yearly average, 2020 to 2026 · 2026: not found · Forms or is added in treatment

Averaged by year, the highest was 28.2 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, it wasn’t found in its one sample.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 15.6 ppb, in 2014.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
About total trihalomethanes (TTHM)
Chromium (total), Legal limit 100 ppb; highest yearly average 7.5 ppb

Highest yearly average, 2022 to 2025 · 2025 average: 1.7 ppb · Comes from the source

Averaged by year, the highest was 7.5 ppb, in 2022, below EPA’s legal limit of 100 ppb. Its highest single sample was 8.4 ppb. In 2025, the latest year on file, its four samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.72 ppb, in 2016.

What handles it

About chromium (total)
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.22 ppm

Highest yearly average, 2020 to 2026 · 2026 average: 0.14 ppm · Forms or is added in treatment

Averaged by year, the highest was 0.22 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its three samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.21 ppm, in 2019.

What handles it

About fluoride
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 2.5 ppb

Highest yearly average, 2020 to 2026 · 2026: not found · Forms or is added in treatment

Averaged by year, the highest was 2.5 ppb, in 2025, below EPA’s legal limit of 60 ppb. In 2026, the latest year on file, it wasn’t found in its one sample.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.47 ppb, in 2013.

What handles it

No certification claim covers this compound yet.

About haloacetic acids (HAA5)
Nitrate, Legal limit 10 ppm; highest 0.048 ppm

Highest sample; found in 23 of 28 · 2026 average: 0.014 ppm · Comes from the source

The highest sample, in 2022, was 0.048 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its four samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest sample of 0.06 ppm, in 2018.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
3 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Lead
  • Uranium

Violations since 2016

1 health-based violation since 2016 for the Lead and Copper Rule Revisions. It began Oct. 17, 2024.

Resolved:
EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
No fix on record:
It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).

EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Got a notice about one? What it means and what to do⁠
Health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024Resolved

Health-based violations only. 6 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), chromium (total), fluoride, haloacetic acids (HAA5), nitrate, arsenic and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Mountain Springs WSC’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from May 13, 2020 to May 5, 2026.

Testing your own tap

Mountain Springs WSC’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Mountain Springs WSC’s latest lead sampling in EPA’s records, 2024, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Texas certifies closest to the area Mountain Springs WSC serves, or a kit by mail

The 3 labs Texas certifies closest to the area Mountain Springs WSC serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Pace Analytical Services, LLC -Dallas TX

    Allen, TX · about 30 miles

    Certified for bacteria

    (972) 727-1123

  • Southern Petroleum Laboratories, Inc. - Plano

    Plano, TX · about 35 miles

    Certified for bacteria, lead and copper

    (972) 424-6422

  • Eurofins Xenco, LLC -Dallas

    Dallas, TX · about 42 miles

    Certified for bacteria

    (281) 240-4200

All 80 certified labs for Texas⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Texas certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Texas’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID TX0490027. Rebuilt from EPA data on Oct. 25, 2026.