Skip to content
TapBuff

Lake Vista Utility

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
834 people
Connections
278
Water source
Groundwater
Based in
Austin, TX
County
Live Oak
Owner
Private
The ZIP code it serves

78383

The short answer

1 result is above the limit’s level with no violation recorded, and 1 more is above the health goal. The worst: Arsenic, above the limit’s level, no violation. No health-based violations on file since 2016.

What handles it

What was found

Arsenic, uranium, fluoride, nitrate, chromium (total), haloacetic acids (HAA5) and total trihalomethanes (TTHM): Texas’s own results, samples taken from Feb. 13, 2020 to July 30, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the limit’s level, no violation recorded1

Arsenic

Comes from the source

Above the limit’s level, no violation

11.6ppb

Highest yearly average, 2020 to 2026

2026 average: 0.67 ppb

Averaged by year, the highest was 11.6 ppb, in 2020, above EPA’s legal limit of 10 ppb. Its highest single sample was 12.3 ppb. In 2026, the latest year on file, its three samples averaged 0.67 ppb. EPA judges this limit on running averages at each sampling point, and recorded no violation for arsenic at this utility since 2020. Results like these with no violation often include water sampled before treatment or blending; the utility’s annual report says what reaches the tap. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 10.3 ppb, in 2019.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Above the health goal1

Uranium

Comes from the source

Above the health goal

11.2ppb

Highest yearly average, 2021 to 2026

Averaged by year, the highest was 11.2 ppb, in 2026: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 9.7 ppb, in 2018.

What handles it

Below EPA’s limits5

Fluoride

Forms or is added in treatment

Below EPA’s limits

1.6ppm

Highest yearly average, 2021 to 2026

2026, one sample: 1.4 ppm

Averaged by year, the highest was 1.6 ppm, in 2024, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its one sample was 1.4 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.6 ppm, in 2012.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

2.8ppm

Highest sample; found in 14 of 14

2026 average: 2.2 ppm

The highest sample, in 2021, was 2.8 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its two samples averaged 2.2 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 2.8 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

11.1ppb

Highest yearly average, 2021 to 2026

2026: not found

Averaged by year, the highest was 11.1 ppb, in 2023, below EPA’s legal limit of 100 ppb. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 14.9 ppb, in 2018.

What handles it

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

4.4ppb

Highest yearly average, 2020 to 2026

2026: not found

Averaged by year, the highest was 4.4 ppb, in 2020, below EPA’s legal limit of 60 ppb. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.7 ppb, in 2019.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

2.4ppb

Highest yearly average, 2020 to 2026

2026: not found

Averaged by year, the highest was 2.4 ppb, in 2024, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 4.5 ppb, in 2013.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claim: Arsenic (Pentavalent)<=50 ppb Reduction

    For: Arsenic

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Uranium

    For: Arsenic, Uranium

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

No health-based violations on file with EPA since 2016. There are 19 monitoring or reporting violations: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Arsenic, uranium, fluoride, nitrate, chromium (total), haloacetic acids (HAA5) and total trihalomethanes (TTHM) results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Lake Vista Utility’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Feb. 13, 2020 to July 30, 2026.

Testing your own tap

Lake Vista Utility’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The lab Texas certifies closest to the area Lake Vista Utility serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Corpus Christi -Nueces County Public Health District Laboratory

    Corpus Christi, TX · about 39 miles

    Certified for bacteria

    (361) 826-7213

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX1490017. Rebuilt from EPA data on Oct. 18, 2026.