Skip to content
TapBuff

Grand Harbor WSC

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
360 people
Connections
120
Water source
Surface water bought from another system
Based in
Chico, TX
County
Wise
Owner
Private
The ZIP code it serves

76431

The short answer

2 results are above EPA’s legal limit. The worst: Total trihalomethanes (TTHM), above the legal limit. 52 health-based violations since 2016.

What handles it

What was found

Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate: Texas’s own results, samples taken from Feb. 13, 2020 to Sept. 23, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit2

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

190ppb

Highest yearly average, 2020 to 2026

2026 average: 135 ppb

Averaged by year, the highest was 190 ppb, in 2025, about 2.4 times EPA’s legal limit of 80 ppb. Its highest single sample was 278 ppb. In 2026, the latest year on file, its three samples averaged 135 ppb, above the limit. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2020, 2021, 2022, 2023, 2024, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 176 ppb, in 2019, and EPA recorded violations in 2015, 2016, 2017 and 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Above the legal limit

123ppb

Highest yearly average, 2020 to 2026

2026 average: 111 ppb

Averaged by year, the highest was 123 ppb, in 2025, about twice EPA’s legal limit of 60 ppb. Its highest single sample was 187 ppb. In 2026, the latest year on file, its three samples averaged 111 ppb, above the limit. EPA recorded violations for haloacetic acids (HAA5) at this utility in 2020, 2021, 2024, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 74.8 ppb, in 2019, and EPA recorded a violation in 2019.

What handles it

No certification claim covers this compound yet.

Below EPA’s limits1

Nitrate

Comes from the source

Below EPA’s limits

0.47ppm

Highest sample; found in 6 of 6

2025, one sample: 0.36 ppm

The highest sample, in 2020, was 0.47 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its one sample was 0.36 ppm.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claim: Trihalomethanes (TTHM) Reduction

    For: Total trihalomethanes (TTHM)

    Other certifiers’ wording: VOC Reduction

  • NSF/ANSI 58

    Claim: Trihalomethanes (TTHM) Reduction

    For: Total trihalomethanes (TTHM)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2026 to June 30, 20260.2 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2026 to June 30, 20260.14 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.13 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.19 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.19 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.12 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.1 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.17 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2025 to June 30, 20250.18 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2025 to June 30, 20250.11 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 20250.11 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 20250.18 MG/LArchived
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.18 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.098 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 20240.098 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 20240.2 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 20240.072 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 20240.15 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2024 to March 31, 20240.11 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2023 to Dec. 31, 20230.11 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2023 to Sept. 30, 20230.1 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2023 to June 30, 20230.15 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2023 to March 31, 20230.14 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2022 to Dec. 31, 20220.13 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2022 to Sept. 30, 20220.13 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2022 to June 30, 20220.082 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2022 to March 31, 20220.083 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2021 to Dec. 31, 20210.095 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 20210.093 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2021 to June 30, 20210.1 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2021 to March 31, 20210.067 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2021 to March 31, 20210.13 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2020 to Dec. 31, 20200.15 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2020 to Dec. 31, 20200.075 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2020 to Sept. 30, 20200.17 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2020 to Sept. 30, 20200.071 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 20200.21 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 20200.11 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2020 to March 31, 20200.094 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 177 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Grand Harbor WSC’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Feb. 13, 2020 to Sept. 23, 2026.

Testing your own tap

Grand Harbor WSC’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The 3 labs Texas certifies closest to the area Grand Harbor WSC serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Tarrant County Public Health Laboratory

    Fort Worth, TX · about 53 miles

    Certified for bacteria

    (817) 321-4758

  • Wichita Falls Wichita County Public Health District Laboratory

    Wichita Falls, TX · about 53 miles

    Certified for bacteria

    (940) 761-7873

  • Pace Analytical Services, LLC -Dallas TX

    Fort Worth, TX · about 54 miles

    Certified for bacteria

    (817) 616-5030

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX2490070. Rebuilt from EPA data on Oct. 18, 2026.