What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
363 people
Connections
121
Water source
Groundwater
Based in
Henderson, TX
County
Rusk
Owner
Local government
The ZIP code it serves

75654

The short answer

1 result is above EPA’s legal limit. The worst: Total trihalomethanes (TTHM), above the legal limit. 2 health-based violations since 2016.

What handles it

What was found

Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic, chromium (total) and uranium: Texas’s own results, samples taken from March 11, 2020 to Sept. 3, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit1

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

101ppb

Highest yearly average, 2020 to 2026

2026 average: 18.4 ppb

Averaged by year, the highest was 101 ppb, in 2024, above EPA’s legal limit of 80 ppb. Its highest single sample was 145 ppb. In 2026, the latest year on file, its three samples averaged 18.4 ppb. EPA recorded a violation for total trihalomethanes (TTHM) at this utility in 2024. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 118 ppb, in 2013, and EPA recorded violations in 2012 and 2013.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Below EPA’s limits3

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

46.8ppb

Highest yearly average, 2020 to 2026

2026 average: 2.9 ppb

Averaged by year, the highest was 46.8 ppb, in 2024, below EPA’s legal limit of 60 ppb. Its highest single sample was 59.7 ppb. In 2026, the latest year on file, its three samples averaged 2.9 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 51.4 ppb, in 2013.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

1.5ppm

Highest yearly average, 2021 to 2024

Averaged by year, the highest was 1.5 ppm, in 2024, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.6 ppm, in 2012.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.2ppm

Highest sample; found in 7 of 7

2026, one sample: 0.068 ppm

The highest sample, in 2020, was 0.2 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was 0.068 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.099 ppm, in 2018.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Uranium

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claim: Trihalomethanes (TTHM) Reduction

    For: Total trihalomethanes (TTHM)

    Other certifiers’ wording: VOC Reduction

  • NSF/ANSI 58

    Claim: Trihalomethanes (TTHM) Reduction

    For: Total trihalomethanes (TTHM)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.1 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 20240.11 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 7 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic, chromium (total) and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Goodsprings WSC Plant C’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from March 11, 2020 to Sept. 3, 2026.

Testing your own tap

Goodsprings WSC Plant C’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The 3 labs Texas certifies closest to the area Goodsprings WSC Plant C serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Southern Petroleum Laboratories (SPL), Inc. (FKA Ana-Lab Corporation)

    Kilgore, TX · about 21 miles

    Certified for bacteria, lead and copper

    (903) 984-0551

  • Analytical Environmental Labs

    Tyler, TX · about 31 miles

    Certified for bacteria

    (903) 509-8700

  • Environmental Monitoring Lab

    Winona, TX · about 32 miles

    Certified for bacteria

    (903) 877-9222

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX2010038. Rebuilt from EPA data on Oct. 18, 2026.