Skip to content
TapBuff

Fort Bend County MUD 218

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
2,412 people
Connections
804
Water source
Surface water bought from another system
Based in
Houston, TX
County
Fort Bend
Owner
Local government
The ZIP code it serves

77469

The short answer

Nothing in EPA’s and Texas’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.

What was found

Haloacetic acids (HAA5), total trihalomethanes (TTHM) and nitrate: Texas’s own results, samples taken from May 18, 2020 to Aug. 11, 2026.

Below EPA’s limits3

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

52.9ppb

Highest yearly average, 2020 to 2026

2026 average: 15.6 ppb

Averaged by year, the highest was 52.9 ppb, in 2021, below EPA’s legal limit of 60 ppb. In 2026, the latest year on file, its three samples averaged 15.6 ppb.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

51.3ppb

Highest yearly average, 2020 to 2026

2026 average: 33.3 ppb

Averaged by year, the highest was 51.3 ppb, in 2025, below EPA’s legal limit of 80 ppb. Its highest single sample was 111 ppb. In 2026, the latest year on file, its three samples averaged 33.3 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Nitrate

Comes from the source

Below EPA’s limits

1.7ppm

Highest sample; found in 25 of 26

2026 average: 0.81 ppm

The highest sample, in 2021, was 1.7 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its three samples averaged 0.81 ppm.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

Violations since 2016

No health-based violations on file with EPA since 2016. There are 6 monitoring or reporting violations: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM) and nitrate results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. Fort Bend County MUD 218’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from May 18, 2020 to Aug. 11, 2026.

Testing your own tap

Fort Bend County MUD 218’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The 3 labs Texas certifies closest to the area Fort Bend County MUD 218 serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Eurofins Xenco, LLC -Houston

    Stafford, TX · about 12 miles

    Certified for lead and copper

    (281) 240-4200

  • ALS Laboratory Group, Environmental Services Division – Houston, Texas

    Houston, TX · about 14 miles

    Certified for lead and copper

    (281) 530-5656

  • Envirodyne Laboratories, Inc.

    Houston, TX · about 14 miles

    Certified for bacteria, lead and copper

    (281) 568-7880

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX0790582. Rebuilt from EPA data on Oct. 18, 2026.