Skip to content
TapBuff

City of Troy

EPA’s and Texas’s records have results for 8 contaminants in its water; 4 were found.

Serves 4,367 people · Surface water bought from another system · Troy, TX

Serves
4,367 people
Connections
1,616
Water source
Surface water bought from another system
Based in
Troy, TX
County
Bell
Owner
Local government
The ZIP code it serves

76579

The short answer

None of the results here is above a limit in force today. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 4 health-based violations since 2016, all resolved in EPA’s file.

The 4 violations⁠Got a notice? What it means⁠

What was found

Where these results come from, and when

Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic, chromium (total) and uranium: Texas’s own results, samples taken from March 9, 2020 to Aug. 27, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.

Below EPA’s limits, 4 results

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 60.6 ppb

Highest yearly average, 2020 to 2026 · 2026 average: 14.4 ppb · Forms or is added in treatment

Averaged by year, the highest was 60.6 ppb, in 2021, below EPA’s legal limit of 80 ppb. Its highest single sample was 101 ppb. In 2026, the latest year on file, its three samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 83.8 ppb, in 2016, and EPA recorded violations in 2015 and 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
About total trihalomethanes (TTHM)
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 31.1 ppb

Highest yearly average, 2020 to 2026 · 2026 average: 8.8 ppb · Forms or is added in treatment

Averaged by year, the highest was 31.1 ppb, in 2024, below EPA’s legal limit of 60 ppb. Its highest single sample was 52.2 ppb. In 2026, the latest year on file, its three samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 40.4 ppb, in 2015.

What handles it

No certification claim covers this compound yet.

About haloacetic acids (HAA5)
Fluoride, Legal limit 4.0 ppm; highest yearly average 2.0 ppm

Highest yearly average, 2021 to 2025 · Forms or is added in treatment

Averaged by year, the highest was 2.0 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.25 ppm, in 2015.

What handles it

About fluoride
Nitrate, Legal limit 10 ppm; highest 1.4 ppm

Highest sample; found in 20 of 24 · 2026 average: 0.52 ppm · Comes from the source

The highest sample, in 2024, was 1.4 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its three samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest sample of 1.6 ppm, in 2015.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Uranium

Violations since 2016

4 health-based violations since 2016, all for TTHM. The latest began Oct. 1, 2016.

Resolved:
EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
No fix on record:
It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).

EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Got a notice about one? What it means and what to do⁠
Health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 2016, 84 ppbResolved
July 1, 2016 to Sept. 30, 2016, 108 ppbResolved
April 1, 2016 to June 30, 2016, 110 ppbResolved
Jan. 1, 2016 to March 31, 2016, 99 ppbResolved

Health-based violations only. 5 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic, chromium (total) and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Troy’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from March 9, 2020 to Aug. 27, 2026.

Testing your own tap

City of Troy’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. City of Troy’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Texas certifies closest to the area City of Troy serves, or a kit by mail

The 3 labs Texas certifies closest to the area City of Troy serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Bio-Chem Lab, Inc.

    West, TX · about 41 miles

    Certified for bacteria, lead and copper

    (254) 829-8001

  • Environmental Monitoring Lab

    Hillsboro, TX · about 58 miles

    Certified for bacteria

    (254) 582-2622

  • Aqua-Tech Laboratories, Inc.

    Bryan, TX · about 59 miles

    Certified for bacteria, lead and copper

    (979) 778-3707

All 80 certified labs for Texas⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Texas certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Texas’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID TX0140037. Rebuilt from EPA data on Oct. 25, 2026.