Skip to content
TapBuff

City of Runaway Bay

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
2,458 people
Connections
1,296
Water source
Surface water
Based in
Runaway Bay, TX
County
Wise
Owner
Local government
The ZIP code it serves

76426

The short answer

1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Total trihalomethanes (TTHM), above the legal limit. 14 health-based violations since 2016.

What handles it

What was found

Total trihalomethanes (TTHM), arsenic, haloacetic acids (HAA5), fluoride, nitrate, chromium (total) and uranium: Texas’s own results, samples taken from Feb. 13, 2020 to Aug. 10, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit1

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

89ppb

Highest yearly average, 2020 to 2026

2026 average: 62.6 ppb

Averaged by year, the highest was 89 ppb, in 2021, above EPA’s legal limit of 80 ppb. Its highest single sample was 118 ppb. In 2026, the latest year on file, its six samples averaged 62.6 ppb. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2020, 2021, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 88 ppb, in 2016, and EPA recorded violations in 2016 and 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Above the health goal1

Arsenic

Comes from the source

Above the health goal

1.5ppb

Highest yearly average, 2020 to 2026

2026, one sample: 1.0 ppb

Averaged by year, the highest was 1.5 ppb, in 2020: below EPA’s legal limit of 10 ppb, but above its health goal of zero. In 2026, the latest year on file, its one sample was 1.0 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.8 ppb, in 2016.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Below EPA’s limits4

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

57.8ppb

Highest yearly average, 2020 to 2026

2026 average: 36.3 ppb

Averaged by year, the highest was 57.8 ppb, in 2025, below EPA’s legal limit of 60 ppb. Its highest single sample was 91.5 ppb. In 2026, the latest year on file, its six samples averaged 36.3 ppb. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 58.9 ppb, in 2016, and EPA recorded a violation in 2016.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.18ppm

Highest yearly average, 2020 to 2026

2026, one sample: 0.13 ppm

Averaged by year, the highest was 0.18 ppm, in 2023, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its one sample was 0.13 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.24 ppm, in 2014.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.32ppm

Highest sample; found in 7 of 7

2026, one sample: 0.12 ppm

The highest sample, in 2025, was 0.32 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was 0.12 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.36 ppm, in 2016.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

2.0ppb

Highest yearly average, 2020 to 2026

2026: not found

Averaged by year, the highest was 2.0 ppb, in 2021, below EPA’s legal limit of 100 ppb. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.9 ppb, in 2014.

What handles it

2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead
  • Uranium

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Total trihalomethanes (TTHM), Arsenic

    Other certifiers’ wording: VOC Reduction; Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Total trihalomethanes (TTHM), Arsenic

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2026 to June 30, 20260.081 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.087 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.087 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.081 MG/LArchived
Interim Enhanced Surface Water Treatment RuleToo many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR)May 1, 2025 to May 31, 2025—Resolved
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2021 to Dec. 31, 20210.092 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 20210.083 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 20200.086 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2017 to March 31, 20170.091 MG/LResolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 20160.061 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 20160.093 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2016 to Sept. 30, 20160.089 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 20160.099 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 24 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), arsenic, haloacetic acids (HAA5), fluoride, nitrate, chromium (total) and uranium results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Runaway Bay’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Feb. 13, 2020 to Aug. 10, 2026.

Testing your own tap

City of Runaway Bay’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The 3 labs Texas certifies closest to the area City of Runaway Bay serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Tarrant County Public Health Laboratory

    Fort Worth, TX · about 43 miles

    Certified for bacteria

    (817) 321-4758

  • Pace Analytical Services, LLC -Dallas TX

    Fort Worth, TX · about 45 miles

    Certified for bacteria

    (817) 616-5030

  • Eurofins Xenco, LLC -Dallas

    Dallas, TX · about 60 miles

    Certified for bacteria

    (281) 240-4200

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX2490017. Rebuilt from EPA data on Oct. 18, 2026.