What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
245 people
Connections
239
Water source
Groundwater
Based in
Dell City, TX
County
Hudspeth
Owner
Local government
The ZIP code it serves

79837

The short answer

1 result is above the health goal. The worst: Uranium, above the health goal. 1 health-based violation since 2016.

What handles it

What was found

Uranium, fluoride, nitrate, chromium (total), total trihalomethanes (TTHM), arsenic and haloacetic acids (HAA5): Texas’s own results, samples taken from Dec. 7, 2020 to Aug. 4, 2025, with EPA’s 2012 to 2019 file for earlier years.

Above the health goal1

Uranium

Comes from the source

Above the health goal

3.1ppb

Highest yearly average, 2021 to 2024

2024, one sample: 3.0 ppb

Averaged by year, the highest was 3.1 ppb, in 2021: below EPA’s legal limit of 30 ppb, but above its health goal of zero. In 2024, the latest year on file, its one sample was 3.0 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.7 ppb, in 2015.

What handles it

Below EPA’s limits4

Fluoride

Forms or is added in treatment

Below EPA’s limits

1.3ppm

Highest yearly average, 2021 to 2024

2024, one sample: 1.2 ppm

Averaged by year, the highest was 1.3 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. In 2024, the latest year on file, its one sample was 1.2 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.3 ppm, in 2018.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

1.4ppm

Highest sample; found in 6 of 6

2025, one sample: 1.2 ppm

The highest sample, in 2022, was 1.4 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its one sample was 1.2 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 1.4 ppm, in 2019.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

6.2ppb

Highest yearly average, 2022 to 2025

2025: not found

Averaged by year, the highest was 6.2 ppb, in 2022, below EPA’s legal limit of 100 ppb. In 2025, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.0 ppb, in 2016.

What handles it

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

1.6ppb

Highest yearly average, 2022 to 2025

2025: not found

Averaged by year, the highest was 1.6 ppb, in 2022, below EPA’s legal limit of 80 ppb. In 2025, the latest year on file, it wasn’t found in its one sample.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
3 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Haloacetic acids (HAA5)
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

None of the filters TapBuff has checked so far carry these claims. Search the certifier listings for the claim above.

Compare five-year costs

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Addressed
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 93 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Uranium, fluoride, nitrate, chromium (total), total trihalomethanes (TTHM), arsenic and haloacetic acids (HAA5) results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Dell’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Dec. 7, 2020 to Aug. 4, 2025.

Testing your own tap

City of Dell’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The lab Texas certifies closest to the area City of Dell serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • City of El Paso Department of Public Health

    El Paso, TX · about 72 miles

    Certified for bacteria

    (915) 212-2765

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX1150001. Rebuilt from EPA data on Oct. 18, 2026.