Skip to content
TapBuff

City of Byers

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
446 people
Connections
288
Water source
Surface water bought from another system
Based in
Byers, TX
County
Clay
Owner
Local government
The ZIP code it serves

76357

The short answer

1 result is above EPA’s legal limit, and 4 more are above the health goal. The worst: Total trihalomethanes (TTHM), above the legal limit. 25 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 1994 to 2025.

Total trihalomethanes (TTHM), nitrate, arsenic, uranium, haloacetic acids (HAA5), fluoride and chromium (total): Texas’s own results, samples taken from March 3, 2020 to Aug. 11, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit1

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

88.2ppb

Highest yearly average, 2020 to 2026

2026 average: 51.2 ppb

Averaged by year, the highest was 88.2 ppb, in 2024, above EPA’s legal limit of 80 ppb. Its highest single sample was 123 ppb. In 2026, the latest year on file, its six samples averaged 51.2 ppb. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2020, 2024, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 140 ppb, in 2015, and EPA recorded violations in 2017, 2018 and 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Above the health goal4

Nitrate

Comes from the source

Above the health goal

13.5ppm

Highest sample; found in 28 of 28

2026 average: 7.8 ppm

One sample, in 2023, was above EPA’s legal limit of 10 ppm, at 13.5 ppm. The next sample at the same point, within 30 days, brought the average back under the limit. 10 ppm is also EPA’s health goal. In 2026, the latest year on file, its three samples averaged 7.8 ppm. EPA recorded no violation for nitrate at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 17.5 ppm, in 2017, and EPA recorded violations in 2013, 2014, 2015 and 2017.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Arsenic

Comes from the source

Above the health goal

1.1ppb

Highest yearly average, 2022 to 2026

2026, one sample: 1.1 ppb

Averaged by year, the highest was 1.1 ppb, in 2025: below EPA’s legal limit of 10 ppb, but above its health goal of zero. In 2026, the latest year on file, its one sample was 1.1 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.0 ppb, in 2019.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Uranium

Comes from the source

Above the health goal

2.7ppb

Highest yearly average, 2022

Averaged by year, the highest was 2.7 ppb, in 2022: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.5 ppb, in 2016.

What handles it

Lead

Comes from pipes, often your own

Above the health goal

0.6ppb

90th percentile, 2025

In the latest period, 9 in 10 homes sampled were at or below 0.6 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits3

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

28.6ppb

Highest yearly average, 2020 to 2026

2026 average: 18.9 ppb

Averaged by year, the highest was 28.6 ppb, in 2025, below EPA’s legal limit of 60 ppb. Its highest single sample was 41.8 ppb. In 2026, the latest year on file, its six samples averaged 18.9 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 43.6 ppb, in 2019.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.7ppm

Highest yearly average, 2021 to 2026

2026, one sample: 0.63 ppm

Averaged by year, the highest was 0.7 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its one sample was 0.63 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.65 ppm, in 2018.

What handles it

Chromium (total)

Comes from the source

Below EPA’s limits

4.6ppb

Highest yearly average, 2022 to 2026

2026, one sample: 1.0 ppb

Averaged by year, the highest was 4.6 ppb, in 2023, below EPA’s legal limit of 100 ppb. In 2026, the latest year on file, its one sample was 1.0 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.3 ppb, in 2016.

What handles it

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Nitrate/Nitrite (30 ppm challenge), Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Nitrate, Arsenic, Lead

    Other certifiers’ wording: VOC Reduction; Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Nitrate/Nitrite Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Uranium, Lead Reduction

    For: Total trihalomethanes (TTHM), Nitrate, Arsenic, Uranium, Lead

    Other certifiers’ wording: Nitrate; Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2026 to June 30, 20260.094 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.089 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.095 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.096 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2025 to June 30, 20250.1 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 20250.11 MG/LArchived
Lead and Copper Rule RevisionsThe required inventory of lead service lines was not completed or submitted on time.EPA: LSL InventoryOct. 17, 2024—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.11 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 20240.1 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 20240.096 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 20200.091 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2020 to March 31, 20200.1 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2019 to Dec. 31, 20190.11 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2019 to Dec. 31, 20190.084 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 20190.1 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2019 to June 30, 20190.099 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2019 to March 31, 20190.086 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2018 to Dec. 31, 20180.082 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2018 to Sept. 30, 20180.082 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2018 to March 31, 20180.089 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2017 to Dec. 31, 201718 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2017 to Dec. 31, 20170.086 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 20170.083 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2017 to June 30, 20170.085 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2017 to March 31, 201711 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 54 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), nitrate, arsenic, uranium, haloacetic acids (HAA5), fluoride and chromium (total) results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Byers’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from March 3, 2020 to Aug. 11, 2026.

Testing your own tap

City of Byers’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The lab Texas certifies closest to the area City of Byers serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Wichita Falls Wichita County Public Health District Laboratory

    Wichita Falls, TX · about 21 miles

    Certified for bacteria

    (940) 761-7873

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX0390003. Rebuilt from EPA data on Oct. 18, 2026.