Skip to content
TapBuff

City of Annona

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
339 people
Connections
113
Water source
Surface water bought from another system
Based in
Annona, TX
County
Red River
Owner
Local government
The ZIP code it serves

75550

The short answer

Nothing in EPA’s and Texas’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 12 health-based violations since 2016.

What was found

Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate: Texas’s own results, samples taken from Feb. 11, 2020 to Sept. 8, 2026, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits3

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

80.1ppb

Highest yearly average, 2020 to 2026

Averaged by year, the highest was 80.1 ppb, in 2026, which EPA rounds to 80 ppb to compare: at its legal limit of 80 ppb, not above it. Its highest single sample was 160 ppb. That was also the latest year on file. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 132 ppb, in 2014, and EPA recorded violations in 2012, 2013, 2014, 2015, 2016, 2017, 2018 and 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

40.4ppb

Highest yearly average, 2020 to 2026

2026 average: 21.4 ppb

Averaged by year, the highest was 40.4 ppb, in 2025, below EPA’s legal limit of 60 ppb. Its highest single sample was 104 ppb. In 2026, the latest year on file, its three samples averaged 21.4 ppb. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 59.2 ppb, in 2017.

What handles it

No certification claim covers this compound yet.

Nitrate

Comes from the source

Below EPA’s limits

0.98ppm

Highest sample; found in 6 of 6

2025, one sample: 0.98 ppm

The highest sample, in 2025, was 0.98 ppm, below EPA’s legal limit of 10 ppm. That was also the latest year on file, and its one sample was 0.98 ppm.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Revised Total Coliform RuleColiform results required a check of the system, and the check or its fixes were not done on time.EPA: Treatment Technique, Level 1 Assessment (RTCR)Sept. 25, 2021—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 20190.084 MG/LResolved
Revised Total Coliform RuleColiform results required a check of the system, and the check or its fixes were not done on time.EPA: Treatment Technique, Level 1 Assessment (RTCR)Sept. 29, 2018—Resolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2018 to March 31, 20180.09 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2017 to Dec. 31, 20170.11 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 20170.11 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2017 to June 30, 20170.11 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2017 to March 31, 20170.087 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 20160.081 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2016 to Sept. 30, 20160.098 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 20160.099 MG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2016 to March 31, 20160.11 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 55 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Annona’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Feb. 11, 2020 to Sept. 8, 2026.

Testing your own tap

City of Annona’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The lab Texas certifies closest to the area City of Annona serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Environmental Monitoring Lab

    Winona, TX · about 72 miles

    Certified for bacteria

    (903) 877-9222

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX1940004. Rebuilt from EPA data on Oct. 18, 2026.