Skip to content
TapBuff

City of Ackerly

What EPA’s and Texas’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
245 people
Connections
148
Water source
Groundwater
Based in
Ackerly, TX
County
Dawson
Owner
Local government
The ZIP code it serves

79713

The short answer

2 results are above EPA’s legal limit, and 1 more is above the health goal. The worst: Nitrate, above the legal limit. 15 health-based violations since 2016.

What handles it

What was found

Nitrate, arsenic, uranium, fluoride, haloacetic acids (HAA5), total trihalomethanes (TTHM) and chromium (total): Texas’s own results, samples taken from Jan. 15, 2020 to July 7, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit2

Nitrate

Comes from the source

Above the legal limit

14.7ppm

Highest sample; found in 27 of 27

2026 average: 10.3 ppm

From 2020 to 2026, five samples were above EPA’s legal limit of 10 ppm, the highest 14.7 ppm in 2021. Five have no follow-up sample on file within 30 days. In 2026, the latest year on file, its three samples averaged 10.3 ppm. EPA recorded violations for nitrate at this utility in 2020, 2021, 2024, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 12.3 ppm, in 2017, and EPA recorded violations in 2016 and 2017.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Arsenic

Comes from the source

Above the legal limit

12.3ppb

Highest yearly average, 2020 to 2026

2026 average: 3.1 ppb

Averaged by year, the highest was 12.3 ppb, in 2025, above EPA’s legal limit of 10 ppb. Its highest single sample was 13.9 ppb. In 2026, the latest year on file, its three samples averaged 3.1 ppb. EPA recorded violations for arsenic at this utility in 2024, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 8.6 ppb, in 2018.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Above the health goal1

Uranium

Comes from the source

Above the health goal

9.2ppb

Highest yearly average, 2021

Averaged by year, the highest was 9.2 ppb, in 2021: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 8.2 ppb, in 2015.

What handles it

Below EPA’s limits4

Fluoride

Forms or is added in treatment

Below EPA’s limits

3.3ppm

Highest yearly average, 2022 to 2025

Averaged by year, the highest was 3.3 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.1 ppm, in 2016.

What handles it

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

23.6ppb

Highest yearly average, 2022 to 2025

Averaged by year, the highest was 23.6 ppb, in 2025, below EPA’s legal limit of 60 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 5.0 ppb, in 2016.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

28ppb

Highest yearly average, 2022 to 2025

Averaged by year, the highest was 28 ppb, in 2025, below EPA’s legal limit of 80 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 16.8 ppb, in 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Chromium (total)

Comes from the source

Below EPA’s limits

4.5ppb

Highest yearly average, 2021 to 2024

2024, one sample: 2.6 ppb

Averaged by year, the highest was 4.5 ppb, in 2021, below EPA’s legal limit of 100 ppb. In 2024, the latest year on file, its one sample was 2.6 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 3.7 ppb, in 2015.

What handles it

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Nitrate/Nitrite (30 ppm challenge), Arsenic (Pentavalent)<=50 ppb Reduction

    For: Nitrate, Arsenic

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Nitrate/Nitrite Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Uranium

    For: Nitrate, Arsenic, Uranium

    Other certifiers’ wording: Nitrate; Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2026 to March 31, 202611 MG/LArchived
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.011 MG/LArchived
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.012 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2025 to Sept. 30, 202512 MG/LArchived
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.013 MG/LArchived
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2025 to June 30, 20250.014 MG/LArchived
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 20250.013 MG/LArchived
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.011 MG/LArchived
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2024 to March 31, 202411 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2021 to Sept. 30, 202115 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJan. 1, 2020 to March 31, 202011 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleOct. 1, 2017 to Dec. 31, 201711 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2017 to Sept. 30, 201712 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleApril 1, 2017 to June 30, 201711 MG/LResolved
NitrateA sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single SampleJuly 1, 2016 to Sept. 30, 201612 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 16 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Nitrate, arsenic, uranium, fluoride, haloacetic acids (HAA5), total trihalomethanes (TTHM) and chromium (total) results here are Texas’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Ackerly’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Texas’s results run from Jan. 15, 2020 to July 7, 2026.

Testing your own tap

City of Ackerly’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Texas certifies.

The lab Texas certifies closest to the area City of Ackerly serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Eurofins Xenco, LLC -Lubbock

    Lubbock, TX · about 68 miles

    Certified for bacteria

    (806) 794-1296

Texas Well Owner Network, Texas A&M AgriLife Extension: Well Informed screening events, where well owners bring in water samples to be screened for common contaminants, followed by an hour-long session explaining the results. Upcoming events are on the network's calendar. Trainings, Texas Well Owner Network.

All 80 certified labs for Texas

Sources

PWSID TX0580011. Rebuilt from EPA data on Oct. 18, 2026.