Skip to content
TapBuff

State Line Muni Svcs Auth

What EPA’s and Pennsylvania’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
95 people
Connections
34
Water source
Surface water bought from another system
Based in
Point Marion, PA
County
Fayette
Owner
Local government
The 2 ZIP codes it serves

15320, 15459

The short answer

1 result is above the limit’s level with no violation recorded, and 1 more is above the health goal. The worst: Total trihalomethanes (TTHM), above the limit’s level, no violation. 6 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 1994 to 1996.

Total trihalomethanes (TTHM) and haloacetic acids (HAA5): Pennsylvania’s own results, samples taken from March 16, 2020 to Sept. 15, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the limit’s level, no violation recorded1

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the limit’s level, no violation

102ppb

Highest yearly average, 2020 to 2026

Averaged by year, the highest was 102 ppb, in 2026, above EPA’s legal limit of 80 ppb. Its highest single sample was 102 ppb. That was also the latest year on file. EPA judges this limit on running averages at each sampling point, and recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Results like these with no violation often include water sampled before treatment or blending; the utility’s annual report says what reaches the tap. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 147 ppb, in 2016, and EPA recorded a violation in 2013.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Above the health goal1

Lead

Comes from pipes, often your own

Above the health goal

2.0ppb

90th percentile, 1996

In the latest period, 9 in 10 homes sampled were at or below 2.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits1

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

33.3ppb

Highest yearly average, 2020 to 2026

2026, one sample: 27.6 ppb

Averaged by year, the highest was 33.3 ppb, in 2025, below EPA’s legal limit of 60 ppb. Its highest single sample was 51.5 ppb. In 2026, the latest year on file, its one sample was 27.6 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 31.4 ppb, in 2019.

What handles it

No certification claim covers this compound yet.

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

    Other certifiers’ wording: VOC Reduction

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Revised Total Coliform RuleColiform results required a check of the system, and the check or its fixes were not done on time.EPA: Treatment Technique, Level 1 Assessment (RTCR)Sept. 12, 2021—Resolved
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Sept. 1, 2021—Resolved
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Aug. 1, 2021—Resolved
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)July 1, 2021—Resolved
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Dec. 1, 2020—Resolved
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Jan. 1, 2020—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 38 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are Pennsylvania’s own from 2020 on, with EPA’s national file for 2012 to 2019. State Line Muni Svcs Auth’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Pennsylvania’s results run from March 16, 2020 to Sept. 15, 2026.

Testing your own tap

State Line Muni Svcs Auth’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Pennsylvania certifies.

The 3 labs Pennsylvania certifies closest to the area State Line Muni Svcs Auth serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • H & H Water Controls Inc

    Carmichaels, PA · about 14 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (724) 966-2278

  • Pace Analytical Services, LLC-Van Voorhis

    Van Voorhis, PA · about 26 miles

    Certified for bacteria

    (724) 463-8378

  • Pace Analytical Services LLC - Greensburg PA

    Greensburg, PA · about 35 miles

    Certified for metals, radioactivity

    (724) 850-5600

Penn State Agricultural Analytical Services Laboratory: Drinking water test kits from many county Extension offices, mailed back to the lab overnight with payment. Packages cover bacteria and basic chemistry, with add-ons for nitrate, metals, lead, and mining or gas drilling concerns. The standard package of bacteria, pH and total dissolved solids is $60, or $70 with nitrate; bacteria alone is $40, nitrate $15 and lead $25. Drinking Water Testing, Penn State Agricultural Analytical Services Lab.

All 108 certified labs for Pennsylvania

Sources

PWSID PA5260035. Rebuilt from EPA data on Oct. 18, 2026.