What EPA’s and Pennsylvania’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
2,907 people
Connections
974
Water source
Surface water bought from another system
Based in
Pottstown, PA
County
Chester
Owner
Local government
The ZIP code it serves

19465

The short answer

Nothing in EPA’s and Pennsylvania’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 2 health-based violations since 2016.

What was found

Lead and copper: lead at 0.8 mg/L (2003) is left out of this report: more than 20 times the action level, it looks like µg/L entered as mg/L.

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 2.0 ppm, for the period ending June 30, 2003. None since is on file, so it is not counted as a current finding.

Total trihalomethanes (TTHM) and haloacetic acids (HAA5): Pennsylvania’s own results, samples taken from March 11, 2020 to Sept. 9, 2026, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits2

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

55.9ppb

Highest yearly average, 2020 to 2026

2026 average: 51.8 ppb

Averaged by year, the highest was 55.9 ppb, in 2020, below EPA’s legal limit of 80 ppb. Its highest single sample was 109 ppb. In 2026, the latest year on file, its 12 samples averaged 51.8 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 55.7 ppb, in 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

30.4ppb

Highest yearly average, 2020 to 2026

Averaged by year, the highest was 30.4 ppb, in 2026, below EPA’s legal limit of 60 ppb. Its highest single sample was 55.4 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 23.1 ppb, in 2017.

What handles it

No certification claim covers this compound yet.

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Oct. 1, 2021—Resolved
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Dec. 1, 2020—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 17 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are Pennsylvania’s own from 2020 on, with EPA’s national file for 2012 to 2019. North Coventry Water System’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Pennsylvania’s results run from March 11, 2020 to Sept. 9, 2026.

Testing your own tap

North Coventry Water System’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Pennsylvania certifies.

The 3 labs Pennsylvania certifies closest to the area North Coventry Water System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • M. J. Reider Associates Inc

    Reading, PA · about 16 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS

    (610) 374-5129

  • Analytical Laboratories, Inc

    Telford, PA · about 19 miles

    Certified for bacteria, nitrate

    (215) 723-6466

  • SPL - Reading

    Reading, PA · about 20 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS, radioactivity

    (610) 375-8378

Penn State Agricultural Analytical Services Laboratory: Drinking water test kits from many county Extension offices, mailed back to the lab overnight with payment. Packages cover bacteria and basic chemistry, with add-ons for nitrate, metals, lead, and mining or gas drilling concerns. The standard package of bacteria, pH and total dissolved solids is $60, or $70 with nitrate; bacteria alone is $40, nitrate $15 and lead $25. Drinking Water Testing, Penn State Agricultural Analytical Services Lab.

All 108 certified labs for Pennsylvania

Sources