Skip to content
TapBuff

Pamelia Town WD #2

What EPA’s and New York’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
150 people
Connections
35
Water source
Surface water bought from another system
Based in
Pamelia (T), NY
County
Jefferson
Owner
Local government
The ZIP code it serves

13601

The short answer

2 results are above EPA’s legal limit, and 1 more is above the health goal. The worst: Haloacetic acids (HAA5), above the legal limit. 13 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2003.

Haloacetic acids (HAA5) and total trihalomethanes (TTHM): New York’s yearly summaries per water system, 2020 to 2024, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit2

Haloacetic acids (HAA5)

Forms or is added in treatment

Above the legal limit

80.2ppb

Highest yearly average, 2020 to 2024

2024 average: 27.4 ppb

Averaged by year, the highest was 80.2 ppb, in 2021, above EPA’s legal limit of 60 ppb. Its highest single sample was 128 ppb. In 2024, the latest year on file, it averaged 27.4 ppb. EPA recorded violations for haloacetic acids (HAA5) at this utility in 2021 and 2022. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 54.7 ppb, in 2018.

What handles it

No certification claim covers this compound yet.

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

77.3ppb

Highest yearly average, 2020 to 2024

2024 average: 34 ppb

Averaged by year, the highest was 77.3 ppb, in 2020, below EPA’s legal limit of 80 ppb. Its highest single sample was 116 ppb. In 2024, the latest year on file, it averaged 34 ppb. EPA judges this limit at each sampling point, and recorded a violation for total trihalomethanes (TTHM) at this utility in 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 100 ppb, in 2019, and EPA recorded violations in 2016, 2017 and 2019.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Above the health goal1

Lead

Comes from pipes, often your own

Above the health goal

3.1ppb

90th percentile, 2001 to 2003

In the latest period, 9 in 10 homes sampled were at or below 3.1 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

    Other certifiers’ wording: VOC Reduction

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2022 to March 31, 202262.5 UG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2021 to Dec. 31, 202180.2 UG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2021 to Sept. 30, 202170.5 UG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2020 to June 30, 202091.6 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2020 to March 31, 202094.5 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2019 to Dec. 31, 201991.3 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2019 to Sept. 30, 201998.2 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2017 to Sept. 30, 201783.9 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2017 to June 30, 201783.1 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2017 to March 31, 201792.1 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2016 to Dec. 31, 201685.5 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2016 to Sept. 30, 201688.2 UG/LResolved
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 201683.6 UG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5) and total trihalomethanes (TTHM) results here are New York’s own yearly summaries from 2020 on, with EPA’s national file for 2012 to 2019. Pamelia Town WD #2’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; New York’s yearly summaries cover 2020 to 2024.

Testing your own tap

Pamelia Town WD #2’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab New York certifies.

The 3 labs New York certifies closest to the area Pamelia Town WD #2 serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Converse Laboratories Inc.

    Watertown, NY · under a mile

    Certified for bacteria

    (315) 788-8388

  • Oswego Water Treatment Plant Lab

    Oswego, NY · about 46 miles

    Certified for bacteria

    (315) 342-8187

  • Certified Environmental Services Inc.

    North Syracuse, NY · about 59 miles

    Certified for bacteria, nitrate, minerals and other inorganics

    (315) 478-2374

All 161 certified labs for New York

Sources