Skip to content
TapBuff

City of Shelby

EPA’s and Montana’s records have results for 37 contaminants in its water; 5 were found.

Serves 3,970 people · Groundwater · Shelby, MT · Hardness: very hard

Serves
3,970 people
Connections
1,244
Water source
Groundwater
Based in
Shelby, MT
County
Toole
Owner
Local government
Hardness
Very hard
The 2 ZIP codes it serves

59435, 59474

The short answer

None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. No health-based violations on file since 2016.

Filters for lead and uranium, if you want them lower⁠

What was found

Where these results come from, and when

PFAS and lithium: EPA UCMR 5, samples taken from Jan. 23 to July 24, 2024.

Lead and copper: EPA SDWIS monitoring periods ending 2004 to 2025.

Fluoride, uranium, nitrate, arsenic, chromium (total) and total trihalomethanes (TTHM): Montana’s own results, samples taken from Dec. 7, 2020 to March 9, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.
Health reference level:
A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.

PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.

Below EPA’s limits, 5 results

Lead and uranium have a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Action level:
Triggers action. If more than 10% of homes sampled are above it, the utility must act.
90th percentile:
How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Health reference level:
A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
Lithium, Health reference level 10 ppbAt EPA’s benchmark, as EPA rounds; highest 12 ppb

Highest sample, Jan. 23, 2024; found in 2 of 2 · Comes from the source

The highest sample was 12 ppb. As EPA rounds results, that is at EPA’s health reference level of 10 ppb, not above it: EPA counts a result as above it from 15 ppb.

What handles it

No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.

How to read your utility’s report
About lithium
Lead, Action level 15 ppb · health goal zero; 90th percentile 2.0 ppb

90th percentile, 2025 · Comes from pipes, often your own

In the latest period, 9 in 10 homes sampled were at or below 2.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

About lead
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.3 ppm

Highest yearly average, 2022 to 2026 · 2026 average: 0.15 ppm · Forms or is added in treatment

Averaged by year, the highest was 0.3 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its four samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.2 ppm, in 2013.

What handles it

About fluoride
Uranium, Legal limit 30 ppb · health goal zero; highest yearly average 1.2 ppb

Highest yearly average, 2025 · Comes from the source

Averaged by year, the highest was 1.2 ppb, in 2025, below EPA’s legal limit of 30 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. That is the only year on file.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 1.0 ppb, in 2017.

What handles it

About uranium
Nitrate, Legal limit 10 ppm; highest 0.07 ppm

Highest sample; found in 11 of 11 · 2026 average: 0.044 ppm · Comes from the source

The highest sample, in 2021, was 0.07 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its five samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest sample of 0.06 ppm, in 2019.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
Utilities above EPA’s PFAS limits, state by state⁠
32 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.

From routine monitoring

  • Arsenic
  • Chromium (total)
  • Total trihalomethanes (TTHM)

PFAS and lithium, from EPA’s UCMR 5 sampling

  • 11Cl-PF3OUdS
  • 4:2 FTS
  • 6:2 FTS
  • 8:2 FTS
  • 9Cl-PF3ONS
  • ADONA
  • HFPO-DA (GenX)
  • NEtFOSAA
  • NFDHA
  • NMeFOSAA
  • PFBA
  • PFBS
  • PFDA
  • PFDoA
  • PFEESA
  • PFHpA
  • PFHpS
  • PFHxA
  • PFHxS
  • PFMBA
  • PFMPA
  • PFNA
  • PFOA
  • PFOS
  • PFPeA
  • PFPeS
  • PFTA
  • PFTrDA
  • PFUnA

Violations since 2016

No health-based violations on file with EPA since 2016. There are 5 monitoring or reporting violations: a sample missed, late or not reported. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Skip past the filters

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

2 more filters
Compare five-year costs

Every filter for these, those that cover both first⁠

The best water filters for lead, ranked⁠

Hardness

Very hard, typically 247 mg/L (14.4 grains per gallon), across 4 sampling points, in 2026.

Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.

Disinfectant

City of Shelby reported ultraviolet light but neither chlorine nor chloramine, in its 2024 sampling for EPA.

What that means

Most utilities add chlorine or chloramine, CDC says. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.

What this report can’t tell you

  • Everything else. Fluoride, uranium, nitrate, arsenic, chromium (total) and total trihalomethanes (TTHM) results here are Montana’s own from 2020 on, with EPA’s national file for 2012 to 2019. City of Shelby’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Jan. 23 to July 24, 2024; Montana’s results run from Dec. 7, 2020 to March 9, 2026.

Testing your own tap

City of Shelby’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Montana certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. City of Shelby’s latest lead sampling in EPA’s records, 2025, had a 90th percentile of 2.0 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
Labs Montana certifies, or a kit by mail

No lab Montana certifies is within 75 miles of the area City of Shelby serves on the state’s list. Some take samples by mail; the state’s page lists them all.

All 36 certified labs for Montana⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Montana certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Montana’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID MT0000328. Rebuilt from EPA data on Oct. 25, 2026.