South Hadley Fd #1 (MWRA)
EPA’s and Massachusetts’s records have results for 34 contaminants in its water; 4 were found.
Serves 14,800 people · Surface water bought from another system · South Hadley, MA
- Serves
- 14,800 people
- Connections
- 4,938
- Water source
- Surface water bought from another system
- Based in
- South Hadley, MA
- County
- Hampshire
- Owner
- Local government
The short answer
None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. No health-based violations on file since 2016.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from Jan. 9 to Oct. 16, 2024.
Lead and copper: EPA SDWIS monitoring periods ending 2008 to 2025.
Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate: Massachusetts’s own results, samples taken from Feb. 18, 2020 to Aug. 10, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Action level:
- Triggers action. If more than 10% of homes sampled are above it, the utility must act.
- 90th percentile:
- How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
- Health goal (MCLG):
- Not enforceable. The level with no expected risk, with a margin of safety.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
Below EPA’s limits, 4 results
Lead has a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Action level:
- Triggers action. If more than 10% of homes sampled are above it, the utility must act.
- 90th percentile:
- How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 62.5 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 56.5 ppb · Forms or is added in treatment
Averaged by year, the highest was 62.5 ppb, in 2022, below EPA’s legal limit of 80 ppb. Its highest single sample was 108 ppb. In 2026, the latest year on file, its 15 samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 71.3 ppb, in 2019.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 28.4 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 17.3 ppb · Forms or is added in treatment
Averaged by year, the highest was 28.4 ppb, in 2024, below EPA’s legal limit of 60 ppb. Its highest single sample was 69.4 ppb. In 2026, the latest year on file, its 12 samples averaged below the limit. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 38.5 ppb, in 2019.
What handles it
No certification claim covers this compound yet.
Lead, Action level 15 ppb · health goal zero; 90th percentile 4.0 ppb
90th percentile, 2023 to 2025 · Comes from pipes, often your own
In the latest period, 9 in 10 homes sampled were at or below 4.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53 look for “Lead Reduction”
- NSF/ANSI 58 look for “Lead Reduction”
Nitrate, Legal limit 10 ppm; highest 0.013 ppm
One sample · 2024, one sample: 0.013 ppm · Comes from the source
The highest sample, in 2024, was 0.013 ppm, below EPA’s legal limit of 10 ppm. That is the only year on file, and its one sample was below the limit.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
30 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- Lithium
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
No health-based violations on file with EPA since 2016. There are 2 monitoring or reporting violations: a sample missed, late or not reported. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.
- NSF/ANSI 53
Claim: Lead Reduction
For: Lead
- NSF/ANSI 58
Claim: Lead Reduction
For: Lead
At the tap, or for the whole house?
These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
Express Water StreamLine Direct Connect System (USC001)
Under-sink carbon
Five years: $527, household of 3, cartridges included
Certified for: Lead
Under-sink reverse osmosis
Five years: $549, household of 3, cartridges included
WQA listing: NSF/ANSI 58, checked Oct. 9, 2026
Certified for: Lead
Frizzlife SK99 Under Sink Water Filter
Under-sink carbon
Five years: $590, household of 3, cartridges included
Certified for: Lead
2 more filters
Bluevua RO100ROPOT-Lite Countertop Reverse Osmosis System
Countertop reverse osmosis
Five years: $805, household of 3, cartridges included
WQA listing: NSF/ANSI 58, checked Oct. 9, 2026
Certified for: Lead
Brondell Coral UC300 Under Sink Water Filtration System
Under-sink carbon
Five years: $900, household of 3, cartridges included
Certified for: Lead
Disinfectant
South Hadley Fd #1 (MWRA) reported disinfecting with chlorine, not chloramine, at its one sampling point, in its 2024 sampling for EPA. It also reported ultraviolet light.
What that means
Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This utility buys its water from another system, so what it reported may leave out treatment done before the water reaches it. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5) and nitrate results here are Massachusetts’s own from 2020 on, with EPA’s national file for 2012 to 2019. South Hadley Fd #1 (MWRA)’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Jan. 9 to Oct. 16, 2024; Massachusetts’s results run from Feb. 18, 2020 to Aug. 10, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. South Hadley Fd #1 (MWRA)’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 4.0 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Massachusetts certifies closest to the area South Hadley Fd #1 (MWRA) serves, or a kit by mail
The 3 labs Massachusetts certifies closest to the area South Hadley Fd #1 (MWRA) serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Quabbin Analytical Laboratory
Belchertown, MA · about 7 miles
Certified for bacteria
Pace Analytical LLC-East Longmeadow
East Longmeadow, MA · about 13 miles
Certified for bacteria, nitrate, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS
Vallid Labs Inc.
Agawam, MA · about 14 miles
Certified for bacteria
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Massachusetts certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Massachusetts’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Nothing here is above an EPA limit or health benchmarkIn EPA’s and Massachusetts’s records for this utility. They don’t cover everything, which is why the next step matters.Every contaminant TapBuff tracks
- Get the utility’s own reportSouth Hadley Fd #1 (MWRA) must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Massachusetts Department of Environmental Protection, Drinking Water Program, results from Jan. 2, 2020 to Oct. 5, 2026, read Oct. 8, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: MassDEP Online Searchable Laboratory Certification Listing, potable water, read Oct. 16, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID MA1275000. Rebuilt from EPA data on Oct. 25, 2026.