Town of Gramercy Waterworks
EPA’s and Louisiana’s records have results for 38 contaminants in its water; 9 were found.
Serves 2,860 people · Surface water · Gramercy, LA
- Serves
- 2,860 people
- Connections
- 1,404
- Water source
- Surface water
- Based in
- Gramercy, LA
- County
- St. James Parish
- Owner
- Local government
The short answer
EPA recorded violations of the legal limit for haloacetic acids (HAA5) here in 2024 and 2025. In 2026, the latest year on file, it averaged 46.1 ppb, below the limit. EPA recorded a violation of the legal limit for total trihalomethanes (TTHM) here in 2025. In 2026, the latest year on file, it averaged 57.4 ppb, below the limit. 5 health-based violations since 2016, none with a fix on record in EPA’s file.
This is what the records show, not medical advice. Worried about a health effect? Talk to a doctor or your local health department.
What handles itThe 5 violationsGot a notice? What it means
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from Jan. 10 to Oct. 16, 2024.
Lead and copper: EPA SDWIS monitoring periods ending 2004 to 2025.
Haloacetic acids (HAA5), total trihalomethanes (TTHM), nitrate, arsenic, fluoride, uranium and chromium (total): Louisiana’s own results, samples taken from Feb. 13, 2020 to Aug. 20, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Action level:
- Triggers action. If more than 10% of homes sampled are above it, the utility must act.
- 90th percentile:
- How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
- Health goal (MCLG):
- Not enforceable. The level with no expected risk, with a margin of safety.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. One other PFAS with no federal limit was found, the highest PFBA at 6.8 ppt: see it below.
A legal-limit violation on record, below the limit in the latest year, 2 results
Haloacetic acids (HAA5)
Forms or is added in treatment
What it means for you. EPA’s concern is long-term exposure, years of drinking it, not an immediate risk to health. A violation like this calls for a notice to customers within 30 days.
67 ppb
Highest yearly average, 2020 to 2026
2026 average: 46.1 ppb
Averaged by year, the highest was 67 ppb, in 2024, above EPA’s legal limit of 60 ppb. Its highest single sample was 83.8 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded violations for haloacetic acids (HAA5) at this utility in 2024 and 2025.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 55 ppb, in 2019.
What handles it
No certification claim covers this compound yet.
Total trihalomethanes (TTHM)
Forms or is added in treatment
What it means for you. EPA’s concern is long-term exposure, years of drinking it, not an immediate risk to health. A violation like this calls for a notice to customers within 30 days. A filter certified for it, at the tap you drink from, reduces it.
76.3 ppb
Highest yearly average, 2020 to 2026
2026 average: 57.4 ppb
Averaged by year, the highest was 76.3 ppb, in 2024, below EPA’s legal limit of 80 ppb. Its highest single sample was 98 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded a violation for total trihalomethanes (TTHM) at this utility in 2025.
How it’s judged
EPA judges this limit at each sampling point, so a violation can be on record in a year whose average is below it.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 73.4 ppb, in 2014.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Below EPA’s limits, 6 results
Arsenic, lead and uranium have a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Action level:
- Triggers action. If more than 10% of homes sampled are above it, the utility must act.
- 90th percentile:
- How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
Lithium, Health reference level 10 ppb; highest 9.9 ppb
Highest sample, July 8, 2024; found in 2 of 4 · Comes from the source
The highest sample was 9.9 ppb, below EPA’s health reference level of 10 ppb. Lithium has no legal limit or health goal of its own.
What handles it
No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.
How to read your utility’s reportNitrate, Legal limit 10 ppm; highest 1.3 ppm
Highest sample; found in 7 of 7 · 2026, one sample: 1.2 ppm · Comes from the source
The highest sample, in 2023, was 1.3 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest sample of 2.1 ppm, in 2017.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
Arsenic, Legal limit 10 ppb · health goal zero; highest yearly average 0.84 ppb
Highest yearly average, 2020 to 2026 · Comes from the source
Averaged by year, the highest was 0.84 ppb, in 2026, below EPA’s legal limit of 10 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. That was also the latest year on file.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 1.0 ppb, in 2012.
What handles it
- NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
- NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
Lead, Action level 15 ppb · health goal zero; 90th percentile 0.49 ppb
90th percentile, 2023 to 2025 · Comes from pipes, often your own
In the latest period, 9 in 10 homes sampled were at or below 0.49 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53 look for “Lead Reduction”
- NSF/ANSI 58 look for “Lead Reduction”
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.1 ppm
Highest yearly average, 2020 to 2026 · 2026, one sample: 0.1 ppm · Forms or is added in treatment
Averaged by year, the highest was 0.1 ppm, in 2020, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 0.21 ppm, in 2017.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Uranium, Legal limit 30 ppb · health goal zero; highest yearly average 0.73 ppb
Highest yearly average, 2020 to 2026 · Comes from the source
Averaged by year, the highest was 0.73 ppb, in 2026, below EPA’s legal limit of 30 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. That was also the latest year on file.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 1.6 ppb, in 2017.
What handles it
- NSF/ANSI 58 look for “Uranium”
Also found, with no federal limit
EPA measured these PFAS to learn how often they occur. None has a legal limit or a health goal yet.
| Compound | Highest sample | Found in | Certification claim |
|---|---|---|---|
| PFBA | 6.8 ppt | 2 of 4 | None covers it |
29 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Chromium (total)
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
5 health-based violations since 2016, 4 for total Haloacetic Acids (HAA5) and 1 for TTHM. The latest began July 1, 2025, and none has a fix on record in EPA’s file.
- Resolved:
- EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
- No fix on record:
- It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).
EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Got a notice about one? What it means and what to do| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2025 to Sept. 30, 2025, 68 ppb | No fix on recordEPA: archived |
| TTHM | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2025 to June 30, 2025, 82 ppb | No fix on recordEPA: archived |
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2025 to June 30, 2025, 69 ppb | No fix on recordEPA: archived |
| Jan. 1, 2025 to March 31, 2025, 66 ppb | No fix on recordEPA: archived | ||
| Oct. 1, 2024 to Dec. 31, 2024, 67 ppb | No fix on recordEPA: archived |
Health-based violations only. 2 monitoring or reporting violations not shown.
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.
- NSF/ANSI 53
Claims: Trihalomethanes (TTHM) Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction
For: Total trihalomethanes (TTHM), Arsenic, Lead
Other claims that cover it: VOC Reduction; Arsenic (III) (50 ppb influent level)
- NSF/ANSI 58
Claims: Trihalomethanes (TTHM) Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction, Uranium
For: Total trihalomethanes (TTHM), Arsenic, Lead, Uranium
Other claims that cover it: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)
At the tap, or for the whole house?
These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
Brondell Coral UC300 Under Sink Water Filtration System
Under-sink carbon
Five years: $900, household of 3, cartridges included
Certified for: Total trihalomethanes (TTHM); also lead, found below its limits
A.O. Smith 2-Stage Under Sink Water Filter (AO-US-200)
Under-sink carbon
Five years: $980, household of 3, cartridges included
Certified for: Total trihalomethanes (TTHM); also lead, found below its limits
Aquasana Claryum 2-Stage (AQ-6200)
Under-sink carbon
Five years: $990, household of 3, cartridges included
Certified for: Total trihalomethanes (TTHM); also lead, found below its limits
2 more filters
Brita Elite Water Filter Faucet System (SAFF-100/FF-100)
Faucet mount
Five years: $1,004, household of 3, cartridges included
Certified for: Total trihalomethanes (TTHM); also lead, found below its limits
Aquasana Clean Water Machine (AQ-CWM2)
Countertop
Five years: $1,061, household of 3, cartridges included
Certified for: Total trihalomethanes (TTHM); also lead, found below its limits
Every filter certified for it
The best water filters for TTHM, ranked
Disinfectant
Town of Gramercy Waterworks reported adding chloramine before water enters its pipes, at its one sampling point, in its 2024 sampling for EPA.
What that means
Chloramine is chlorine combined with ammonia. It lasts longer in the pipes, and unlike chlorine, it doesn’t leave water that sits out. A filter’s chlorine claim doesn’t cover it: look for the separate chloramine claim under NSF/ANSI 42. No shower filter can carry one: NSF/ANSI 177, the shower filter standard, covers free chlorine only. Fish, turtles and frogs need it removed from their water. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM), nitrate, arsenic, fluoride, uranium and chromium (total) results here are Louisiana’s own from 2020 on, with EPA’s national file for 2012 to 2019. Town of Gramercy Waterworks’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Jan. 10 to Oct. 16, 2024; Louisiana’s results run from Feb. 13, 2020 to Aug. 20, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Town of Gramercy Waterworks’s latest lead sampling in EPA’s records, 2023 to 2025, had a 90th percentile of 0.49 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
- What Town of Gramercy Waterworks’s results flag: haloacetic acids (HAA5) and total trihalomethanes (TTHM). These are in the water the utility sends out, so a test of your tap mostly confirms them. Include them if you want a number for your own home.
The 3 labs Louisiana certifies closest to the area Town of Gramercy Waterworks serves, or a kit by mail
The 3 labs Louisiana certifies closest to the area Town of Gramercy Waterworks serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Curtis Environmental Services, Inc.
LaPlace, LA · about 19 miles
Certified for minerals and other inorganics, disinfection byproducts
LDH Central Laboratory
Baton Rouge, LA · about 41 miles
Certified for bacteria
Water Test, Inc.
Covington, LA · about 46 miles
Certified for bacteria
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Louisiana certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Louisiana’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Read up on these 2 resultsWhat each one does to health, where it comes from, and the certification claim that addresses it.Start with haloacetic acids (HAA5)
- Get the utility’s own reportTown of Gramercy Waterworks must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Louisiana Department of Health, Drinking Water Viewer, results from Jan. 2, 2020 to Oct. 14, 2026, read Oct. 25, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: LDH, laboratories certified by Louisiana for drinking water analysis, read Oct. 16, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID LA1093002. Rebuilt from EPA data on Oct. 25, 2026.