Madison Co Utilities District
EPA’s and Kentucky’s records have results for 33 contaminants in its water; 2 were found.
Serves 25,120 people · Surface water bought from another system · Richmond, KY
- Serves
- 25,120 people
- Connections
- 12,834
- Water source
- Surface water bought from another system
- Based in
- Richmond, KY
- County
- Madison
- Owner
- Local government
The short answer
None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. 1 health-based violation since 2016, resolved in EPA’s file.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from July 16, 2024 to April 8, 2025.
Total trihalomethanes (TTHM) and haloacetic acids (HAA5): Kentucky’s own results, samples taken from Feb. 11, 2020 to Aug. 10, 2026, with EPA’s 2012 to 2019 file for earlier years.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
Below EPA’s limits, 2 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 57.6 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 47.9 ppb · Forms or is added in treatment
Averaged by year, the highest was 57.6 ppb, in 2024, below EPA’s legal limit of 80 ppb. Its highest single sample was 141 ppb. In 2026, the latest year on file, its 12 samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 68.8 ppb, in 2013.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 28.6 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 26.8 ppb · Forms or is added in treatment
Averaged by year, the highest was 28.6 ppb, in 2024, below EPA’s legal limit of 60 ppb. Its highest single sample was 66 ppb. In 2026, the latest year on file, its 12 samples averaged below the limit. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 42.8 ppb, in 2013.
What handles it
No certification claim covers this compound yet.
31 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Lead
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- Lithium
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
1 health-based violation since 2016 for the Revised Total Coliform Rule. It began June 1, 2019.
- Resolved:
- EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
- No fix on record:
- It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).
EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Got a notice about one? What it means and what to do| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Revised Total Coliform Rule | E. coli was confirmed in the water system.EPA: Maximum Contaminant Level Violation, E. coli (RTCR) | June 1, 2019 to June 30, 2019 | Resolved |
Health-based violations only. 2 monitoring or reporting violations not shown.
Disinfectant
Madison Co Utilities District reported adding no disinfectant at its one sampling point, in its 2024 to 2025 sampling for EPA.
What that means
Most utilities add chlorine or chloramine, CDC says. This utility buys its water from another system, so what it reported may leave out treatment done before the water reaches it. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are Kentucky’s own from 2020 on, with EPA’s national file for 2012 to 2019. Madison Co Utilities District’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from July 16, 2024 to April 8, 2025; Kentucky’s results run from Feb. 11, 2020 to Aug. 10, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Madison Co Utilities District’s latest lead sampling in EPA’s records, 2022 to 2024, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
Labs Kentucky certifies, or a kit by mail
TapBuff hasn’t read Kentucky’s list of certified labs yet. The national page links every state’s own list.
Certified labs, state by stateOr test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Kentucky certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Kentucky’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded
- Get the utility’s own reportMadison Co Utilities District must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Kentucky Division of Water, results from Jan. 2, 2020 to Sept. 23, 2026, read Oct. 17, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID KY0760224. Rebuilt from EPA data on Oct. 25, 2026.