Breathitt Co Water District
EPA’s and Kentucky’s records have results for 33 contaminants in its water; 3 were found.
Serves 5,068 people · Surface water bought from another system · Jackson, KY
- Serves
- 5,068 people
- Connections
- 2,788
- Water source
- Surface water bought from another system
- Based in
- Jackson, KY
- County
- Breathitt
- Owner
- Local government
The short answer
None of the results here is above a limit in force today. Lithium is above EPA’s health benchmark. 4 health-based violations since 2016, all resolved in EPA’s file.
This is what the records show, not medical advice. Worried about a health effect? Talk to a doctor or your local health department.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from Feb. 5 to Nov. 5, 2024.
Haloacetic acids (HAA5) and total trihalomethanes (TTHM): Kentucky’s own results, samples taken from Feb. 11, 2020 to Aug. 12, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
Above EPA’s health benchmark, 1 result
Lithium
Comes from the source
20.3 ppb
Highest sample, Nov. 5, 2024; found in 2 of 8
The highest sample was 20.3 ppb, about twice EPA’s health reference level of 10 ppb. That is a screening level, not an enforceable limit.
What handles it
No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.
How to read your utility’s reportBelow EPA’s limits, 2 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 40.5 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 24.2 ppb · Forms or is added in treatment
Averaged by year, the highest was 40.5 ppb, in 2024, below EPA’s legal limit of 60 ppb. Its highest single sample was 62.9 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 44.3 ppb, in 2017, and EPA recorded violations in 2017 and 2018.
What handles it
No certification claim covers this compound yet.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 51.7 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 45.8 ppb · Forms or is added in treatment
Averaged by year, the highest was 51.7 ppb, in 2023, below EPA’s legal limit of 80 ppb. Its highest single sample was 86.4 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 57 ppb, in 2013.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
30 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Lead
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
4 health-based violations since 2016, 2 for the Revised Total Coliform Rule and 2 for total Haloacetic Acids (HAA5). The latest began Sept. 23, 2019.
- Resolved:
- EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
- No fix on record:
- It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).
EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Got a notice about one? What it means and what to do| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Revised Total Coliform Rule | Coliform results required a check of the system, and the check or its fixes were not done on time.EPA: Treatment Technique, Level 1 Assessment (RTCR) | Sept. 23, 2019 | Resolved |
| Aug. 25, 2019 | Resolved | ||
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2018 to March 31, 2018, 61 ppb | Resolved |
| Oct. 1, 2017 to Dec. 31, 2017, 62 ppb | Resolved |
Health-based violations only. 4 monitoring or reporting violations not shown.
Disinfectant
Breathitt Co Water District reported another disinfectant but neither chlorine nor chloramine, in its 2024 sampling for EPA.
What that means
Most utilities add chlorine or chloramine, CDC says. This utility buys its water from another system, so what it reported may leave out treatment done before the water reaches it. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Haloacetic acids (HAA5) and total trihalomethanes (TTHM) results here are Kentucky’s own from 2020 on, with EPA’s national file for 2012 to 2019. Breathitt Co Water District’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Feb. 5 to Nov. 5, 2024; Kentucky’s results run from Feb. 11, 2020 to Aug. 12, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Breathitt Co Water District’s latest lead sampling in EPA’s records, 2024 to 2026, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
- What Breathitt Co Water District’s results flag: lithium. It is in the water the utility sends out, so a test of your tap mostly confirms it. Include it if you want a number for your own home.
Labs Kentucky certifies, or a kit by mail
TapBuff hasn’t read Kentucky’s list of certified labs yet. The national page links every state’s own list.
Certified labs, state by stateOr test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Kentucky certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Kentucky’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Read up on lithiumWhat it does to health, where it comes from, and the certification claim that addresses it.About lithium
- Get the utility’s own reportBreathitt Co Water District must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Kentucky Division of Water, results from Jan. 2, 2020 to Sept. 23, 2026, read Oct. 17, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID KY0131012. Rebuilt from EPA data on Oct. 25, 2026.