Skip to content
TapBuff

Rowan Muni Water Supply

What EPA’s and Iowa’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
124 people
Connections
91
Water source
Groundwater
Based in
Rowan, IA
County
Wright
Owner
Local government
The ZIP code it serves

50470

The short answer

1 result is above the limit’s level with no violation recorded, and 1 more is above the health goal. The worst: Arsenic, above the limit’s level, no violation. No health-based violations on file since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2013 to 2025.

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 1.4 ppm, for the period ending June 30, 1994. None since is on file, so it is not counted as a current finding.

Arsenic, fluoride, total trihalomethanes (TTHM), nitrate, chromium (total) and haloacetic acids (HAA5): Iowa’s own results, samples taken from July 8, 2020 to July 20, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the limit’s level, no violation recorded1

Arsenic

Comes from the source

Above the limit’s level, no violation

12ppb

Highest yearly average, 2021 to 2026

2026: not found

Averaged by year, the highest was 12 ppb, in 2024, above EPA’s legal limit of 10 ppb. In 2026, the latest year on file, it wasn’t found in any of its three samples. EPA judges this limit on running averages at each sampling point, and recorded no violation for arsenic at this utility since 2020. Results like these with no violation often include water sampled before treatment or blending; the utility’s annual report says what reaches the tap. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 4.0 ppb, in 2012.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Above the health goal1

Lead

Comes from pipes, often your own

Above the health goal

1.4ppb

90th percentile, 2023 to 2025

In the latest period, 9 in 10 homes sampled were at or below 1.4 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits3

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.37ppm

Highest yearly average, 2022

Averaged by year, the highest was 0.37 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.39 ppm, in 2013.

What handles it

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

5.2ppb

Highest yearly average, 2020 to 2024

2024, one sample: 3.4 ppb

Averaged by year, the highest was 5.2 ppb, in 2023, below EPA’s legal limit of 80 ppb. In 2024, the latest year on file, its one sample was 3.4 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.2 ppb, in 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Nitrate

Comes from the source

Below EPA’s limits

0.15ppm

Highest sample; found in 3 of 7

2026: not found

The highest sample, in 2022, was 0.15 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.23 ppm, in 2018.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Chromium (total)
  • Haloacetic acids (HAA5)

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Arsenic, Lead

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Arsenic, Lead

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

The best water filters for lead, ranked

Violations since 2016

No health-based violations on file with EPA since 2016. There are 8 monitoring or reporting violations: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Arsenic, fluoride, total trihalomethanes (TTHM), nitrate, chromium (total) and haloacetic acids (HAA5) results here are Iowa’s own from 2020 on, with EPA’s national file for 2012 to 2019. Rowan Muni Water Supply’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Iowa’s results run from July 8, 2020 to July 20, 2026.

Testing your own tap

Rowan Muni Water Supply’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Iowa certifies.

The 3 labs Iowa certifies closest to the area Rowan Muni Water Supply serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • AgSource

    Ellsworth, IA · about 29 miles

    Certified for bacteria, nitrate, metals, minerals and other inorganics

    (515) 297-8103

  • Eurofins - Cedar Falls

    Cedar Falls, IA · about 57 miles

    Certified for bacteria, nitrate, minerals and other inorganics

    (319) 277-2401

  • Microbac Laboratories - Waterloo

    Waterloo, IA · about 66 miles

    Certified for bacteria, nitrate

    (319) 235-4440

State Hygienic Laboratory at the University of Iowa: Through the Grants-to-Counties program, private well owners in participating counties can have their water tested for total coliform bacteria and nitrate. Start with the county sanitarian at your county health department. No cost in a participating county. The Grants-to-Counties Program, State Hygienic Lab at the University of Iowa.

All 36 certified labs for Iowa

Sources

PWSID IA9958004. Rebuilt from EPA data on Oct. 18, 2026.