Rathbun Reg WTR Assn (Burlington)
EPA’s and Iowa’s records have results for 33 contaminants in its water; 5 were found.
Serves 8,375 people · Surface water bought from another system · Burlington, IA
- Serves
- 8,375 people
- Connections
- 3,350
- Water source
- Surface water bought from another system
- Based in
- Burlington, IA
- Counties
- Des Moines, Henry
- Owner
- Private
The short answer
None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. No health-based violations on file since 2016.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from March 3 to Dec. 2, 2025.
Total trihalomethanes (TTHM) and haloacetic acids (HAA5): Iowa’s own results, samples taken from Jan. 6, 2020 to July 13, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. Two other PFAS with no federal limit were found, the highest PFBA at 32 ppt: see them below.
Below EPA’s limits, 3 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
Lithium, Health reference level 10 ppb; highest 9.2 ppb
Highest sample, Sept. 9, 2025; found in 1 of 4 · Comes from the source
The highest sample was 9.2 ppb, below EPA’s health reference level of 10 ppb. Lithium has no legal limit or health goal of its own.
What handles it
No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.
How to read your utility’s reportTotal trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 72.1 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 49 ppb · Forms or is added in treatment
Averaged by year, the highest was 72.1 ppb, in 2022, below EPA’s legal limit of 80 ppb. Its highest single sample was 160 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 66.5 ppb, in 2013.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 26.4 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 14.8 ppb · Forms or is added in treatment
Averaged by year, the highest was 26.4 ppb, in 2022, below EPA’s legal limit of 60 ppb. Its highest single sample was 47 ppb. In 2026, the latest year on file, its six samples averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 28.4 ppb, in 2014.
What handles it
No certification claim covers this compound yet.
Also found, with no federal limit
EPA measured these PFAS to learn how often they occur. None has a legal limit or a health goal yet.
| Compound | Highest sample | Found in | Certification claim |
|---|---|---|---|
| PFBA | 32 ppt | 4 of 4 | None covers it |
| PFPeA | 13 ppt | 4 of 4 | None covers it |
28 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Lead
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
No health-based violations on file with EPA since 2016. There are 2 monitoring or reporting violations: a sample missed, late or not reported. EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Disinfectant
Rathbun Reg WTR Assn (Burlington) reported adding chloramine before water enters its pipes, at its one sampling point, in its 2025 sampling for EPA.
What that means
Chloramine is chlorine combined with ammonia. It lasts longer in the pipes, and unlike chlorine, it doesn’t leave water that sits out. A filter’s chlorine claim doesn’t cover it: look for the separate chloramine claim under NSF/ANSI 42. No shower filter can carry one: NSF/ANSI 177, the shower filter standard, covers free chlorine only. Fish, turtles and frogs need it removed from their water. This utility buys its water from another system, so what it reported may leave out treatment done before the water reaches it. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM) and haloacetic acids (HAA5) results here are Iowa’s own from 2020 on, with EPA’s national file for 2012 to 2019. Rathbun Reg WTR Assn (Burlington)’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from March 3 to Dec. 2, 2025; Iowa’s results run from Jan. 6, 2020 to July 13, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Rathbun Reg WTR Assn (Burlington)’s latest lead sampling in EPA’s records, 2022 to 2024, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Iowa certifies closest to the area Rathbun Reg WTR Assn (Burlington) serves, or a kit by mail
The 3 labs Iowa certifies closest to the area Rathbun Reg WTR Assn (Burlington) serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Ion Environmental Solutions
Muscatine, IA · about 38 miles
Certified for bacteria, nitrate
State Hygienic Laboratory - Coralville
Coralville, IA · about 56 miles
Certified for bacteria, nitrate, organic chemicals, disinfection byproducts, PFAS, radioactivity
Quad Cities Metallurgical Laboratory
Davenport, IA · about 58 miles
Certified for bacteria, nitrate
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Iowa certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Iowa’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded
- Get the utility’s own reportRathbun Reg WTR Assn (Burlington) must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Iowa Department of Natural Resources, Water Supply Programs, results from Jan. 1, 2020 to Oct. 6, 2026, read Oct. 8, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: Iowa DNR, laboratories certified for drinking water, read Oct. 10, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID IA0400902. Rebuilt from EPA data on Oct. 25, 2026.