Skip to content
TapBuff

Pleasantville Water Works

What EPA’s and Iowa’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
1,676 people
Connections
651
Water source
Groundwater
Based in
Pleasantville, IA
County
Marion
Owner
Local government
The ZIP code it serves

50225

The short answer

Nothing in EPA’s and Iowa’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 1 health-based violation since 2016.

What was found

Fluoride, haloacetic acids (HAA5), nitrate, total trihalomethanes (TTHM), arsenic, chromium (total) and uranium: Iowa’s own results, samples taken from April 27, 2020 to July 13, 2026, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits4

Fluoride

Forms or is added in treatment

Below EPA’s limits

1.8ppm

Highest yearly average, 2021

Averaged by year, the highest was 1.8 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.7 ppm, in 2012.

What handles it

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

8.1ppb

Highest yearly average, 2020 to 2026

Averaged by year, the highest was 8.1 ppb, in 2026, below EPA’s legal limit of 60 ppb. That was also the latest year on file.

What handles it

No certification claim covers this compound yet.

Nitrate

Comes from the source

Below EPA’s limits

1.3ppm

Highest sample; found in 7 of 7

2026, one sample: 1.2 ppm

The highest sample, in 2022, was 1.3 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was 1.2 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 1.2 ppm, in 2015.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

6.2ppb

Highest yearly average, 2020 to 2026

2026, one sample: 3.4 ppb

Averaged by year, the highest was 6.2 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, its one sample was 3.4 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 14.1 ppb, in 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
4 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Chromium (total)
  • Lead
  • Uranium

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Gross alpha radiation (excluding radon and uranium)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2018 to March 31, 201819.9 PCI/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record.

What this report can’t tell you

  • Everything else. Fluoride, haloacetic acids (HAA5), nitrate, total trihalomethanes (TTHM), arsenic, chromium (total) and uranium results here are Iowa’s own from 2020 on, with EPA’s national file for 2012 to 2019. Pleasantville Water Works’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Iowa’s results run from April 27, 2020 to July 13, 2026.

Testing your own tap

Pleasantville Water Works’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Iowa certifies.

The 3 labs Iowa certifies closest to the area Pleasantville Water Works serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Microbac Laboratories - Newton

    Newton, IA · about 26 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts

    (641) 792-8451

  • State Hygienic Laboratory - Ankeny

    Ankeny, IA · about 30 miles

    Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics

    (515) 725-1600

  • Microbac Laboratories - Centerville

    Centerville, IA · about 50 miles

    Certified for bacteria

    (641) 437-7023

State Hygienic Laboratory at the University of Iowa: Through the Grants-to-Counties program, private well owners in participating counties can have their water tested for total coliform bacteria and nitrate. Start with the county sanitarian at your county health department. No cost in a participating county. The Grants-to-Counties Program, State Hygienic Lab at the University of Iowa.

All 36 certified labs for Iowa

Sources

PWSID IA6377046. Rebuilt from EPA data on Oct. 18, 2026.