Lone Tree Muni Water System
What EPA’s and Iowa’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 1,357 people
- Connections
- 510
- Water source
- Groundwater
- Based in
- Lone Tree, IA
- County
- Johnson
- Owner
- Local government
The ZIP code it serves
The short answer
1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Copper, above the action level. No health-based violations on file since 2016.
What handles itWhat was found
Lead and copper: EPA SDWIS monitoring periods ending 1999 to 2021.
Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic and chromium (total): Iowa’s own results, samples taken from Jan. 9, 2020 to Aug. 12, 2026, with EPA’s 2012 to 2019 file for earlier years.
Above the legal limit1
Copper
Comes from pipes, often your own
1.9ppm
90th percentile, 2019 to 2021
In the latest period, 9 in 10 homes sampled were at or below 1.9 ppm, above EPA’s action level of 1.3 ppm.
What handles it
- NSF/ANSI 53 look for “Copper Reduction”
- NSF/ANSI 58 look for “Copper Reduction”
Above the health goal1
Lead
Comes from pipes, often your own
2.0ppb
90th percentile, 2024
In the latest period, 9 in 10 homes sampled were at or below 2.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53 look for “Lead Reduction”
- NSF/ANSI 58 look for “Lead Reduction”
Below EPA’s limits4
Total trihalomethanes (TTHM)
Forms or is added in treatment
51ppb
Highest yearly average, 2020 to 2026
2026, one sample: 3.9 ppb
Averaged by year, the highest was 51 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, its one sample was 3.9 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 62 ppb, in 2014.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Haloacetic acids (HAA5)
Forms or is added in treatment
37ppb
Highest yearly average, 2020 to 2026
2026: not found
Averaged by year, the highest was 37 ppb, in 2021, below EPA’s legal limit of 60 ppb. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 42 ppb, in 2017.
What handles it
No certification claim covers this compound yet.
Fluoride
Forms or is added in treatment
0.48ppm
Highest yearly average, 2021
Averaged by year, the highest was 0.48 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.6 ppm, in 2012.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Nitrate
Comes from the source
0.23ppm
Highest sample; found in 2 of 8
2026: not found
The highest sample, in 2024, was 0.23 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, it wasn’t found in its one sample.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
- Arsenic
- Chromium (total)
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”
- NSF/ANSI 53
Claims: Copper Reduction, Lead Reduction
For: Copper, Lead
- NSF/ANSI 58
Claims: Copper Reduction, Lead Reduction
For: Copper, Lead
At the tap, or for the whole house?
Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
PUR PLUS 11-Cup Pitcher (PPT111W)
Pitcher
- NSF listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Copper, Lead
Culligan 10-Cup Pitcher with ZeroWater Technology (ZEROP10)
Pitcher
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
LifeStraw Home 7-Cup Glass Water Filter Pitcher
Pitcher
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
Aquasana SmartFlow Reverse Osmosis (AQ-SFRO2)
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
Brondell Capella RC250 Reverse Osmosis System
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Lead
Violations since 2016
No health-based violations on file with EPA since 2016. There are 4 monitoring or reporting violations: a sample missed, late or not reported.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, arsenic and chromium (total) results here are Iowa’s own from 2020 on, with EPA’s national file for 2012 to 2019. Lone Tree Muni Water System’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Iowa’s results run from Jan. 9, 2020 to Aug. 12, 2026.
Testing your own tap
The 3 labs Iowa certifies closest to the area Lone Tree Muni Water System serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
State Hygienic Laboratory - Coralville
Coralville, IA · about 17 miles
Certified for bacteria, nitrate, organic chemicals, disinfection byproducts, PFAS, radioactivity
Ion Environmental Solutions
Muscatine, IA · about 19 miles
Certified for bacteria, nitrate
Linn County Public Health Department
Cedar Rapids, IA · about 36 miles
Certified for bacteria, nitrate
State Hygienic Laboratory at the University of Iowa: Through the Grants-to-Counties program, private well owners in participating counties can have their water tested for total coliform bacteria and nitrate. Start with the county sanitarian at your county health department. No cost in a participating county. The Grants-to-Counties Program, State Hygienic Lab at the University of Iowa.
All 36 certified labs for IowaSources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Iowa Department of Natural Resources, Water Supply Programs, results from Jan. 1, 2020 to Oct. 6, 2026, read Oct. 8, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Certified labs: Iowa DNR, laboratories certified for drinking water, read Oct. 10, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID IA5240095. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Read up on the 2 results above a lineWhat each one does to health, where it comes from, and the certification claim that addresses it.Start with Copper
- Get the utility’s own reportLone Tree Muni Water System must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Compare certified filtersWhat the filters certified for these results cost over five years, cartridges included.Compare five-year costs