Skip to content
TapBuff

Aurora Acres

What EPA’s and Florida’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
170 people
Connections
136
Water source
Groundwater
Based in
Inglis, FL
County
Citrus
Owner
Private
The ZIP code it serves

34449

The short answer

Nothing in EPA’s and Florida’s records for this utility is above a health goal. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. No health-based violations on file since 2016.

What was found

Haloacetic acids (HAA5), nitrate, total trihalomethanes (TTHM), fluoride, chromium (total) and arsenic: Florida’s own results, samples taken from Dec. 8, 2020 to Dec. 7, 2022, with EPA’s 2012 to 2019 file for earlier years.

Below EPA’s limits5

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

29.5ppb

Highest yearly average, 2021

Averaged by year, the highest was 29.5 ppb, in 2021, below EPA’s legal limit of 60 ppb. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 58.5 ppb, in 2018.

What handles it

No certification claim covers this compound yet.

Nitrate

Comes from the source

Below EPA’s limits

1.3ppm

Highest sample; found in 1 of 3

2022, one sample: 1.3 ppm

The highest sample, in 2022, was 1.3 ppm, below EPA’s legal limit of 10 ppm. That was also the latest year on file, and its one sample was 1.3 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.46 ppm, in 2019.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

8.4ppb

Highest yearly average, 2021

Averaged by year, the highest was 8.4 ppb, in 2021, below EPA’s legal limit of 80 ppb. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 13.8 ppb, in 2018.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.27ppm

Highest yearly average, 2021

Averaged by year, the highest was 0.27 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.19 ppm, in 2015.

What handles it

Chromium (total)

Comes from the source

Below EPA’s limits

1.7ppb

Highest yearly average, 2021

Averaged by year, the highest was 1.7 ppb, in 2021, below EPA’s legal limit of 100 ppb. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 10 ppb, in 2015.

What handles it

2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Lead

Violations since 2016

No health-based violations on file with EPA since 2016. There are 23 monitoring or reporting violations: a sample missed, late or not reported.

What this report can’t tell you

  • Everything else. Haloacetic acids (HAA5), nitrate, total trihalomethanes (TTHM), fluoride, chromium (total) and arsenic results here are Florida’s own from 2020 on, with EPA’s national file for 2012 to 2019. Aurora Acres’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Florida’s results run from Dec. 8, 2020 to Dec. 7, 2022.

Testing your own tap

Aurora Acres’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Florida certifies.

The 3 labs Florida certifies closest to the area Aurora Acres serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Marion County Water Test Lab., LLC

    Ocala, FL · about 35 miles

    Certified for bacteria

    (352) 694-6042

  • Aqua Pure Water & Sewage Service, LLC

    Ocala, FL · about 37 miles

    Certified for bacteria

    (352) 355-2383

  • Advanced Environmental Laboratories, Inc. - Gainesville

    Gainesville, FL · about 40 miles

    Certified for bacteria, nitrate, minerals and other inorganics

    (352) 377-2349

Florida Department of Health Bureau of Public Health Laboratories: Coliform and E. coli testing for private wells at the Jacksonville and Miami labs. Collection kits come from your county health department, and the sample has to reach the lab on ice the same day it is collected. $40 for private testing through the state lab. Well Water Testing, Florida Department of Health.

All 212 certified labs for Florida

Sources

PWSID FL6092331. Rebuilt from EPA data on Oct. 18, 2026.