Jewett City Water Company
EPA’s and CDC’s records have results for 38 contaminants in its water; 5 were found.
Serves 6,840 people · Surface water · Griswold, CT
- Serves
- 6,840 people
- Connections
- 1,684
- Water source
- Surface water
- Based in
- Griswold, CT
- County
- New London
- Owner
- Private
The ZIP code it serves
The short answer
None of the results here is above a limit in force today. That covers PFAS and lithium; nitrate, arsenic and other regulated chemicals; and lead and copper, not everything. 1 health-based violation since 2016, resolved in EPA’s file.
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from Feb. 13 to Nov. 7, 2023.
Haloacetic acids (HAA5), total trihalomethanes (TTHM), nitrate, arsenic and uranium: Connecticut’s yearly averages per water system, as CDC’s Environmental Public Health Tracking Network publishes them, 2020 to 2023, with EPA’s 2012 to 2019 file for earlier years.
Chromium (total) and fluoride: EPA’s compliance monitoring file, samples taken from May 4, 2012 to Oct. 15, 2019. Newer results are in the utility’s annual water quality report.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Health goal (MCLG):
- Not enforceable. The level with no expected risk, with a margin of safety.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. One other PFAS with no federal limit was found, the highest PFBA at 12.1 ppt: see it below.
Below EPA’s limits, 4 results
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 48 ppb
Highest yearly average, 2020 to 2023 · 2023 average: 39.3 ppb · Forms or is added in treatment
Averaged by year, the highest was 48 ppb, in 2021, below EPA’s legal limit of 60 ppb. In 2023, the latest year on file, it averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 43.1 ppb, in 2014, and EPA recorded a violation in 2018.
What handles it
No certification claim covers this compound yet.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 59.9 ppb
Highest yearly average, 2020 to 2023 · 2023 average: 45 ppb · Forms or is added in treatment
Averaged by year, the highest was 59.9 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2023, the latest year on file, it averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 40.6 ppb, in 2014.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Nitrate, Legal limit 10 ppm; highest yearly average 0.91 ppm
Highest yearly average, 2020 to 2023 · 2023 average: 0.15 ppm · Comes from the source
Averaged by year, the highest was 0.91 ppm, in 2020, below EPA’s legal limit of 10 ppm. In 2023, the latest year on file, it averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest sample of 2.1 ppm, in 2012.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
Chromium (total), Legal limit 100 ppb; highest yearly average 0.33 ppb
Highest yearly average, 2012 to 2019 · 2019: not found · Comes from the source
Averaged by year, the highest was 0.33 ppb, in 2017, below EPA’s legal limit of 100 ppb. Its highest single sample was 1.0 ppb. In 2019, the latest year on file, it wasn’t found in any of its two samples.
What handles it
- NSF/ANSI 58 look for “Chromium (Hexavalent) Reduction”
- NSF/ANSI 53 look for “Chromium Reduction”
Also found, with no federal limit
EPA measured these PFAS to learn how often they occur. None has a legal limit or a health goal yet.
| Compound | Highest sample | Found in | Certification claim |
|---|---|---|---|
| PFBA | 12.1 ppt | 1 of 6 | None covers it |
33 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Arsenic
- Fluoride
- Lead
- Uranium
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- Lithium
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
1 health-based violation since 2016 for total Haloacetic Acids (HAA5). It began Jan. 1, 2018.
- Resolved:
- EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
- No fix on record:
- It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).
EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Got a notice about one? What it means and what to do| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Total Haloacetic Acids (HAA5) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2018 to March 31, 2018, 61 ppb | Resolved |
Health-based violations only. 26 monitoring or reporting violations not shown.
Disinfectant
Jewett City Water Company reported disinfecting with chlorine, not chloramine, at all 2 of its sampling points, in its 2023 sampling for EPA.
What that means
Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Haloacetic acids (HAA5), total trihalomethanes (TTHM), nitrate, arsenic and uranium results here are Connecticut’s yearly averages as CDC publishes them, from 2020 on, with EPA’s national file for 2012 to 2019. Chromium (total) and fluoride come from EPA’s file alone, which ends in 2019. Jewett City Water Company’s own annual report, which it must send you every year, has newer results for those and the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Feb. 13 to Nov. 7, 2023; CDC’s yearly averages for Connecticut cover 2020 to 2023; EPA’s compliance samples are from May 4, 2012 to Oct. 15, 2019.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Jewett City Water Company’s latest lead sampling in EPA’s records, 2024 to 2026, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs Connecticut certifies closest to the area Jewett City Water Company serves, or a kit by mail
The 3 labs Connecticut certifies closest to the area Jewett City Water Company serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
Microbac Laboratories, INC. - Dayville
Dayville, CT · about 19 miles
Certified for bacteria, nitrate, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, radioactivity
New England Testing Laboratory, Inc.
West Warwick, RI · about 23 miles
Certified for bacteria, nitrate, metals, minerals and other inorganics, organic chemicals, disinfection byproducts
Eurofins Rhode Island
North Kingstown, RI · about 25 miles
Certified for nitrate, metals, minerals and other inorganics
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that Connecticut certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against Connecticut’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Decide if you want a filter at allA filter for taste or chlorine is a preference, not a need. The standards say what each kind can do.NSF/ANSI standards, decoded
- Get the utility’s own reportJewett City Water Company must send you a water quality report every year. It covers contaminants this page does not show, and has newer results than EPA’s national file for the ones here that come from it.How to read it
- Test your own tap for leadIts latest lead sampling found none at the 90th percentile, but your own service line, solder and fixtures decide the lead at your faucet.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- CDC Environmental Public Health Tracking Network, yearly averages Connecticut supplied to CDC, 2020 to 2023, read Oct. 8, 2026. TapBuff’s comparisons with EPA’s limits are its own, not CDC’s or Connecticut’s.
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: Connecticut DPH, approved commercial laboratories certified to test drinking water, read Oct. 10, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID CT0580011. Rebuilt from EPA data on Oct. 25, 2026.