Skip to content
TapBuff

Town of Ovid

What EPA’s and Colorado’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
259 people
Connections
215
Water source
Groundwater
Based in
Ovid, CO
County
Sedgwick
Owner
Local government
The ZIP code it serves

80744

The short answer

1 result is above EPA’s legal limit, and 2 more are above the health goal. The worst: Arsenic, above the legal limit. 1 health-based violation since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2017 to 2024.

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 1.4 ppm, for the period ending Dec. 31, 2007. None since is on file, so it is not counted as a current finding.

Arsenic, uranium, nitrate, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride and chromium (total): Colorado’s own results, samples taken from Jan. 13, 2020 to Aug. 26, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit1

Arsenic

Comes from the source

Above the legal limit

10.7ppb

Highest yearly average, 2020 to 2026

2026 average: 9.4 ppb

Averaged by year, the highest was 10.7 ppb, in 2025, above EPA’s legal limit of 10 ppb. Its highest single sample was 11 ppb. In 2026, the latest year on file, its three samples averaged 9.4 ppb. EPA recorded a violation for arsenic at this utility in 2025. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 9.4 ppb, in 2012.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Above the health goal2

Uranium

Comes from the source

Above the health goal

19ppb

Highest yearly average, 2021 to 2024

2024, one sample: 18 ppb

Averaged by year, the highest was 19 ppb, in 2021: below EPA’s legal limit of 30 ppb, but above its health goal of zero. In 2024, the latest year on file, its one sample was 18 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 18 ppb, in 2018.

What handles it

Lead

Comes from pipes, often your own

Above the health goal

3.7ppb

90th percentile, 2024

In the latest period, 9 in 10 homes sampled were at or below 3.7 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Below EPA’s limits5

Nitrate

Comes from the source

Below EPA’s limits

5.9ppm

Highest sample; found in 7 of 7

2026, one sample: 5.5 ppm

The highest sample, in 2024, was 5.9 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its one sample was 5.5 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 7.0 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

31.7ppb

Highest yearly average, 2021 to 2026

2026, one sample: 22.2 ppb

Averaged by year, the highest was 31.7 ppb, in 2021, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, its one sample was 22.2 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 15.7 ppb, in 2015.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

12ppb

Highest yearly average, 2021 to 2026

2026, one sample: 7.2 ppb

Averaged by year, the highest was 12 ppb, in 2024, below EPA’s legal limit of 60 ppb. In 2026, the latest year on file, its one sample was 7.2 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 9.3 ppb, in 2012.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.47ppm

Highest yearly average, 2021 to 2024

2024: not found

Averaged by year, the highest was 0.47 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. In 2024, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.58 ppm, in 2018.

What handles it

Chromium (total)

Comes from the source

Below EPA’s limits

6.0ppb

Highest yearly average, 2021 to 2025

Averaged by year, the highest was 6.0 ppb, in 2025, below EPA’s legal limit of 100 ppb. That was also the latest year on file.

What handles it

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction

    For: Arsenic, Lead

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Uranium, Lead Reduction

    For: Arsenic, Uranium, Lead

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
ArsenicThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.011 MG/LArchived
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 5 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Arsenic, uranium, nitrate, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride and chromium (total) results here are Colorado’s own from 2020 on, with EPA’s national file for 2012 to 2019. Town of Ovid’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Colorado’s results run from Jan. 13, 2020 to Aug. 26, 2026.

Testing your own tap

Town of Ovid’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Colorado certifies.

The lab Colorado certifies closest to the area Town of Ovid serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Northeast Colorado Health Dept.

    Sterling, CO · about 47 miles

    Certified for bacteria

All 54 certified labs for Colorado

Sources