Skip to content
TapBuff

Town of Flagler

What EPA’s and Colorado’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
2,160 people
Connections
345
Water source
Groundwater
Based in
Flagler, CO
County
Kit Carson
Owner
Local government
The ZIP code it serves

80815

The short answer

2 results are above the health goal. The worst: Uranium, above the health goal. 2 health-based violations since 2016.

What handles it

What was found

Uranium, arsenic, nitrate, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride and chromium (total): Colorado’s own results, samples taken from Feb. 3, 2020 to Oct. 5, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the health goal2

Uranium

Comes from the source

Above the health goal

16.4ppb

Highest yearly average, 2025

Averaged by year, the highest was 16.4 ppb, in 2025: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 11.5 ppb, in 2017.

What handles it

Arsenic

Comes from the source

Above the health goal

5.0ppb

Highest yearly average, 2022 to 2025

2025, one sample: 5.0 ppb

Averaged by year, the highest was 5.0 ppb, in 2022: below EPA’s legal limit of 10 ppb, but above its health goal of zero. In 2025, the latest year on file, its one sample was 5.0 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 5.0 ppb, in 2016.

What handles it

  • NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
  • NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”

Below EPA’s limits5

Nitrate

Comes from the source

Below EPA’s limits

10.3ppm

Highest sample; found in 21 of 21

2026 average: 8.4 ppm

The highest sample, in 2025, was 10.3 ppm, which EPA rounds to 10 ppm to compare: at its legal limit of 10 ppm, not above it. In 2026, the latest year on file, its four samples averaged 8.4 ppm. EPA recorded no violation for nitrate at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 13.1 ppm, in 2017, and EPA recorded violations in 2016 and 2017.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

30.6ppb

Highest yearly average, 2020 to 2026

2026, one sample: 14.7 ppb

Averaged by year, the highest was 30.6 ppb, in 2024, below EPA’s legal limit of 80 ppb. In 2026, the latest year on file, its one sample was 14.7 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 41.8 ppb, in 2014.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

11.1ppb

Highest yearly average, 2020 to 2026

Averaged by year, the highest was 11.1 ppb, in 2026, below EPA’s legal limit of 60 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 10.3 ppb, in 2014.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.64ppm

Highest yearly average, 2021 to 2025

Averaged by year, the highest was 0.64 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.58 ppm, in 2017.

What handles it

Chromium (total)

Comes from the source

Below EPA’s limits

4.0ppb

Highest yearly average, 2022 to 2025

Averaged by year, the highest was 4.0 ppb, in 2025, below EPA’s legal limit of 100 ppb. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.0 ppb, in 2015.

What handles it

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claim: Arsenic (Pentavalent)<=50 ppb Reduction

    For: Arsenic

    Other certifiers’ wording: Arsenic (III) (50 ppb influent level)

  • NSF/ANSI 58

    Claims: Uranium, Arsenic (Pentavalent)<=50 ppb Reduction

    For: Uranium, Arsenic

    Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best reverse osmosis systems, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
NitrateThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2017 to March 31, 201713.1 MG/LResolved
NitrateThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2016 to June 30, 201611 MG/LResolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 6 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Uranium, arsenic, nitrate, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride and chromium (total) results here are Colorado’s own from 2020 on, with EPA’s national file for 2012 to 2019. Town of Flagler’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Colorado’s results run from Feb. 3, 2020 to Oct. 5, 2026.

Testing your own tap

Town of Flagler’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Colorado certifies.

The lab Colorado certifies closest to the area Town of Flagler serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Fort Morgan, City of

    Ft. Morgan, CO · about 68 miles

    Certified for bacteria

All 54 certified labs for Colorado

Sources

PWSID CO0132010. Rebuilt from EPA data on Oct. 18, 2026.