What EPA’s and Colorado’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
75 people
Connections
41
Water source
Surface water
Based in
Loveland, CO
County
Larimer
Owner
Private
The ZIP code it serves

80538

The short answer

1 result is above the health goal. The worst: Uranium, above the health goal. 3 health-based violations since 2016.

What handles it

What was found

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 2.3 ppm, for the period ending Dec. 31, 1993. None since is on file, so it is not counted as a current finding.

Uranium, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, chromium (total), nitrate and arsenic: Colorado’s own results, samples taken from Feb. 5, 2020 to Aug. 25, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the health goal1

Uranium

Comes from the source

Above the health goal

3.6ppb

Highest yearly average, 2020 to 2026

Averaged by year, the highest was 3.6 ppb, in 2026: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 5.9 ppb, in 2016.

What handles it

Below EPA’s limits5

Total trihalomethanes (TTHM)

Forms or is added in treatment

Below EPA’s limits

72.8ppb

Highest yearly average, 2020 to 2026

2026 average: 50.2 ppb

Averaged by year, the highest was 72.8 ppb, in 2021, below EPA’s legal limit of 80 ppb. Its highest single sample was 86.1 ppb. In 2026, the latest year on file, its three samples averaged 50.2 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 60.6 ppb, in 2016.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Below EPA’s limits

34.5ppb

Highest yearly average, 2020 to 2026

2026 average: 30.3 ppb

Averaged by year, the highest was 34.5 ppb, in 2025, below EPA’s legal limit of 60 ppb. Its highest single sample was 69.9 ppb. In 2026, the latest year on file, its three samples averaged 30.3 ppb. EPA recorded no violation for haloacetic acids (HAA5) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 48.2 ppb, in 2016.

What handles it

No certification claim covers this compound yet.

Fluoride

Forms or is added in treatment

Below EPA’s limits

1.9ppm

Highest yearly average, 2020 to 2023

Averaged by year, the highest was 1.9 ppm, in 2023, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.7 ppm, in 2016.

What handles it

Chromium (total)

Comes from the source

Below EPA’s limits

3.0ppb

Highest yearly average, 2020 to 2024

2024, one sample: 2.0 ppb

Averaged by year, the highest was 3.0 ppb, in 2022, below EPA’s legal limit of 100 ppb. In 2024, the latest year on file, its one sample was 2.0 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.0 ppb, in 2017.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.2ppm

Highest sample; found in 3 of 7

2026: not found

The highest sample, in 2025, was 0.2 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.3 ppm, in 2014.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Lead

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

At the tap, or for the whole house?

These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.

Filters with those claims on a certifier’s listing

None of the filters TapBuff has checked so far carry these claims. Search the certifier listings for the claim above.

Compare five-year costs

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalApril 1, 2026 to June 30, 20260.63 RATIOArchived
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)March 1, 2016 to March 31, 2016—Resolved
Interim Enhanced Surface Water Treatment RuleOne cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR)March 1, 2016 to March 31, 2016—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 27 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Uranium, total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, chromium (total), nitrate and arsenic results here are Colorado’s own from 2020 on, with EPA’s national file for 2012 to 2019. Sunrise Ranch’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Colorado’s results run from Feb. 5, 2020 to Aug. 25, 2026.

Testing your own tap

Sunrise Ranch’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Colorado certifies.

The 3 labs Colorado certifies closest to the area Sunrise Ranch serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • EAnalytics Laboratory

    Loveland, CO · under a mile

    Certified for bacteria

  • M.M.S Environmental Laboratories

    Fort Collins, CO · about 6 miles

    Certified for bacteria

  • Technology Laboratory, Inc.

    Fort Collins, CO · about 6 miles

    Certified for nitrate, minerals and other inorganics, organic chemicals

All 54 certified labs for Colorado

Sources

PWSID CO0135725. Rebuilt from EPA data on Oct. 18, 2026.