Skip to content
TapBuff

Pinewood Springs WD

What EPA’s and Colorado’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.

Serves
745 people
Connections
298
Water source
Surface water
Based in
Greenwood Village, CO
County
Larimer
Owner
Local government
The ZIP code it serves

80540

The short answer

2 results are above EPA’s legal limit, and 2 more are above the health goal. The worst: Total trihalomethanes (TTHM), above the legal limit. 27 health-based violations since 2016.

What handles it

What was found

Lead and copper: EPA SDWIS monitoring periods ending 2011 to 2025.

Copper: EPA’s file records a utility’s copper only when it exceeds the action level. The last here was 3.3 ppm, for the period ending Dec. 31, 2003. None since is on file, so it is not counted as a current finding.

Total trihalomethanes (TTHM), haloacetic acids (HAA5), uranium, fluoride, nitrate, chromium (total) and arsenic: Colorado’s own results, samples taken from Feb. 18, 2020 to Aug. 11, 2026, with EPA’s 2012 to 2019 file for earlier years.

Above the legal limit2

Total trihalomethanes (TTHM)

Forms or is added in treatment

Above the legal limit

164ppb

Highest yearly average, 2020 to 2026

2026 average: 90.1 ppb

Averaged by year, the highest was 164 ppb, in 2025, about twice EPA’s legal limit of 80 ppb. Its highest single sample was 352 ppb. In 2026, the latest year on file, its three samples averaged 90.1 ppb, above the limit. EPA recorded violations for total trihalomethanes (TTHM) at this utility in 2023, 2024, 2025 and 2026. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 55.6 ppb, in 2013.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”

Haloacetic acids (HAA5)

Forms or is added in treatment

Above the legal limit

81.4ppb

Highest yearly average, 2020 to 2026

2026 average: 33.2 ppb

Averaged by year, the highest was 81.4 ppb, in 2024, above EPA’s legal limit of 60 ppb. Its highest single sample was 193 ppb. In 2026, the latest year on file, its three samples averaged 33.2 ppb. EPA recorded violations for haloacetic acids (HAA5) at this utility in 2023, 2024 and 2025. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 60.3 ppb, in 2013.

What handles it

No certification claim covers this compound yet.

Above the health goal2

Lead

Comes from pipes, often your own

Above the health goal

1.0ppb

90th percentile, 2025

In the latest period, 9 in 10 homes sampled were at or below 1.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.

What handles it

Uranium

Comes from the source

Above the health goal

0.97ppb

Highest yearly average, 2020

Averaged by year, the highest was 0.97 ppb, in 2020: below EPA’s legal limit of 30 ppb, but above its health goal of zero. That is the only year on file. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.3 ppb, in 2016.

What handles it

Below EPA’s limits3

Fluoride

Forms or is added in treatment

Below EPA’s limits

0.32ppm

Highest yearly average, 2020 to 2026

2026, one sample: 0.26 ppm

Averaged by year, the highest was 0.32 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. In 2026, the latest year on file, its one sample was 0.26 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.45 ppm, in 2014.

What handles it

Nitrate

Comes from the source

Below EPA’s limits

0.22ppm

Highest sample; found in 3 of 7

2026: not found

The highest sample, in 2020, was 0.22 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, it wasn’t found in its one sample. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 0.78 ppm, in 2016.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”

Chromium (total)

Comes from the source

Below EPA’s limits

2.0ppb

Highest yearly average, 2020 to 2026

2026: not found

Averaged by year, the highest was 2.0 ppb, in 2022, below EPA’s legal limit of 100 ppb. In 2026, the latest year on file, it wasn’t found in its one sample.

What handles it

One compound tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic

What handles it

A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”

  • NSF/ANSI 53

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction

    For: Total trihalomethanes (TTHM), Lead

    Other certifiers’ wording: VOC Reduction

  • NSF/ANSI 58

    Claims: Trihalomethanes (TTHM) Reduction, Lead Reduction, Uranium

    For: Total trihalomethanes (TTHM), Lead, Uranium

At the tap, or for the whole house?

Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.

Filters with those claims on a certifier’s listing

Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money

Compare five-year costs

The best water filters for lead, ranked

Violations since 2016

Contaminant or ruleTypePeriodMeasuredStatus
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2026 to June 30, 20260.12 MG/LArchived
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyJan. 21, 2026—Unaddressed
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyJan. 21, 2026—Unaddressed
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyJan. 21, 2026—Unaddressed
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2026 to March 31, 20260.15 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.066 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2025 to Dec. 31, 20250.16 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.22 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2025 to Sept. 30, 20250.071 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2025 to June 30, 20250.067 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2025 to June 30, 20250.19 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 20250.18 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2025 to March 31, 20250.093 MG/LArchived
Surface Water Treatment RuleRequired treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR)Dec. 1, 2024 to Dec. 31, 2024—Resolved
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.081 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2024 to Dec. 31, 20240.15 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 20240.13 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJuly 1, 2024 to Sept. 30, 20240.092 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 20240.11 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageApril 1, 2024 to June 30, 20240.097 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2024 to March 31, 20240.11 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageJan. 1, 2024 to March 31, 20240.075 MG/LArchived
TTHMThe running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2023 to Dec. 31, 20230.1 MG/LArchived
Total Haloacetic Acids (HAA5)The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, AverageOct. 1, 2023 to Dec. 31, 20230.07 MG/LArchived
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 16, 2022—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 16, 2022—Resolved
Groundwater RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyOct. 16, 2022—Resolved
Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 19 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), uranium, fluoride, nitrate, chromium (total) and arsenic results here are Colorado’s own from 2020 on, with EPA’s national file for 2012 to 2019. Pinewood Springs WD’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Colorado’s results run from Feb. 18, 2020 to Aug. 11, 2026.

Testing your own tap

Pinewood Springs WD’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab Colorado certifies.

The 3 labs Colorado certifies closest to the area Pinewood Springs WD serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • EAnalytics Laboratory

    Loveland, CO · about 23 miles

    Certified for bacteria

  • M.M.S Environmental Laboratories

    Fort Collins, CO · about 23 miles

    Certified for bacteria

  • Technology Laboratory, Inc.

    Fort Collins, CO · about 23 miles

    Certified for nitrate, minerals and other inorganics, organic chemicals

All 54 certified labs for Colorado

Sources

PWSID CO0135610. Rebuilt from EPA data on Oct. 18, 2026.