Homestead WC
What EPA’s and Colorado’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 1,000 people
- Connections
- 336
- Water source
- Surface water
- Based in
- Evergreen, CO
- County
- Jefferson
- Owner
- Private
The ZIP code it serves
The short answer
1 result is above EPA’s legal limit, and 3 more are above the health goal. The worst: Copper, above the action level. 17 health-based violations since 2016.
What handles itWhat was found
Lead and copper: EPA SDWIS monitoring periods ending 2009 to 2023.
Uranium, arsenic, total trihalomethanes (TTHM), fluoride, nitrate, haloacetic acids (HAA5) and chromium (total): Colorado’s own results, samples taken from Feb. 4, 2020 to Aug. 10, 2026, with EPA’s 2012 to 2019 file for earlier years.
Above the legal limit1
Copper
Comes from pipes, often your own
1.4ppm
90th percentile, 2023
In the latest period, 9 in 10 homes sampled were at or below 1.4 ppm, above EPA’s action level of 1.3 ppm.
What handles it
- NSF/ANSI 53 look for “Copper Reduction”
- NSF/ANSI 58 look for “Copper Reduction”
Above the health goal3
Uranium
Comes from the source
19.3ppb
Highest yearly average, 2020 to 2026
2026 average: 1.1 ppb
Averaged by year, the highest was 19.3 ppb, in 2020: below EPA’s legal limit of 30 ppb, but above its health goal of zero. Its highest single sample was 61 ppb. In 2026, the latest year on file, its six samples averaged 1.1 ppb. EPA recorded no violation for uranium at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 12.2 ppb, in 2019.
What handles it
- NSF/ANSI 58 look for “Uranium”
Arsenic
Comes from the source
0.67ppb
Highest yearly average, 2020 to 2026
2026: not found
Averaged by year, the highest was 0.67 ppb, in 2022: below EPA’s legal limit of 10 ppb, but above its health goal of zero. Its highest single sample was 2.0 ppb. In 2026, the latest year on file, it wasn’t found in any of its three samples. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.3 ppb, in 2019.
What handles it
- NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
- NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
Lead
Comes from pipes, often your own
1.0ppb
90th percentile, 2026
In the latest period, 9 in 10 homes sampled were at or below 1.0 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53 look for “Lead Reduction”
- NSF/ANSI 58 look for “Lead Reduction”
Below EPA’s limits5
Total trihalomethanes (TTHM)
Forms or is added in treatment
59.6ppb
Highest yearly average, 2020 to 2026
2026 average: 24.2 ppb
Averaged by year, the highest was 59.6 ppb, in 2022, below EPA’s legal limit of 80 ppb. Its highest single sample was 93.7 ppb. In 2026, the latest year on file, its four samples averaged 24.2 ppb. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 50.2 ppb, in 2017.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Fluoride
Forms or is added in treatment
1.6ppm
Highest yearly average, 2020 to 2026
2026 average: 0.82 ppm
Averaged by year, the highest was 1.6 ppm, in 2021, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 2.9 ppm. In 2026, the latest year on file, its three samples averaged 0.82 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 2.2 ppm, in 2013.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Nitrate
Comes from the source
2.2ppm
Highest sample; found in 18 of 21
2026 average: 0.2 ppm
The highest sample, in 2024, was 2.2 ppm, below EPA’s legal limit of 10 ppm. In 2026, the latest year on file, its three samples averaged 0.2 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 2.3 ppm, in 2016.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
Haloacetic acids (HAA5)
Forms or is added in treatment
10.4ppb
Highest yearly average, 2020 to 2026
2026 average: 2.4 ppb
Averaged by year, the highest was 10.4 ppb, in 2023, below EPA’s legal limit of 60 ppb. Its highest single sample was 14.3 ppb. In 2026, the latest year on file, its four samples averaged 2.4 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 14.6 ppb, in 2015.
What handles it
No certification claim covers this compound yet.
Chromium (total)
Comes from the source
3.3ppb
Highest yearly average, 2020 to 2026
2026 average: 0.67 ppb
Averaged by year, the highest was 3.3 ppb, in 2025, below EPA’s legal limit of 100 ppb. Its highest single sample was 5.0 ppb. In 2026, the latest year on file, its three samples averaged 0.67 ppb. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 1.7 ppb, in 2019.
What handles it
- NSF/ANSI 58 look for “Chromium (Hexavalent) Reduction”
- NSF/ANSI 53 look for “Chromium Reduction”
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”
- NSF/ANSI 53
Claims: Copper Reduction, Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction
For: Copper, Arsenic, Lead
Other certifiers’ wording: Arsenic (III) (50 ppb influent level)
- NSF/ANSI 58
Claims: Copper Reduction, Uranium, Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction
For: Copper, Uranium, Arsenic, Lead
Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)
At the tap, or for the whole house?
Lead and copper usually come from pipes and fixtures inside or near your home. A whole-house system sits where water enters, so it cannot catch what your own plumbing adds after it. For those, the filter that counts is the one at the tap. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
Aquasana SmartFlow Reverse Osmosis (AQ-SFRO2)
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Arsenic, Lead
Brondell Capella RC250 Reverse Osmosis System
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Copper, Arsenic, Lead
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 58checked Oct. 9, 2026
Certified for: Copper, Arsenic, Lead
Countertop reverse osmosis
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 4, 2026
Certified for: Copper, Arsenic, Lead
PUR PLUS 11-Cup Pitcher (PPT111W)
Pitcher
- NSF listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 401checked Oct. 4, 2026
Certified for: Copper, Lead
Violations since 2016
| Contaminant or rule | Type | Period | Measured | Status |
|---|---|---|---|---|
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2024 to Sept. 30, 2024 | 20 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2024 to June 30, 2024 | 17.1 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2024 to March 31, 2024 | 22.7 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2023 to Dec. 31, 2023 | 15.5 PCI/L | Resolved |
| Lead and Copper Rule | Water chemistry used to keep pipes from corroding was outside the required range.EPA: WQP Entry Point/Tap Treatment Technique Non-Compliance | July 1, 2023 to Dec. 31, 2023 | — | Archived |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2022 to June 30, 2022 | 17.3 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2022 to March 31, 2022 | 20 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2021 to Dec. 31, 2021 | 20 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2021 to Sept. 30, 2021 | 21 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2021 to June 30, 2021 | 29 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2021 to March 31, 2021 | 39 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2020 to Dec. 31, 2020 | 40.6 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2020 to Sept. 30, 2020 | 40 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2020 to June 30, 2020 | 29 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2020 to March 31, 2020 | 18.5 PCI/L | Resolved |
| Gross alpha radiation (excluding radon and uranium) | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2019 to Dec. 31, 2019 | 17 PCI/L | Resolved |
| Surface Water Treatment Rule | Required treatment for surface water or groundwater was not met.EPA: Treatment Technique (SWTR and GWR) | April 1, 2017 to April 30, 2017 | — | Resolved |
| Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 20 monitoring or reporting violations not shown. | ||||
What this report can’t tell you
Everything else. Uranium, arsenic, total trihalomethanes (TTHM), fluoride, nitrate, haloacetic acids (HAA5) and chromium (total) results here are Colorado’s own from 2020 on, with EPA’s national file for 2012 to 2019. Homestead WC’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; Colorado’s results run from Feb. 4, 2020 to Aug. 10, 2026.
Testing your own tap
The 3 labs Colorado certifies closest to the area Homestead WC serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
SGS North America, Inc. - Wheat Ridge
Wheat Ridge, CO · about 13 miles
Certified for nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, radioactivity
GeoWater Services
Evergreen, CO · about 13 miles
Certified for bacteria
Eurofins Denver
Arvada, CO · about 14 miles
Certified for nitrate, minerals and other inorganics, organic chemicals, PFAS
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- Colorado Department of Public Health and Environment, Water Quality Control Division, results from Jan. 3, 2020 to Oct. 6, 2026, read Oct. 17, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Certified labs: CDPHE certified drinking water laboratories, read Oct. 16, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID CO0130050. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Read up on the 4 results above a lineWhat each one does to health, where it comes from, and the certification claim that addresses it.Start with Copper
- Get the utility’s own reportHomestead WC must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Compare certified filtersWhat the filters certified for these results cost over five years, cartridges included.Compare five-year costs