Two Twenty Four Mobile Home Pk
What EPA’s and California’s records show in this utility’s water: nitrate, arsenic and other regulated chemicals; lead and copper; and violations since 2016, with the certification that handles each result.
- Serves
- 35 people
- Connections
- 16
- Water source
- Groundwater
- Based in
- Clovis, CA
- County
- Madera
- Owner
- Private
- Hardness
- Moderately hard
The ZIP code it serves
The short answer
1 result is above EPA’s legal limit, and 1 more is above the health goal. The worst: Uranium, above the legal limit. 26 health-based violations since 2016.
What handles itWhat was found
Uranium, arsenic, nitrate, fluoride and chromium (total): California’s own results, samples taken from April 7, 2020 to June 30, 2026, with EPA’s 2012 to 2019 file for earlier years.
Above the legal limit1
Uranium
Comes from the source
363ppb
Highest yearly average, 2020 to 2026
2026 average: 220 ppb
Averaged by year, the highest was 363 ppb, in 2020, about 12 times EPA’s legal limit of 30 ppb. Its highest single sample was 507 ppb. In 2026, the latest year on file, its four samples averaged 220 ppb, above the limit. EPA recorded violations for uranium at this utility in 2020, 2021, 2022, 2023, 2024 and 2025. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 193 ppb, in 2019, and EPA recorded violations in 2012, 2013, 2015, 2016, 2017, 2018 and 2019.
What handles it
- NSF/ANSI 58 look for “Uranium”
Above the health goal1
Arsenic
Comes from the source
9.5ppb
Highest yearly average, 2020 to 2025
Averaged by year, the highest was 9.5 ppb, in 2025: below EPA’s legal limit of 10 ppb, but above its health goal of zero. Its highest single sample was 11 ppb. That was also the latest year on file. EPA recorded no violation for arsenic at this utility since 2020. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 8.4 ppb, in 2018.
What handles it
- NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
- NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
Below EPA’s limits2
Nitrate
Comes from the source
7.3ppm
Highest sample; found in 7 of 7
2025, one sample: 0.79 ppm
The highest sample, in 2023, was 7.3 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its one sample was 0.79 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest sample of 1.1 ppm, in 2018.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
Fluoride
Forms or is added in treatment
0.47ppm
Highest yearly average, 2022 to 2025
2025, one sample: 0.39 ppm
Averaged by year, the highest was 0.47 ppm, in 2022, below EPA’s legal limit of 4.0 ppm. In 2025, the latest year on file, its one sample was 0.39 ppm. Earlier, from 2012 to 2019, EPA’s file shows a highest yearly average of 0.26 ppm, in 2019.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
- Chromium (total)
- Lead
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box. Wording varies a little: NSF writes “Lead Reduction,” WQA just “Lead.”
- NSF/ANSI 53
Claim: Arsenic (Pentavalent)<=50 ppb Reduction
For: Arsenic
Other certifiers’ wording: Arsenic (III) (50 ppb influent level)
- NSF/ANSI 58
Claims: Uranium, Arsenic (Pentavalent)<=50 ppb Reduction
For: Uranium, Arsenic
Other certifiers’ wording: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)
At the tap, or for the whole house?
These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
Countertop reverse osmosis
- IAPMO listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 4, 2026
Certified for: Arsenic
Aquasana SmartFlow Reverse Osmosis (AQ-SFRO2)
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Arsenic
Brondell Capella RC250 Reverse Osmosis System
Under-sink reverse osmosis
- WQA listing:NSF/ANSI 42NSF/ANSI 53NSF/ANSI 58NSF/ANSI 401checked Oct. 9, 2026
Certified for: Arsenic
Hardness
Moderately hard, 120 mg/L (7 grains per gallon), at its one sampling point, 2019 to 2025.
Hardness is calcium and magnesium. EPA sets no limit for it: it shows up as scale on fixtures and in water heaters, and as soap that won’t lather. USGS calls water above 60 mg/L moderately hard, above 120 hard and above 180 very hard.
Violations since 2016
| Contaminant or rule | Type | Period | Measured | Status |
|---|---|---|---|---|
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2025 to Dec. 31, 2025 | 155 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2025 to Sept. 30, 2025 | 163 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2025 to June 30, 2025 | 233 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2025 to March 31, 2025 | 288 PCI/L | Resolved |
| Lead and Copper Rule Revisions | The required inventory of lead service lines was not completed or submitted on time.EPA: LSL Inventory | Oct. 17, 2024 | — | Unaddressed |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2024 to Dec. 31, 2024 | 203 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2024 to Sept. 30, 2024 | 127 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2024 to June 30, 2024 | 122 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2024 to March 31, 2024 | 88.8 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2023 to Dec. 31, 2023 | 93 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2023 to Sept. 30, 2023 | 248 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | April 1, 2023 to June 30, 2023 | 115 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2023 to March 31, 2023 | 129 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2022 to Dec. 31, 2022 | 183 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2021 to Dec. 31, 2021 | 188 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2020 to Dec. 31, 2020 | 240 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2019 to Dec. 31, 2019 | 89 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | July 1, 2019 to Sept. 30, 2019 | 130 PCI/L | Resolved |
| Combined Uranium | A sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single Sample | April 1, 2019 to June 30, 2019 | 170 PCI/L | Resolved |
| Combined Uranium | A sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single Sample | Jan. 1, 2019 to March 31, 2019 | 220 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2018 to Dec. 31, 2018 | 196 PCI/L | Resolved |
| Combined Uranium | A sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single Sample | Oct. 1, 2017 to Dec. 31, 2017 | 180 PCI/L | Resolved |
| Combined Uranium | A sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single Sample | July 1, 2017 to Sept. 30, 2017 | 340 PCI/L | Resolved |
| Combined Uranium | A sample was above the legal limit, for a contaminant judged one sample at a time.EPA: Maximum Contaminant Level Violation, Single Sample | April 1, 2017 to June 30, 2017 | 67 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Oct. 1, 2016 to Dec. 31, 2016 | 140 PCI/L | Resolved |
| Combined Uranium | The running average was above the legal limit.EPA: Maximum Contaminant Level Violation, Average | Jan. 1, 2016 to Dec. 31, 2016 | 183 PCI/L | Resolved |
| Health-based violations only. Resolved and archived mean the utility returned to compliance or the state closed the record. 6 monitoring or reporting violations not shown. | ||||
What this report can’t tell you
Everything else. Uranium, arsenic, nitrate, fluoride and chromium (total) results here are California’s own from 2020 on, with EPA’s national file for 2012 to 2019. Two Twenty Four Mobile Home Pk’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; California’s results run from April 7, 2020 to June 30, 2026.
Testing your own tap
The 3 labs California certifies closest to the area Two Twenty Four Mobile Home Pk serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
SGS North America, Inc.
Clovis, CA · about 28 miles
Certified for nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS
BSK Associates
Fresno, CA · about 35 miles
Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, disinfection byproducts, PFAS, radioactivity
Dellavalle Laboratory, Inc.
Fresno, CA · about 38 miles
Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, radioactivity
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- California State Water Resources Control Board, Division of Drinking Water, results from Jan. 1, 2020 to July 17, 2026, read Oct. 8, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Certified labs: California State Water Resources Control Board, ELAP accredited laboratories and their fields of accreditation, read Oct. 17, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Hardness: California State Water Resources Control Board, Division of Drinking Water, results from June 14, 2019 to Dec. 23, 2025, read Oct. 10, 2026
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID CA2000592. Rebuilt from EPA data on Oct. 18, 2026.
What to do next
- Read up on the 2 results above a lineWhat each one does to health, where it comes from, and the certification claim that addresses it.Start with Uranium
- Get the utility’s own reportTwo Twenty Four Mobile Home Pk must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
- Compare certified filtersWhat the filters certified for these results cost over five years, cartridges included.Compare five-year costs