Skip to content
TapBuff

Pine Grove Water

EPA’s and West Virginia’s records have results for 7 contaminants in its water; 5 were found.

Serves 620 people · Surface water · Pine Grove, WV

Serves
620 people
Connections
240
Water source
Surface water
Based in
Pine Grove, WV
County
Wetzel
Owner
Local government
The 2 ZIP codes it serves

26167, 26419

The short answer

None of the results here is above a limit in force today. That covers nitrate, arsenic and other regulated chemicals, plus lead and copper, not everything. 5 health-based violations since 2016, 1 with no fix on record in EPA’s file.

The 5 violations⁠Got a notice? What it means⁠

What was found

Where these results come from, and when

Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, chromium (total) and arsenic: West Virginia’s own results, samples taken from Feb. 12, 2020 to Aug. 25, 2026, with EPA’s 2012 to 2019 file for earlier years.

What the lines mean
Legal limit (MCL):
Enforceable. The most a utility may deliver.
Health goal (MCLG):
Not enforceable. The level with no expected risk, with a margin of safety.

Below EPA’s limits, 5 results

Legal limit (MCL):
Enforceable. The most a utility may deliver.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 45 ppb

Highest yearly average, 2020 to 2026 · 2026 average: 16.4 ppb · Forms or is added in treatment

Averaged by year, the highest was 45 ppb, in 2022, below EPA’s legal limit of 80 ppb. Its highest single sample was 142 ppb. In 2026, the latest year on file, its two samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 58.4 ppb, in 2017.

What handles it

  • NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
  • NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
About total trihalomethanes (TTHM)
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 26.3 ppb

Highest yearly average, 2020 to 2026 · 2026 average: 9.5 ppb · Forms or is added in treatment

Averaged by year, the highest was 26.3 ppb, in 2023, below EPA’s legal limit of 60 ppb. Its highest single sample was 43.2 ppb. In 2026, the latest year on file, its two samples averaged below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 51.9 ppb, in 2017.

What handles it

No certification claim covers this compound yet.

About haloacetic acids (HAA5)
Fluoride, Legal limit 4.0 ppm; highest yearly average 0.27 ppm

Highest yearly average, 2020 to 2025 · Forms or is added in treatment

Averaged by year, the highest was 0.27 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. That was also the latest year on file.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 0.75 ppm, in 2017.

What handles it

About fluoride
Nitrate, Legal limit 10 ppm; highest 0.47 ppm

Highest sample; found in 3 of 3 · 2022, one sample: 0.24 ppm · Comes from the source

The highest sample, in 2020, was 0.47 ppm, below EPA’s legal limit of 10 ppm. In 2022, the latest year on file, its one sample was below the limit.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest sample of 0.99 ppm, in 2019.

What handles it

  • NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
  • NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
About nitrate
Chromium (total), Legal limit 100 ppb; highest yearly average 1.1 ppb

Highest yearly average, 2020 to 2025 · 2025: not found · Comes from the source

Averaged by year, the highest was 1.1 ppb, in 2022, below EPA’s legal limit of 100 ppb. In 2025, the latest year on file, it wasn’t found in its one sample.

Earlier, 2012 to 2019

From 2012 to 2019, EPA’s file shows a highest yearly average of 1.0 ppb, in 2016.

What handles it

About chromium (total)
2 compounds tested and not foundBelow the reporting level in every sample. Not found is not the same as zero.
  • Arsenic
  • Lead

Violations since 2016

5 health-based violations since 2016, 2 for the Long Term 2 Enhanced Surface Water Treatment Rule, 2 for total organic carbon and 1 for the Interim Enhanced Surface Water Treatment Rule. The latest began July 17, 2025, and 1 has no fix on record in EPA’s file.

Resolved:
EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
No fix on record:
It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).

EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.

Got a notice about one? What it means and what to do⁠
Health-based violations, newest first
Contaminant or ruleWhat happenedPeriod, and what was measuredStatus
Long Term 2 Enhanced Surface Water Treatment RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyJuly 17, 2025No fix on recordEPA: unaddressed
Total organic carbonNot enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor RemovalJuly 1, 2025 to Sept. 30, 2025, 0.99 RATIOResolved
Jan. 1, 2025 to March 31, 2025, 0.92 RATIOResolved
Long Term 2 Enhanced Surface Water Treatment RuleA significant problem found in a state inspection was not fixed on time.EPA: Failure To Address DeficiencyJuly 6, 2019Resolved
Interim Enhanced Surface Water Treatment RuleToo many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR)Aug. 1, 2017 to Aug. 31, 2017Resolved

Health-based violations only. 94 monitoring or reporting violations not shown.

What this report can’t tell you

  • Everything else. Total trihalomethanes (TTHM), haloacetic acids (HAA5), fluoride, nitrate, chromium (total) and arsenic results here are West Virginia’s own from 2020 on, with EPA’s national file for 2012 to 2019. Pine Grove Water’s own annual report, which it must send you every year, has the contaminants this page does not show.

  • Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.

  • What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.

  • Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 didn’t sample this utility; West Virginia’s results run from Feb. 12, 2020 to Aug. 25, 2026.

Testing your own tap

Pine Grove Water’s results are for the water it sends out. What your own service line, solder and fixtures add shows up only in a test of your tap, by a lab West Virginia certifies.

What to test for at your tap

  • Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Pine Grove Water’s latest lead sampling in EPA’s records, 2026, had a 90th percentile of 0 ppb across the homes it sampled. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
The 3 labs West Virginia certifies closest to the area Pine Grove Water serves, or a kit by mail

The 3 labs West Virginia certifies closest to the area Pine Grove Water serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.

  • Sturm Environmental Services

    Bridgeport, WV · about 31 miles

    Certified for bacteria

  • Pace Analytical Services, LLC - Morgantown WV

    Morgantown, WV · about 37 miles

    Certified for bacteria

  • Microbac Laboratories Inc., Ohio Valley Division

    Marietta, OH · about 38 miles

    Certified for nitrate, lead and copper, metals, minerals and other inorganics, organic chemicals, PFAS

All 50 certified labs for West Virginia⁠

Or test by mail

Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that West Virginia certifies it for the test you want.

  • Tap Score

    Return shipping included.

    Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against West Virginia’s list.

Prices from Tap Score’s own store on Oct. 22, 2026.

What to do now

Sources

PWSID WV3305205. Rebuilt from EPA data on Oct. 25, 2026.