Lincoln PSD
EPA’s and West Virginia’s records have results for 38 contaminants in its water; 8 were found.
Serves 3,981 people · Surface water · Alum Creek, WV
- Serves
- 3,981 people
- Connections
- 1,588
- Water source
- Surface water
- Based in
- Alum Creek, WV
- County
- Lincoln
- Owner
- Local government
The short answer
None of the results here is above a limit in force today. Lithium is above EPA’s health benchmark. 19 health-based violations since 2016, 6 with no fix on record in EPA’s file.
This is what the records show, not medical advice. Worried about a health effect? Talk to a doctor or your local health department.
Filters for arsenic and lead, if you want them lowerThe 19 violationsGot a notice? What it means
What was found
Where these results come from, and when
PFAS and lithium: EPA UCMR 5, samples taken from Feb. 4 to Oct. 20, 2025.
Lead and copper: EPA SDWIS monitoring periods ending 2013 to 2024.
Total trihalomethanes (TTHM), fluoride, haloacetic acids (HAA5), arsenic, nitrate, chromium (total) and uranium: West Virginia’s own results, samples taken from Feb. 24, 2020 to Aug. 5, 2026, with EPA’s 2012 to 2019 file for earlier years.
What the lines mean
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Action level:
- Triggers action. If more than 10% of homes sampled are above it, the utility must act.
- 90th percentile:
- How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
- Health goal (MCLG):
- Not enforceable. The level with no expected risk, with a margin of safety.
- Health reference level:
- A screening level from EPA’s work on whether to regulate a contaminant, where there is no legal limit or health goal; not enforceable.
PFAS: None of the six PFAS in EPA’s 2024 drinking water rule was found in this utility’s samples. None of the other 23 PFAS tested for was found either.
Above EPA’s health benchmark, 1 result
Lithium
Comes from the source
64.5 ppb
Highest sample, Oct. 20, 2025; found in 4 of 4
The highest sample was 64.5 ppb, about 6.5 times EPA’s health reference level of 10 ppb. That is a screening level, not an enforceable limit.
What handles it
No filter certification covers lithium yet, and EPA’s 2023 fact sheet says boiling doesn’t remove it. Because it was found, your utility has to report its lithium results in its annual water quality report, where newer ones will appear.
How to read your utility’s reportBelow EPA’s limits, 7 results
Arsenic and lead have a health goal of zero: the level with no known or expected risk. Any amount found is above it, but the goal isn’t a limit.
- Legal limit (MCL):
- Enforceable. The most a utility may deliver.
- Action level:
- Triggers action. If more than 10% of homes sampled are above it, the utility must act.
- 90th percentile:
- How a lead or copper result is held against its action level: nine in ten of the homes sampled were at or below it.
Total trihalomethanes (TTHM), Legal limit 80 ppb; highest yearly average 49.3 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 35.3 ppb · Forms or is added in treatment
Averaged by year, the highest was 49.3 ppb, in 2024, below EPA’s legal limit of 80 ppb. Its highest single sample was 125 ppb. In 2026, the latest year on file, its six samples averaged below the limit. EPA recorded no violation for total trihalomethanes (TTHM) at this utility since 2020.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 71.3 ppb, in 2016.
What handles it
- NSF/ANSI 53 look for “Trihalomethanes (TTHM) Reduction”
- NSF/ANSI 58 look for “Trihalomethanes (TTHM) Reduction”
Fluoride, Legal limit 4.0 ppm; highest yearly average 2.1 ppm
Highest yearly average, 2020 to 2025 · Forms or is added in treatment
Averaged by year, the highest was 2.1 ppm, in 2025, below EPA’s legal limit of 4.0 ppm. Its highest single sample was 3.9 ppm. That was also the latest year on file.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 1.1 ppm, in 2012.
What handles it
- NSF/ANSI 58 look for “Fluoride Reduction”
- NSF/ANSI 53 look for “Fluoride”
Haloacetic acids (HAA5), Legal limit 60 ppb; highest yearly average 26.5 ppb
Highest yearly average, 2020 to 2026 · 2026 average: 14.3 ppb · Forms or is added in treatment
Averaged by year, the highest was 26.5 ppb, in 2022, below EPA’s legal limit of 60 ppb. Its highest single sample was 50.5 ppb. In 2026, the latest year on file, its six samples averaged below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 28.6 ppb, in 2016.
What handles it
No certification claim covers this compound yet.
Arsenic, Legal limit 10 ppb · health goal zero; highest yearly average 2.7 ppb
Highest yearly average, 2020 to 2025 · 2025: not found · Comes from the source
Averaged by year, the highest was 2.7 ppb, in 2023, below EPA’s legal limit of 10 ppb. Its health goal is zero, so any amount found is above it; the goal isn’t a limit. In 2025, the latest year on file, it wasn’t found in its one sample.
What handles it
- NSF/ANSI 58 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
- NSF/ANSI 53 look for “Arsenic (Pentavalent)<=50 ppb Reduction”
Nitrate, Legal limit 10 ppm; highest 0.69 ppm
Highest sample; found in 6 of 7 · 2025, one sample: 0.056 ppm · Comes from the source
The highest sample, in 2024, was 0.69 ppm, below EPA’s legal limit of 10 ppm. In 2025, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest sample of 2.3 ppm, in 2012.
What handles it
- NSF/ANSI 58 look for “Nitrate/Nitrite Reduction”
- NSF/ANSI 53 look for “Nitrate/Nitrite (30 ppm challenge)”
Lead, Action level 15 ppb · health goal zero; 90th percentile 0.8 ppb
90th percentile, 2024 · Comes from pipes, often your own
In the latest period, 9 in 10 homes sampled were at or below 0.8 ppb, below EPA’s action level of 15 ppb. The action level drops to 10 ppb on Nov. 1, 2027. EPA’s health goal for lead is zero.
What handles it
- NSF/ANSI 53 look for “Lead Reduction”
- NSF/ANSI 58 look for “Lead Reduction”
Chromium (total), Legal limit 100 ppb; highest yearly average 4.5 ppb
Highest yearly average, 2020 to 2025 · 2025, one sample: 2.6 ppb · Comes from the source
Averaged by year, the highest was 4.5 ppb, in 2023, below EPA’s legal limit of 100 ppb. In 2025, the latest year on file, its one sample was below the limit.
Earlier, 2012 to 2019
From 2012 to 2019, EPA’s file shows a highest yearly average of 4.1 ppb, in 2016.
What handles it
- NSF/ANSI 58 look for “Chromium (Hexavalent) Reduction”
- NSF/ANSI 53 look for “Chromium Reduction”
30 compounds tested and not foundIncluding all six PFAS in EPA’s 2024 rule. Below the reporting level in every sample. Not found is not the same as zero.
From routine monitoring
- Uranium
PFAS and lithium, from EPA’s UCMR 5 sampling
- 11Cl-PF3OUdS
- 4:2 FTS
- 6:2 FTS
- 8:2 FTS
- 9Cl-PF3ONS
- ADONA
- HFPO-DA (GenX)
- NEtFOSAA
- NFDHA
- NMeFOSAA
- PFBA
- PFBS
- PFDA
- PFDoA
- PFEESA
- PFHpA
- PFHpS
- PFHxA
- PFHxS
- PFMBA
- PFMPA
- PFNA
- PFOA
- PFOS
- PFPeA
- PFPeS
- PFTA
- PFTrDA
- PFUnA
Violations since 2016
19 health-based violations since 2016, 10 for the Interim Enhanced Surface Water Treatment Rule, 5 for total organic carbon, 2 for the Long Term 2 Enhanced Surface Water Treatment Rule, 1 for the Lead and Copper Rule and 1 for the Stage 1 Disinfectants and Disinfection Byproducts Rule. The latest began April 1, 2026, and 6 have no fix on record in EPA’s file.
- Resolved:
- EPA’s file records a resolving action. The utility came back into compliance, the rule no longer applied, or no further action was needed.
- No fix on record:
- It records none. EPA’s own word for these is archived, addressed or unaddressed, shown beside each (EPA’s definitions, updated Oct. 9, 2026).
EPA’s file runs to 2026 Q3, so a notice your utility sent since then may not be here yet.
Got a notice about one? What it means and what to do| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Total organic carbon | Not enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor Removal | April 1, 2026 to June 30, 2026, 0.67 RATIO | No fix on recordEPA: archived |
| Interim Enhanced Surface Water Treatment Rule | Too many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR) | March 1, 2026 to March 31, 2026 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | One cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR) | Feb. 1, 2026 to Feb. 28, 2026 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | Too many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR) | Feb. 1, 2026 to Feb. 28, 2026 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | One cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR) | Jan. 1, 2026 to Jan. 31, 2026 | Resolved |
The other 14, back to 2018
| Contaminant or rule | What happened | Period, and what was measured | Status |
|---|---|---|---|
| Interim Enhanced Surface Water Treatment Rule | Too many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR) | Jan. 1, 2026 to Jan. 31, 2026 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | One cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR) | Dec. 1, 2025 to Dec. 31, 2025 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | Too many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR) | Dec. 1, 2025 to Dec. 31, 2025 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | One cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR) | Nov. 1, 2025 to Nov. 30, 2025 | Resolved |
| Lead and Copper Rule | OCCT/SOWT Treatment Installation/Demonstration | Oct. 1, 2025 | No fix on recordEPA: unaddressed |
| Interim Enhanced Surface Water Treatment Rule | One cloudiness reading was above the maximum allowed.EPA: Single Turbidity Exceed (Enhanced SWTR) | April 1, 2025 to April 30, 2025 | Resolved |
| Interim Enhanced Surface Water Treatment Rule | Too many readings in a month showed cloudiness above the filtration standard.EPA: Monthly Turbidity Exceed (Enhanced SWTR) | April 1, 2025 to April 30, 2025 | Resolved |
| Long Term 2 Enhanced Surface Water Treatment Rule | A significant problem found in a state inspection was not fixed on time.EPA: Failure To Address Deficiency | Aug. 1, 2023 | No fix on recordEPA: unaddressed |
| Aug. 1, 2023 | No fix on recordEPA: unaddressed | ||
| Total organic carbon | Not enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor Removal | July 1, 2020 to Sept. 30, 2020 | Resolved |
| Jan. 1, 2020 to March 31, 2020 | Resolved | ||
| Stage 1 Disinfectants and Disinfection Byproducts Rule | Treatment was not run by a certified operator as required.EPA: Treatment Technique No Certif. Operator | June 18, 2019 | Resolved |
| Total organic carbon | Not enough organic matter was removed. It reacts with disinfectant to form byproducts.EPA: Treatment Technique Precursor Removal | Oct. 1, 2018 to Dec. 31, 2018 | No fix on recordEPA: archived |
| July 1, 2018 to Sept. 30, 2018 | No fix on recordEPA: archived |
Health-based violations only. 187 monitoring or reporting violations not shown.
What handles it
A certification covers specific claims, not a whole standard. Look for these claims on the certifier’s listing, not the box.
- NSF/ANSI 53
Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction
For: Arsenic, Lead
Other claims that cover it: Arsenic (III) (50 ppb influent level)
- NSF/ANSI 58
Claims: Arsenic (Pentavalent)<=50 ppb Reduction, Lead Reduction
For: Arsenic, Lead
Other claims that cover it: Arsenic (Pentavalent)<=300 ppb Reduction; Arsenic (V) (300 ppb influent level)
At the tap, or for the whole house?
These come with the water itself, so a whole-house system certified for the same claims treats every tap and shower. A filter at the tap treats drinking water for much less. How whole-house systems compare.
Filters with those claims on a certifier’s listing
Disclosure: TapBuff earns a commission if you buy through some links on this page. It does not change which standard or filter we name. As an Amazon Associate, TapBuff earns from qualifying purchases. How TapBuff makes money
Under-sink reverse osmosis
Five years: $549, household of 3, cartridges included
WQA listing: NSF/ANSI 58, checked Oct. 9, 2026
Certified for: Arsenic, Lead
Countertop reverse osmosis
Five years: $1,344, household of 3, cartridges included
Certified for: Arsenic, Lead
Brondell Capella RC250 Reverse Osmosis System
Under-sink reverse osmosis
Five years: $1,950, household of 3, cartridges included
Certified for: Arsenic, Lead
2 more filters
Aquasana SmartFlow Reverse Osmosis (AQ-SFRO2)
Under-sink reverse osmosis
Five years: $2,917, household of 3, cartridges included
Certified for: Arsenic, Lead
Express Water StreamLine Direct Connect System (USC001)
Under-sink carbon
Five years: $527, household of 3, cartridges included
Certified for: Lead
Every filter for these, those that cover both first
Disinfectant
Lincoln PSD reported disinfecting with chlorine, not chloramine, at its one sampling point, in its 2025 sampling for EPA.
What that means
Chlorine leaves water that sits out for a few days, CDC says. A filter certified for it carries a chlorine claim under NSF/ANSI 42; a shower filter, a free chlorine claim under NSF/ANSI 177. This is what the utility reported for that sampling. Its annual water quality report says what it uses now.
What this report can’t tell you
Everything else. Total trihalomethanes (TTHM), fluoride, haloacetic acids (HAA5), arsenic, nitrate, chromium (total) and uranium results here are West Virginia’s own from 2020 on, with EPA’s national file for 2012 to 2019. Lincoln PSD’s own annual report, which it must send you every year, has the contaminants this page does not show.
Your own plumbing. Lead results are the 90th percentile across homes the utility samples. Your home’s service line, solder and fixtures decide yours. A certified lab test is the only way to know.
What it means for your health. This page reports what the records show and EPA’s limits and goals; it is not medical advice. If you are worried about a health effect, talk to a doctor or your local health department.
Anything after the latest data. SDWIS data is from 2026 Q3; UCMR 5 samples are from Feb. 4 to Oct. 20, 2025; West Virginia’s results run from Feb. 24, 2020 to Aug. 5, 2026.
Testing your own tap
What to test for at your tap
- Lead and copper. Both come mostly from a building’s own service line, solder and faucets, so a utility’s numbers can’t tell you yours. Lincoln PSD’s latest lead sampling in EPA’s records, 2024, had a 90th percentile of 0.8 ppb: 9 in 10 of the homes it sampled were at or below that. The action level is 15 ppb, dropping to 10 ppb in November 2027, and EPA’s health goal for lead is zero. About lead.
- What Lincoln PSD’s results flag: lithium. It is in the water the utility sends out, so a test of your tap mostly confirms it. Include it if you want a number for your own home.
The 3 labs West Virginia certifies closest to the area Lincoln PSD serves, or a kit by mail
The 3 labs West Virginia certifies closest to the area Lincoln PSD serves, in a straight line. Call first: certification is test by test, and not every lab takes samples from homeowners.
West Virginia Dept. of Health - Office of Lab Services, Chemistry
Charleston, WV · about 21 miles
Certified for nitrate, lead and copper, metals, minerals and other inorganics, disinfection byproducts
West Virginia Dept. of Health - Office of Lab Services, Microbiology
Charleston, WV · about 21 miles
Certified for bacteria
Analabs, Inc.
Crab Orchard, WV · about 48 miles
Certified for bacteria, nitrate, lead and copper, metals, minerals and other inorganics, disinfection byproducts
Or test by mail
Tap Score sells lab tests as kits you fill at your tap and mail back. The sample goes to Tap Score’s lab, not one near you, so check that West Virginia certifies it for the test you want.
Tap Score
- Lead and Copper Water Test, with a pH test strip: $55
- Essential City Water Test, 25 metals, 4 minerals, nitrate, fluoride, hardness and pH: $189
Return shipping included.
Tap Score says each kit ships to “an accredited laboratory” but doesn’t name it, so TapBuff can’t check it against West Virginia’s list.
Prices from Tap Score’s own store on Oct. 22, 2026.
What to do now
- Read up on lithiumWhat it does to health, where it comes from, and the certification claim that addresses it.About lithium
- Get the utility’s own reportLincoln PSD must send you a water quality report every year. It covers contaminants this page does not show.How to read it
- Test your own tap for leadYour service line, solder and fixtures decide the lead at your faucet, not the utility’s average.Lead in your water: what to do
Sources
- EPA UCMR 5 occurrence data, file of Oct. 15, 2026
- EPA SDWA bulk download (SDWIS federal data), 2026 Q3
- West Virginia Department of Health, Drinking Water Viewer, results from Jan. 3, 2020 to Oct. 15, 2026, read Oct. 25, 2026
- EPA Six-Year Review 4 compliance monitoring data, 2012 to 2019, file of Feb. 5, 2024
- Disinfectant: EPA UCMR 5 occurrence data, additional data elements, file of Oct. 15, 2026
- Certified labs: West Virginia Office of Laboratory Services, laboratory certified parameter list, read Oct. 11, 2026; distances from the Census 2020 ZIP code tabulation area gazetteer
- Limits and goals: each contaminant’s page, with its EPA source.
- How this page is built: methodology.
PWSID WV3302205. Rebuilt from EPA data on Oct. 25, 2026.